Plan Review Details - Permit 20040919
Plan Review Stops For Permit 20040919
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-01 Cont ID  
Sent By jwitmer Date 2020-07-01 Time 08:01 Rev Time 0.00
Received By jwitmer Date 2020-07-01 Time 07:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By jwitmer Date 2020-06-09 Time 14:06 Rev Time 0.00
Received By jwitmer Date 2020-06-09 Time 13:32 Sent To  
Notes
2020-06-09 14:04:422017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040919
 ADD: 701 S. OLIVE AVE. SUITE: 916
 CONT: TD ROOFING & CONTRACTING
 TEL: 561-719-0725
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 09/2020
 ACTION: DENIED
  
 1) THIS REVIEW CYCLE THE CONTRACTOR SUBMITTED 2 SOUND
 TEST FOR THE PRODUCT SUPER SAM 125 FOR THE IIC RATING
 OF 51 AND STC RATING OF 54. THE SUBMITTED FLAME SPREAD
 SMOKE DEVELOPMENT TEST IS FOR CORK AND ANOTHER
 MANUFACTURER. ALL 3 TEST HAVE TO BE FOR THE SAME
 PRODUCT AND SAME MANUFACTURER. WE DO NOT HAVE ON FILE A
 FLAME SPREAD TEST FOR SUPER SAM 125. IF A PERMIT WAS
 ISSUED FOR THIS PRODUCT IT WAS ISSUED IN ERROR.
  
 FLOOR INSULATION (FBC-B 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 TYPE I AND II BUILDINGS
 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-01 Cont ID  
Sent By jleahy Date 2020-07-01 Time 16:46 Rev Time 0.00
Received By jleahy Date 2020-07-01 Time 16:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-16 Cont ID  
Sent By jpearson Date 2020-06-16 Time 13:55 Rev Time 0.00
Received By jpearson Date 2020-06-16 Time 13:31 Sent To  
Notes
2020-06-16 13:55:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN, INCLUDING THE ISLAND, REQUIRE GFCI PROTECTION.
 SOME AREAS REQUIRE AFCI AND GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8, 210.12
 2. PROVIDE LAYOUT OF EXISTING RECEPTACLE OUTLETS IN
 KITCHEN TO CONFIRM CODE COMPLIANCE. WPB FBC 107.2.1
 3. LOAD CALCULATION USES 240 VOLT FOR THE CALCULATION.
 MOST BUIDLINGS OF THIS TYPE HAVE A 208 VOLT 3 PHASE
 SYSTEM. PROVIDE CLARIFICATIOIN AND/OR CORRECTION FOR
 LOAD CALCULATION AS NEEDED. NEC 110.4, 220.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-01 Cont ID  
Sent By jleahy Date 2020-07-01 Time 16:50 Rev Time 0.00
Received By jleahy Date 2020-06-29 Time 07:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-06-16 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-29 Time 14:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-01 Cont ID  
Sent By jleahy Date 2020-07-01 Time 16:48 Rev Time 0.00
Received By jleahy Date 2020-07-01 Time 16:48 Sent To  
Notes
2020-07-01 16:50:04PLAN IS NOT SIGNED JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-16 Cont ID  
Sent By jpearson Date 2020-06-16 Time 13:48 Rev Time 0.00
Received By jpearson Date 2020-06-16 Time 13:48 Sent To  
Notes
2020-06-16 13:48:45PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED (AND SEALED FOR DESIGN
 PROFESSIONALS) BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED OR SIGNED/SEALED
 PAPER SET MAY BE SUPPLIED TO THE BUILDING DEPARTMENT
 WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481