Plan Review Details - Permit 20041068
Plan Review Stops For Permit 20041068
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-07-21 Cont ID  
Sent By cpuell Date 2020-07-21 Time 12:20 Rev Time 0.00
Received By cpuell Date 2020-07-21 Time 12:20 Sent To  
Notes
2020-07-21 12:20:43ADDRESS CHANGED FROM 315 1/2 GREENWOOD TO 317
 GREENWOOD. CP

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-07-17 Cont ID  
Sent By cpuell Date 2020-07-17 Time 16:38 Rev Time 0.00
Received By cpuell Date 2020-07-17 Time 16:38 Sent To  
Notes
2020-07-17 16:40:111/2 ADDRESSES FOR REAR STRUCTURE NO LONGER ALLOWED
 PLEASE CONTACT [email protected] TO DISCUSS ADDRESS
 POSSIBILITES FOR THE REAR STRUCTURE (GUEST HOUSE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-20 Cont ID  
Sent By cthroop Date 2020-07-20 Time 16:37 Rev Time 0.00
Received By cthroop Date 2020-07-20 Time 16:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-05-15 Cont ID  
Sent By cthroop Date 2020-05-15 Time 11:49 Rev Time 0.00
Received By cthroop Date 2020-05-15 Time 07:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-14 Cont ID  
Sent By jleahy Date 2020-07-14 Time 08:24 Rev Time 0.00
Received By jleahy Date 2020-07-14 Time 08:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-05-14 Cont ID  
Sent By jleahy Date 2020-05-14 Time 15:37 Rev Time 0.00
Received By jleahy Date 2020-05-14 Time 15:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-06-02 Cont ID  
Sent By cthroop Date 2020-05-15 Time 11:57 Rev Time 0.00
Received By cthroop Date 2020-05-15 Time 11:05 Sent To  
Notes
2020-05-15 12:04:00SEPERATE GAS PERMIT REQUIRED. CT

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-07-06 Cont ID  
Sent By fmittner Date 2020-07-06 Time 15:48 Rev Time 0.00
Received By fmittner Date 2020-07-06 Time 15:48 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-05-06 Cont ID  
Sent By fmittner Date 2020-05-06 Time 15:26 Rev Time 0.00
Received By fmittner Date 2020-05-06 Time 15:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-20 Cont ID  
Sent By cthroop Date 2020-07-20 Time 16:37 Rev Time 0.00
Received By cthroop Date 2020-06-29 Time 10:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-15 Cont ID  
Sent By cthroop Date 2020-05-15 Time 12:04 Rev Time 0.00
Received By cthroop Date 2020-05-05 Time 11:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-07-10 Cont ID  
Sent By medwards Date 2020-07-10 Time 13:25 Rev Time 0.00
Received By medwards Date 2020-07-10 Time 13:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-05-06 Cont ID  
Sent By medwards Date 2020-05-06 Time 12:21 Rev Time 0.00
Received By medwards Date 2020-05-06 Time 12:21 Sent To  
Notes
2020-05-06 12:22:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20041068
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW VENTILATION OF KITCHEN BASED ON FBC RES
 TABLE M1507.4
  
 2) PLEASE PROVIDE A DETAIL DRAWING OF THE ANCHORAGE OF
 THE APPLIANCE ACCORDING TO- FBC RES M1307.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-07-06 Cont ID  
Sent By cthroop Date 2020-07-06 Time 15:30 Rev Time 0.00
Received By cthroop Date 2020-07-06 Time 15:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-05-15 Cont ID  
Sent By cthroop Date 2020-05-15 Time 11:57 Rev Time 0.00
Received By cthroop Date 2020-05-15 Time 07:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-08 Cont ID  
Sent By medwards Date 2020-07-10 Time 13:28 Rev Time 0.00
Received By medwards Date 2020-08-08 Time 15:58 Sent To  
Notes
2020-08-08 15:59:35PLEASE SEE 1ST REVIEWERS COMMENTS.
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-15 Cont ID  
Sent By cthroop Date 2020-05-15 Time 11:47 Rev Time 0.00
Received By cthroop Date 2020-05-15 Time 07:13 Sent To  
Notes
2020-05-15 11:49:30PLAN REVIEW - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DIGITAL SIGNATURES AND SEALS
  
 DESIGN PROFESSIONALS
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
 DIGITAL SIGNATURE IS NOT ISSUED IN A MANNER WHICH IS
 ACCEPTABLE TO EITHER FBPA OR FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS. THIS TYPE OF SELF-CERTIFICATION
 IS NOT INTENDED TO BE USED FOR PROFESSIONAL PURPOSES.
 THIRD PARTY CERTIFICATION IS REQUIRED.
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-07-06 Cont ID  
Sent By fmittner Date 2020-07-06 Time 15:48 Rev Time 0.00
Received By fmittner Date 2020-07-06 Time 15:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-05-06 Cont ID  
Sent By fmittner Date 2020-05-06 Time 15:26 Rev Time 0.00
Received By fmittner Date 2020-05-06 Time 15:26 Sent To  
Notes
***NONE***