Plan Review Details - Permit 20041076
Plan Review Stops For Permit 20041076
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-02 Cont ID  
Sent By rmcphers Date 2020-06-02 Time 08:12 Rev Time 0.00
Received By rmcphers Date 2020-06-02 Time 08:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-05-26 Cont ID  
Sent By rmcphers Date 2020-05-26 Time 09:15 Rev Time 0.00
Received By rmcphers Date 2020-05-26 Time 09:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-06-02 Cont ID  
Sent By jleahy Date 2020-06-02 Time 07:46 Rev Time 0.00
Received By jleahy Date 2020-06-02 Time 07:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-05-26 Cont ID  
Sent By jleahy Date 2020-05-26 Time 13:26 Rev Time 0.00
Received By jleahy Date 2020-05-26 Time 13:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2020-08-25 Cont ID  
Sent By shill Date 2020-08-25 Time 07:20 Rev Time 0.00
Received By shill Date 2020-08-25 Time 07:20 Sent To  
Notes
2020-08-25 07:20:45SEPARATE PERMIT AND PLANS REQUIRED

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-07-31 Cont ID  
Sent By lcrespo Date 2020-07-31 Time 12:04 Rev Time 0.00
Received By lcrespo Date 2020-07-31 Time 12:04 Sent To  
Notes
2020-07-31 12:04:5407/31/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE GENERATOR ON THE ISOMETRIC IT SAYS 330 BTU'S AND
 ON YOUR SPECIFICATION IT HAS A 309 BTU'S PLEASE CHANGE
 A TALLY UP NEW TOTAL, PUT THE 309 ON THE ISO NOT 22 KW
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING GAS. A FULL EVALUATION OF ALL GAS EQUIPMENT
 WILL BE DONE AT FIELD, IF NOT TO CODE, IT MAY NEED TO
 BE BOUT UP TO CODE COMPLIANCE.
  
 3. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR PER THE 2017 FBC RES. SEC.
 G2420.4.
  
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.4.1.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
  
 6. NOTE: IF THE EXISTING SYSTEM IS LESS THAN A 2 PSI
 SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO 2 PSI, A
 LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE EXISTING
 APPLIANCES PER THE 2017 FBC RES. SECS. G2412.4,
 G2412.8, G2413.1, G2413.2, G2413.3.
  
 7. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
  
 8. PLEASE SHOW AND LABEL UNIONS IN FRONT OF REGULATOR
 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2.
  
 9. SHOW DRIP LEG AND LABEL ON EQUIPMENT INSTALLED PER
 THE 2017 FBC RES. SEC. G2419.2.
  
 10. PLEASE SHOW THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-06-03 Cont ID  
Sent By medwards Date 2020-06-03 Time 14:21 Rev Time 0.00
Received By medwards Date 2020-06-03 Time 14:04 Sent To  
Notes
2020-06-03 14:21:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20041076
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE IS NOT ENOUGH INFORMATION ON THE DRAWING TO DO
 A REVIEW. PLEASE PROVIDE A COMPLETE GAS LINE DIAGRAM
 SHOWING THE EXIST SYSTEM AND THE NEW ADDITION TO THE
 SYSTEM. SHOW THAT THE EXISTING GAS LINE IS OF
 SUFFICIENT SIZE TO HANDLE THE ADDITIONAL LOAD. FBC FG
 401.8
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-10 Cont ID  
Sent By cpuell Date 2020-08-10 Time 12:23 Rev Time 0.00
Received By cpuell Date 2020-07-22 Time 16:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-12 Cont ID  
Sent By cpuell Date 2020-06-12 Time 16:24 Rev Time 0.00
Received By cpuell Date 2020-05-08 Time 16:58 Sent To Z
Notes
2020-05-08 14:05:46ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-07-31 Cont ID  
Sent By lcrespo Date 2020-07-31 Time 12:08 Rev Time 0.00
Received By lcrespo Date 2020-07-31 Time 12:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-03 Cont ID  
Sent By medwards Date 2020-06-03 Time 14:24 Rev Time 0.00
Received By medwards Date 2020-06-03 Time 14:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-13 Cont ID  
Sent By pvalenti Date 2020-05-13 Time 15:15 Rev Time 0.00
Received By pvalenti Date 2020-05-13 Time 15:15 Sent To  
Notes
2020-05-13 15:17:50PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW APPROVED PER PAPER ORIGINAL
 SUBMITTALS. THE ORIGINAL SUBMITTALS HAVE BEEN ROUTED TO
 THE PERMIT LIBRARY FOR FILING.

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2020-08-06 Time   Rev Time 0.00
Received By   Date 2020-08-06 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-06-12 Cont ID  
Sent By cpuell Date 2020-06-12 Time 16:24 Rev Time  
Received By awooten Date 2020-06-12 Time   Sent To  
Notes
2020-06-12 16:21:13************************************ZONING REVIEW
 FAILED****************************************
  
 PROVIDE THE SETBACKS FOR THE PROPOSED GENERATOR TO THE
 PROPERTYLINES ON THE SURVEY. MECHANICAL EQUIPMENT MAY
 NOT PROJECT MORE THAN FOUR FEET INTO A SETBACK.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]