Plan Review Details - Permit 20041095
Plan Review Stops For Permit 20041095
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-05-21 Cont ID  
Sent By cthroop Date 2020-05-21 Time 10:02 Rev Time 0.00
Received By cthroop Date 2020-05-20 Time 14:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-06 Cont ID  
Sent By cthroop Date 2020-05-06 Time 11:08 Rev Time 0.00
Received By cthroop Date 2020-05-06 Time 09:22 Sent To  
Notes
2020-05-06 11:11:04CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CUSTOM DOORS SHALL COMPLY WITH FBC SEC. 1709.5. (SEE
 EXCEPTION)
  
  
 1709.5 EXTERIOR WINDOW AND DOOR ASSEMBLIES.
 THE DESIGN PRESSURE RATING OF EXTERIOR WINDOWS AND
 DOORS IN BUILDINGS SHALL BE DETERMINED IN ACCORDANCE
 WITH SECTION 1709.5.1 OR 1709.5.2. FOR THE PURPOSES OF
 THIS SECTION, THE REQUIRED DESIGN PRESSURE SHALL BE
 DETERMINED USING THE ALLOWABLE STRESS DESIGN LOAD
 COMBINATIONS OF SECTION 1605.3.
  
 EXCEPTION: CUSTOM DOORS. CUSTOM (ONE-OF-A-KIND)
 EXTERIOR DOOR ASSEMBLIES SHALL BE TESTED BY AN APPROVED
 TESTING LABORATORY OR BE DESIGNED AND ENGINEERED IN
 ACCORDANCE WITH ACCEPTED ENGINEERING PRACTICES BY A
 FLORIDA REGISTERED DESIGN PROFESSIONAL. SIGNED AND
 SEALED COPIES OF THE RATIONAL ANALYSIS AND CALCULATIONS
 SHALL BE PROVIDED TO THE BUILDING OFFICIAL UPON PERMIT
 APPLICATION.
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-05-21 Cont ID  
Sent By aborngra Date 2020-05-21 Time 10:51 Rev Time 0.00
Received By aborngra Date 2020-05-21 Time 10:42 Sent To  
Notes
2020-05-21 10:42:39EXISTING SHUTTERS TO BE REINSTALLED.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2020-05-06 Cont ID  
Sent By aborngra Date 2020-05-06 Time 11:28 Rev Time 0.00
Received By aborngra Date 2020-05-06 Time 11:27 Sent To  
Notes
2020-05-06 11:28:23 
 THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. PLEASE RESUBMIT AND FOLLOW THE ATTACHED WINDOW
 PERMIT APPLICATION EXAMPLE. PROVIDE A WINDOW SCHEDULE
 AND PHOTOS OF EACH ELEVATION AND/OR WINDOW/DOOR WITH
 LABELS.
 2. THE PROPOSED DOOR IS MISSION IN STYLE. REVISE TO A
 PROPER MINIMAL TRADITIONAL DOOR. I RECOMMEND A DOOR
 WITH PANELS.
  
 THE FOLLOWING ARE PROPOSED CONDITIONS, SUBJECT TO
 CHANGE:
 1. ALL WINDOWS SHALL BE SIZED TO FIT THE ORIGINAL
 WINDOW FRAME OPENING AND MATCH THE INSET/DEPTH/LOCATION
 OF THE ORIGINAL WINDOWS WITHIN THE WINDOW FRAME.
 2. ALL STREET FACING GLASS SHALL BE CLEAR ONLY.
 NON-STREET FACING GLASS MAY HAVE CLEAR OR CLEAR WITH
 LOW-E COATING. THE BATHROOM MAY HAVE OBSCURED TEXTURED
 GLASS AS IT IS NON-STREET FACING.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-21 Cont ID  
Sent By cthroop Date 2020-05-21 Time 10:59 Rev Time 0.00
Received By cthroop Date 2020-05-20 Time 14:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-06 Cont ID  
Sent By lmarchan Date 2020-05-06 Time 11:51 Rev Time 0.00
Received By lmarchan Date 2020-04-28 Time 16:14 Sent To  
Notes
2020-05-05 16:15:14CONVERTED TO DIGITAL. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-05-21 Cont ID  
Sent By cthroop Date 2020-05-21 Time 10:02 Rev Time 0.00
Received By cthroop Date 2020-05-20 Time 14:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-06 Cont ID  
Sent By cthroop Date 2020-05-06 Time 11:11 Rev Time 0.00
Received By cthroop Date 2020-05-06 Time 10:08 Sent To  
Notes
2020-05-06 11:12:58CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 PLAN REVIEW - SIGNATURE AND SEAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CONTRACTOR SIGNATURE ON FLOOR PLAN IS APPROVED.
  
 2. DESIGN PROFESSIONAL SHALL SIGN AND SEAL CUSTOM DOOR
 SUBMITTAL. (SEE BUILDING REVIEW COMMENTS)
  
  