Plan Review Details - Permit 20041046
Plan Review Stops For Permit 20041046
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-05-13 Cont ID  
Sent By cpuell Date 2020-05-13 Time 15:48 Rev Time 0.00
Received By jwitmer Date 2020-06-28 Time 16:32 Sent To  
Notes
2020-05-13 15:48:51SUITE 100, ADDED AND UPDATED

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-07-13 Cont ID  
Sent By pvalenti Date 2020-07-13 Time 10:21 Rev Time 0.00
Received By pvalenti Date 2020-07-13 Time 10:21 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-06-28 Cont ID  
Sent By jwitmer Date 2020-06-28 Time 16:56 Rev Time 0.00
Received By jwitmer Date 2020-06-28 Time 16:32 Sent To  
Notes
2020-06-28 17:04:29PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND 'ASBESTOS' IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2020-05-12 Time 10:02 Sent To  
Notes
2020-05-12 11:37:00PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-28 Cont ID  
Sent By jwitmer Date 2020-06-28 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2020-06-28 Time 16:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-12 Cont ID  
Sent By jwitmer Date 2020-05-12 Time 11:35 Rev Time 0.00
Received By jwitmer Date 2020-05-12 Time 10:02 Sent To  
Notes
2020-05-12 11:35:442017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20041046
 ADD: 2751 S. DIXIE HWY.
 CONT: L. J. SHEEHAN INC.
 TEL: 561-223-2750
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 12/ 2020
 ACTION: DENIED
  
 1) SHEET A3.01 DETAIL # 2 INDICATES AN ISLAND WITH
 HI-LOW COUNTER-TOPS. THE HIGH COUNTERTOP AT 3 FEET 6
 INCHES, THE LOW COUNTER TOP AT A HEIGHT OF 3 FEET. THE
 LIFE SAFETY SHEET DOES SHOW SEATING AT THE HIGH SIDE OR
 3 FEET 6 INCH SIDE OF THE ISLAND. PLEASE SHOW HOW
 COMPLIANCE WITH THE 2017 ACCESSIBILITY CODE SECTIONS:
  
 1A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 1B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 1C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 1D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 1D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 1D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2)SHEET A3.01 DETAIL B AND DETAIL 6 SHOWS AN EXISTING
 WATER COOLER PLEASE PROVIDE HOW COMPLIANCE WITH THE:
  
 2017 ACCESSIBILITY CODE SECTION: 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-13 Cont ID  
Sent By jleahy Date 2020-07-13 Time 15:58 Rev Time 0.00
Received By jleahy Date 2020-07-13 Time 15:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-05-21 Cont ID  
Sent By jleahy Date 2020-05-21 Time 18:08 Rev Time 0.00
Received By jleahy Date 2020-05-21 Time 17:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-06-25 Cont ID  
Sent By pleduc Date 2020-06-25 Time   Rev Time 0.00
Received By pleduc Date 2020-06-25 Time 14:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-05-07 Cont ID  
Sent By pleduc Date 2020-05-07 Time   Rev Time 0.00
Received By pleduc Date 2020-05-07 Time 15:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-13 Cont ID  
Sent By jleahy Date 2020-07-13 Time 15:58 Rev Time 0.00
Received By jleahy Date 2020-06-24 Time 11:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-05-29 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-06 Time 08:52 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-05-12 Cont ID  
Sent By jwitmer Date 2020-05-12 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2020-05-12 Time 10:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-07-10 Cont ID  
Sent By medwards Date 2020-07-10 Time 11:52 Rev Time 0.00
Received By medwards Date 2020-07-10 Time 11:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-05-07 Cont ID  
Sent By medwards Date 2020-05-07 Time 15:45 Rev Time 0.00
Received By medwards Date 2020-05-07 Time 14:45 Sent To  
Notes
2020-05-07 15:46:131ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20041046
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS APPEARS TO BE A CHANGE OF USE FOR THE REMODELED
 SPACE. PLEASE PROVIDE VENTILATION CALCULATIONS FOR THIS
 SPACE. FBC M TABLE 403.3.1.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-07-09 Cont ID  
Sent By jsmith Date 2020-07-09 Time 12:02 Rev Time 0.00
Received By rmcdouga Date 2020-07-09 Time 10:42 Sent To  
Notes
2020-07-09 10:45:0020041046 2751 S DIXIE HWY # 100
  
 PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PROVISO
 1. INSPECTOR SHALL CONFIRM IN FIELD THAT THE DRINKING
 FOUNTAIN IS ADA COMPLIANT AS STATED IN ARCHITECTURAL
 RESPONSE LETTER DATED 6/22/20.
 2. THE ICE MAKER DRAIN SHALL DISCHARGE TO THE WASTE
 RECEPTACLE THROUGH AN AIR GAP IN ACCORDANCE WITH FBC PL
 802.1.1, 802.2 AND 802.2.1. PER FBC PL 802.3, THE WASTE
 RECEPTACLE SHALL NOT BE INSTALLED IN A CONCEALED SPACE
 AND READY ACCESS SHALL BE PROVIDED TO THE WASTE
 RECEPTOR.
 3. SEE ARCHITECTURAL RESPONSE LETTER DATED 6/22/20 FOR
 TANKLESS WATER HEATER CALCULATIONS INDICATING IT MEETS
 HOT WATER DEMAND
 4. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR THE ICE MAKER AND
 THE DISHWASHER INDICATED ON PLAN SHEET; DISHWASHER IS
 CONNECTED TO COLD WATER AND SHALL BE CAPABLE OF HEATING
 THE WATER INTERNALLY AS STATED IN THE ARCHITECTURAL
 RESPONSE LETTER DATED 6/22/20. SUBMITTAL SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION. PROCEED AT YOUR OWN RISK.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20041046 2751 S DIXIE HWY # 100
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-05-29 Cont ID  
Sent By jpearson Date 2020-05-29 Time 07:27 Rev Time 0.00
Received By jpearson Date 2020-05-28 Time 15:52 Sent To  
Notes
2020-05-28 15:52:22REVIEWED BY JERRY SMITH.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20041046 2751 S DIXIE HWY # 100
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS INDICATING
 THE REQUIRED PLUMBING FIXTURES FOR THE FLOOR TO COMPLY
 WITH FBC PL TABLE 403.1 AND INDICATE THE PLUMBING
 FIXTURES THAT ARE FURNISHED ON THE FLOOR TO COMPLY.
 2. INDICATE ON THE PLAN THAT THE DRINKING FOUNTAIN IN
 THE COMMON AREA MEETS THE REQUIREMENTS OF FBC ACC 211.2
 AND 602.1 THROUGH 602.7.
 3. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS TO SHOW
 THAT THE SPECIFIED CHRONOMITE SR-20 TANKLESS WATER
 HEATER WILL MEET THE HOT WATER DEMAND OF THE SINK AND
 DISHWASHER.
 4. PLAN PAGE P2-1 IS NOT DIGITALLY SIGNED.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20041046 2751 S DIXIE HWY # 100
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-10 Cont ID  
Sent By medwards Date 2020-07-10 Time 11:59 Rev Time 0.00
Received By medwards Date 2020-07-10 Time 11:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-29 Cont ID  
Sent By medwards Date 2020-05-07 Time 15:58 Rev Time 0.00
Received By jpearson Date 2020-05-07 Time 15:46 Sent To  
Notes
2020-05-29 07:30:48P2.1 IS MISSING THE DIGITAL SIGNATURE. PER THE WPB
 AMENDMENTS TO THE FBC, EACH SHEET OF PLAN IS REQUIRED
 TO BE SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. WPB FBC 107.1; FS 471/481