Plan Review Details - Permit 20040978
Plan Review Stops For Permit 20040978
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-05-22 Cont ID  
Sent By jpearson Date 2020-05-22 Time 07:42 Rev Time 0.00
Received By jpearson Date 2020-05-22 Time 07:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-20 Cont ID  
Sent By jpearson Date 2020-05-20 Time 08:56 Rev Time 0.00
Received By jpearson Date 2020-05-20 Time 08:41 Sent To  
Notes
2020-05-20 08:56:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. THE APPROVED PLANS HAVE BEEN DESIGNED BY NADER
 GROUBAN, ARCHITECT, ANY REVISIONS TO THIS PLAN MUST BE
 PREPARED BY THE ARCHITECT OF RECORD. PROVIDE
 CORRECTION. WPB FBC 105.1 (THE REVISION REQUESTED IS
 FOR ITEMS SHOWN ON SHEET E-1 OF THE APPROVED PLANS. A
 PROPOSED REVISION SHOULD BE PREPARED ON THAT SHEET AND
 SUBMITTED FOR REVIEW. THE NEW SHEET, WHEN APPROVED,
 WILL REPLACE THE EXISTING SHEET. A HAND DRAWN SHEET
 WITH JUST THE RISER DIAGRAM CANNOT REPLACE THE ENTIRE
 E-1 SHEET. PROVIDE CORRECTION.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-05-08 Cont ID  
Sent By jpearson Date 2020-05-08 Time 08:33 Rev Time 0.00
Received By jpearson Date 2020-05-08 Time 08:33 Sent To  
Notes
2020-05-08 08:33:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE APPROVED PLANS HAVE BEEN DESIGNED BY NADER
 GROUBAN, ARCHITECT, ANY REVISIONS TO THIS PLAN MUST BE
 PREPARED BY THE ARCHITECT OF RECORD. PROVIDE
 CORRECTION. WPB FBC 105.1
 2. RISER DIAGRAM IS NOT CODE COMPLIANT. FEEDER
 CONDUCTORS FROM TRANSFER SWITCH TO MCB PANELS IS SHOWN
 AS 2/0 WIRE TO A 200 AMP MAIN BREAKER. WIRE SIZES FROM
 NEC 310.15(B)(7), OR FBC RE E3603.1, CAN ONLY BE USED
 WHEN THE SERVICE CONDUCTOR SUPPLIES 100% OF THE LOAD.
 SINCE THIS IS NOT THE CASE, PROVIDE CORRECTED WIRE SIZE
 FROM METER CAN TO PANELS. NEC 310.15(B)(7) AND (B)(16);
 FBC RE E3603.1, E3705.1
 3. CONDUCTORS FROM TRANSFER SWITCH TO MAIN BREAKER
 PANELS ARE FEEDERS THAT ARE DOWNSTREAM FROM THE MAIN
 AND REQUIRE AN EQUIPMENT GROUNDING CONDUCTOR, SIZED PER
 CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6,
 3607.3.1
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-05-22 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-22 Time 07:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-20 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-12 Time 14:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-05-08 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-07 Time 07:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-05-22 Cont ID  
Sent By jpearson Date 2020-05-22 Time 07:42 Rev Time 0.00
Received By jpearson Date 2020-05-22 Time 07:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-20 Cont ID  
Sent By jpearson Date 2020-05-20 Time 08:57 Rev Time 0.00
Received By jpearson Date 2020-05-20 Time 08:57 Sent To  
Notes
2020-05-20 08:57:12PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-08 Cont ID  
Sent By jpearson Date 2020-05-08 Time 08:19 Rev Time 0.00
Received By jpearson Date 2020-05-08 Time 08:19 Sent To  
Notes
2020-05-08 08:19:38PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481