Plan Review Details - Permit 20040867
Plan Review Stops For Permit 20040867
Review Stop AD ADDRESSING
Rev No 5 Status P Date 2021-12-08 Cont ID  
Sent By cpuell Date 2021-12-08 Time 14:56 Rev Time 0.00
Received By cpuell Date 2021-12-08 Time 14:56 Sent To  
Notes
2021-12-08 14:57:07ADDRESS UPDATED FROM 936 27TH ST TO 976 27TH ST

Review Stop AD ADDRESSING
Rev No 4 Status F Date 2021-12-01 Cont ID  
Sent By cpuell Date 2021-12-01 Time 12:15 Rev Time 0.00
Received By cpuell Date 2021-12-01 Time 12:15 Sent To  
Notes
2021-12-01 12:16:01PROPOSED ADDRESS OF 976 27TH ST WAITING TO HEAR BACK
 FROM MIKE MOORE

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2021-11-15 Cont ID  
Sent By cpuell Date 2021-11-15 Time 11:13 Rev Time 0.00
Received By cpuell Date 2021-11-15 Time 11:13 Sent To  
Notes
2021-11-15 11:14:57PROPOSED ADDRESS OF 976 27TH ST WAITING TO HEAR BACK
 FROM MIKE MOORE

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-07-28 Cont ID  
Sent By cpuell Date 2021-07-28 Time 09:13 Rev Time 0.00
Received By cpuell Date 2021-07-28 Time 09:13 Sent To  
Notes
2021-07-28 09:13:53PREVIOUS COMMENTS NOT ADDRESSED, PLEASE CONTACT
 [email protected] OR CALL 561-805-6659 DO DISCUSS
 ADDRESSING ISSUES.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-05-26 Cont ID  
Sent By cpuell Date 2020-05-26 Time 11:33 Rev Time 0.00
Received By cpuell Date 2020-05-26 Time 11:33 Sent To  
Notes
2020-05-26 11:34:03PLEASE PROVIDE A SITE PLAN SHOWING THE EXACT LOCATION
 OF THE MAIN ENTRANCE AND ANY SUITE/UNITS IN THE
 BUILDING. PLEASE EMAIL TO [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-01-26 Cont ID  
Sent By jwitmer Date 2022-01-26 Time 06:43 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-01-26 06:42:04WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040867
 ADD: 936 27TH ST.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] CONTACT: MATTHEW DONNELL
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 4TH REVIEW
 DATE: WED. JAN. 26TH/ 2022
 ACTION: BUILDIG PROVISO.
  
 1) PROVISO. THERE IS A DETAIL FOR THE DUMPSTER
 ENCLOSURE, PLEASE NOTE THE DUMPSTER ENCLOSURE TAKES A
 SEPARATE, PERMIT, REVIEW AND ASSOCIATED FEES.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE 105.1.
  
 2) PROVISO. JUST TO THE RIGHT OF THE FLOOR PLAN SHOWS A
 CONCRETE SLAB WITH (3) 500-GALLON FUEL TANKS. FUEL
 TANKS ALSO TAKE SEPARATE PERMITS REVIEWS AND ASSOCIATED
 FEES. 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE 105.1.
  
 3) PROVISO, WELDED OR BOLTED CONNECTIONS, THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT561-805-6666 OR ACTING CHIEF RICHARD BRUNELLE
 561-805-6670.
 CITY INSPECTORS REQUIRED FOR ALL OTHER INSPECTIONS.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-12-01 Cont ID  
Sent By jwitmer Date 2021-12-01 Time 09:14 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-12-01 09:14:14WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040867
 ADD: 936 27TH ST.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] CONTACT: MATTHEW DONNELL
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. AUGUST 03RD/ 2020
 ACTION: DENIED
  
 1) COMPLIED. VALUATION.
  
 2) COMPLIED.
  
  
 3A-B) COMPLIED.
  
 3C)PROVISO/ NOTICE NO ACTION REQUIRED. THERE IS A
 DETAIL FOR THE DUMPSTER ENCLOSURE, PLEASE NOTE THE
 DUMPSTER ENCLOSURE TAKES A SEPARATE, REVIEW AND
 ASSOCIATED FEES.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE 105.1.
  
 3D) PROVISO/ NOTICE NO ACTION REQUIRED. JUST TO THE
 RIGHT OF THE FLOOR PLAN SHOWS A CONCRETE SLAB WITH (3)
 500 GALLON FUEL TANKS. FUEL TANKS ALSO TAKE SEPARATE
 PERMITS REVIEWS AND ASSOCIATED FEES. 2017 FLORIDA
 BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 105.1.
  
 3E) NOT APPLICABLE.
  
 4) SHEET 003 4.1 COMPLIED PRESSURES IN VASD. THANK YOU.
  
  
 5) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS, THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 6A) 2ND REQUEST. FOR METAL BUILDINGS THE WALL AND ROOF
 PRODUCT APPROVALS ARE REQUIRED BEFORE PERMIT ISSUANCE
 JUST AS THE BUILDING SHOP DRAWINGS ARE REQUIRED, TO
 VERIFY GIRT & PURLIN SPACING AND PRESSURES MATCH FOR
 THE WALL END ZONE 5 AND ROOF CORNER ZONE 3. MOST OF THE
 TIME THE GIRTS AND PURLINS NEED TO BE SPACED CLOSER
 TOGETHER FOR THE HIGHER PRESSURES IN THESE ZONES.
 COMPONENTS & CLADDING PLEASE SUPPLY THE PRODUCT
 APPROVAL FULL REPORTS. IF IN THE PRODUCT APPROVAL THERE
 ARE MULTIPLE SUB-SYSTEMS APPROVED IDENTIFY (CIRCLE)
 WHICH APPLICATION IS TO BE INSTALLED.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: METAL WALL PANELS, LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, METAL ROOF PANELS,
  
 6B) 3RD REQUEST. RESPONSE COMMENT INDICATES WALL AND
 ROOF PANEL PRODUCT APPROVALS ATTACHED. NO PRODUCT
 APPROVALS ARE ATTACHED.
 W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6C) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 7) THE SHEETS SUBMITTED BY MBMI 4/ 10 ROOF FRAMING
 PURLIN SPACING @ 3FEET 5 ? INCH SPACING & GIRTS AND
 SHEET 5/10 END WALL AND SIDE WALL FRAMING WITH VARIED
 SPACING, BUT IN THE END WALL ZONES SAME SPACING AS WALL
 ZONE 4. NEED PRODUCT APPROVALS TO VERIFY SPACING AND
 THE ASSOCIATED PRESSURES.
 THE MISSING INFORMATION IS THE PRODUCT APPROVAL FOR THE
 METAL EXTERIOR WALL SYSTEM AND METAL ROOF SYSTEM.
 WITHOUT THE PRODUCT APPROVALS BEING SUBMITTED,
 IDENTIFYING THE TYPE OF WALL AND ROOF PANELS BEING
 INSTALLED, WITH THEIR ALLOWABLE SPACING BETWEEN
 SUPPORTS AND ASSOCIATED PRESSURES NO REVIEW FOR THE
 STRUCTURAL PORTION OF THE BUILDING CAN BE COMPLETED.
  
 8) SEMI COMPLIED. IS THE ENGINEER FOR MBMI TAKING THE
 DOUBLE REDUCTION IN ROOF PANEL PRESSURES, IT IS NOT
 STATED, AND WITHOUT THE ROOFING PRODUCT APPROVAL
 VERIFICATION OF ROOF DESIGN PANEL AND TYPE OF PANEL
 LOCKING DEVICE CANNOT BE VERIFIED.
 THE OTHER UNKNOWN IS IF THE ENGINEER OF RECORD FOR MBMI
 HAS DESIGNED THE ROOF SYSTEM TO SECTION 2211.5 OF THE
 FBC-B AISI S210 OR AISI S 100? WITH A GREATER DEDUCTION
 IN PRESSURES THAN ALLOWED IN VASD?
  
 9) NEW COMMENT. MBMI SHEET 6 END WALL FRAMING LINE 3
 EC-2 SIDE SHOWS 6 GIRTS WHEREAS SIDE EC-5 ONLY SHOWS 5.
 END WALL FRAMING LEFT SIDE ON THE LEFT SIDE IT IS
 DIMENSIONED AS A GIRT BEING THERE BUT NOT SHOWN AGAIN
 THE RIGHT SIDE DOES NOT SHOW BUT 5 GIRTS. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 10) NEW COMMENT. SITE PLAN SP-1 CHANGE SHOWS THE
 PROPOSED BUILDING 5 FEET FROM THE PROPERTY LINE. WITH
 THE BUILDING TYPE BEING DECLARED TYPE IIB/ S1
 OCCUPANCY, AND 5 FEET FROM THE PROPERTY LINE THIS WALL
 WILL NEED TO BE 1 HOUR FIRE RATED PER TABLE 602 OF THE
 2020 FBC-BUILDING CODE.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN ( NO
 PRODUCT APPROVALS) SINCE THERE WAS A GREAT DEFICIENCY
 IN PLANS AND REQUIRED DOCUMENTATION. WITH THE NEXT PLAN
 REVIEW CYCLE THERE MAYBE ADDITIONAL REVIEW COMMENTS
 BECAUSE OF NEW PLANS AND INFORMATION LACKING UNDER THE
 PRIOR REVIEW.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-03 Cont ID  
Sent By jwitmer Date 2021-08-03 Time 14:20 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-08-03 14:19:55WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040867
 ADD: 936 27TH ST.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] CONTACT: MATTHEW DONNELL
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. AUGUST 03RD/ 2020
 ACTION: DENIED
  
 1) COMPLIED. VALUATION.
  
 2A) COMPLIED. SURVEY.
  
 2B) THE PLANS PRODUCED BY GCP ARCHITECTURE LLC ARE
 SIGNED AND SEALED BUT THEY APPEAR TO HAVE ELECTRONIC
 SIGNATURES, THE PLANS DOWNLOADED TO PAPER FORM AND THEN
 RE-UPLOADED. THE ELECTRONIC SIGNATURES WILL NOT OPEN
 FOR VERIFICATION.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2C) THE SUBMITTED PLANS BY MBMI METAL BUILDINGS DOES
 HAVE THE ENGINEERS SEAL WHO PREPARED THESE DRAWINGS,
 KENNETH VOGAN, AGAIN THE SUBMITTED DOCUMENTS APPEAR TO
 BE PAPER PLANS THAT WERE UPLOADED, THERE IS NO
 ELECTRONIC SIGNATURES.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 2D) THE ARCHITECT OF RECORD HAS NOT PUT THEIR SHOP
 DRAWING OF APPROVAL ON THE SUBMITTED DRAWING BY MBMI
 METAL BUILDINGS. THE METAL SHOP DRAWINGS ARE REQUIRED
 BEFORE PERMITTING AS WELL AS THE ROOFING AND SIDING
 PRODUCT APPROVALS TO BE ABLE TO CHECK SPANS BETWEEN
 PURLINS FOR THE ROOF AND GIRTS, FOR SIDE WALL
 COMPONENTS +/- PRESSURES FOR COMPONENT AND CLADDING
 PRODUCT APPROVALS.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 3A-B) COMPLIED.
  
 3C)PROVISO/ NOTICE NO ACTION REQUIRED. THERE IS A
 DETAIL FOR THE DUMPSTER ENCLOSURE, PLEASE NOTE THE
 DUMPSTER ENCLOSURE TAKES A SEPARATE, REVIEW AND
 ASSOCIATED FEES.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE 105.1.
  
 3D) PROVISO/ NOTICE NO ACTION REQUIRED. JUST TO THE
 RIGHT OF THE FLOOR PLAN SHOWS A CONCRETE SLAB WITH (3)
 500 GALLON FUEL TANKS. FUEL TANKS ALSO TAKE SEPARATE
 PERMITS REVIEWS AND ASSOCIATED FEES. 2017 FLORIDA
 BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 105.1.
  
 3E) NOT APPLICABLE.
  
 4) SHEET 003 4.1 SEMI-COMPLIED. THE ROOF ZONE PRESSURES
 STATE GROSS ROOF UPLIFT VALUES, PLEASE INDICATE THE
 PRESSURES IN VASD, THE TERM GROSS I WOULD ASSOCIATE
 WITH VULT PRESSURES, I ASSUME THE DESIGN PRESSURES
 FOUND FOR WALL ZONES 4 & 5 TO BE SERVICE PRESSURES OR
 VASD, PLEASE HAVE ALL COMPONENTS AND CLADDING PRESSURES
 IN VASD.
  
  
 5) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS, THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 6A) 2ND REQUEST. FOR METAL BUILDINGS THE WALL AND ROOF
 PRODUCT APPROVALS ARE REQUIRED BEFORE PERMIT ISSUANCE
 JUST AS THE BUILDING SHOP DRAWINGS ARE REQUIRED, TO
 VERIFY GIRT & PURLIN SPACING AND PRESSURES MATCH FOR
 THE WALL END ZONE 5 AND ROF CORNER ZONE 3. MOST OF THE
 TIME THE GIRTS AND PURLINS NEED TO BE SPACED CLOSER
 TOGETHER FOR THE HIGHER PRESSURES IN THESE ZONES.
 COMPONENTS & CLADDING PLEASE SUPPLY THE PRODUCT
 APPROVAL FULL REPORTS. IF IN THE PRODUCT APPROVAL THERE
 ARE MULTIPLE SUB-SYSTEMS APPROVED IDENTIFY (CIRCLE)
 WHICH APPLICATION IS TO BE INSTALLED.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: METAL WALL PANELS, STOREFRONTS,
 CURTAIN WALLS, WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, METAL ROOF PANELS,
 LIGHTWEIGHT CONCRETE INSULATION, ROOF TOP VENTILATORS
  
  
 6B) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6C) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 7) THE SHEETS SUBMITTED BY MBMI 4/ 10 ROOF FRAMING
 PURLIN SPACING @ 3FEET 5 ? INCH SPACING & GIRTS AND
 SHEET 5/10 END WALL AND SIDE WALL FRAMING WITH VARIED
 SPACING, BUT IN THE END WALL ZONES SAME SPACING AS WALL
 ZONE 4. NEED PRODUCT APPROVALS TO VERIFY SPACING AND
 THE ASSOCIATED PRESSURES.
 THE MISSING INFORMATION IS THE PRODUCT APPROVAL FOR THE
 METAL EXTERIOR WALL SYSTEM AND METAL ROOF SYSTEM.
 WITHOUT THE PRODUCT APPROVALS BEING SUBMITTED,
 IDENTIFYING THE TYPE OF WALL AND ROOF PANELS BEING
 INSTALLED, WITH THEIR ALLOWABLE SPACING BETWEEN
 SUPPORTS AND ASSOCIATED PRESSURES NO REVIEW FOR THE
 STRUCTURAL PORTION OF THE BUILDING CAN BE COMPLETED.
  
 8) THE OTHER UNKNOWN IS IF THE ENGINEER OF RECORD FOR
 MBMI HAS DESIGNED THE ROOF SYSTEM TO SECTION 2211.5 OF
 THE FBC-B AISI S210 OR AISI S 100? WITH A GREATER
 DEDUCTION IN PRESSURES THAN ALLOWED IN VASD?
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-12 Cont ID  
Sent By jwitmer Date 2020-07-12 Time 13:43 Rev Time 0.00
Received By jwitmer Date 2020-07-12 Time 08:15 Sent To  
Notes
2020-07-12 13:33:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040867
 ADD: 936 27TH ST.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] CONTACT: MATTHEW DONNELL
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: SUN. JULY 12TH/ 2020
 ACTION: DENIED
  
 1) THE BUILDING VALUE IS LOW, LESS THAN ? OF THE VALUE
 FOR THE SQUARE FOOTAGE OF THE PROPOSED BUILDING. THE
 SUBMITTED VALUE OF THE PROPOSED BUILDING A (S1
 OCCUPANCY STORAGE OR MOTOR VEHICLE REPAIR GARAGE) PER
 SQ. FT. IS $28.57 DOLLARS / SQ. FT. $50.000.00/1750=
 $28.57. THE CALCULATED VALUE OF THE STRUCTURE WITHOUT
 FIRE SPRINKLERS IS $62.56 A SQ. FT. OR A PROPOSED
 CALCULATED VALUE OF $109,605.00 DOLLARS IN VALUE.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 2A) PLEASE PROVIDE EITHER A SITE PLAN AND OR SURVEY
 SHOWING THE LOCATION OF THE PROPOSED BUILDING AND ALL
 OTHER BUILDINGS AND OR STRUCTURES. 2017 FBC-B 503.1.2.
 & TABLE 602. SHOW DISTANCES FROM PROPERTY LINES AND
 OTHER STRUCTURES AND OR PROPOSED STRUCTURES.
  
 2B) THE PLANS PRODUCED BY GCP ARCHITECTURE LLC ARE NOT
 SIGNED NOR SEALED. NO SIGNATURE NOR SEAL. ARCHITECTS:
 FLORIDA ADMINISTRATIVE CODE 61G1-16.005. PROCEDURES FOR
 DIGITALLY SIGNING AND SEALING AND FOR ELECTRONICALLY
 TRANSMITTING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC...
  
 2C) THE SUBMITTED PLANS BY MBMI METAL BUILDINGS DOES
 NOT HAVE THE ENGINEERS SEAL WHO PREPARED THESE
 DRAWINGS. 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED
 & SEALED BY A PROFESSIONAL ENGINEER SHALL INCLUDE
 EITHER THE: NAME, ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS
 THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S.
 AND 471.023 F.S.).
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2D) THE ARCHITECT OF RECORD HAS NOT PUT THEIR SHOP
 DRAWING OF APPROVAL ON THE SUBMITTED DRAWING BY MBMI
 METAL BUILDINGS.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 3A) THERE IS NO LIFE SAFETY SHEET IN THIS SET OF PLANS.
 SHEET 002 3.1 IS A FLOOR PLAN WITH SOME REQUIREMENTS
 FROM THE NFPA BUT NONE OF THE REQUIREMENTS FOUND FOR
 THE 2017 FBC-B. FOR THIS REVIEW THE OCCUPANCY TYPE IS
 GOING TO BE CONSIDERED S1 A MOTOR VEHICLE REPAIR GARAGE
 COMPLYING WITH THE MAXIMUM QUANTITIES OF HAZARDOUS
 MATERIALS LISTED IN TABLE 307.1(1) SEE SECTION 406.8
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
  
 MISSING CODE DATA:
 SET BACK / SEPARATION (ASSUMED PROPERTY LINES)
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
 IF IN A FLOOD ZONE. PROPOSED FLOOD ELEVATION
 CERTIFICATE FOR STRUCTURES IN A SPECIFIC FLOOD HAZARD
 AREAS
 OCCUPANCY GROUP
 MINIMUM TYPE OF CONSTRUCTION
 FIRE RESISTANCE SEPARATION
  
 LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE
 FOLLOWING:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS OR NET
 MEANS OF EGRESS EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 QUANTITIES OF HAZARDOUS MATERIALS TABLE 307.1(1).
 PROVIDE QUANTITIES AND STORAGE TYPE + MSDS SHEETS.
  
 3B) ACCESSIBILITY CODE DETAILS:
  
 3B)(1) IN THE FLOOR PLAN DETAIL THE DOOR SWINGS INTO
 THE CLEAR FLOOR SPACE OF THE LAV AND WATER CLOSET
 PLEASE SHOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY
 603.2.3 AND OR EXCEPTIONS ON THE DETAIL FLOOR PLAN.
  
 3B)(2) IN BOTH ELEVATION VIEWS 2 & 3 THE GRAB BARS FOR
 THE WATER CLOSET BOTH SHOW THE GRAB BARS BEING MEASURED
 FROM THE FINISH FLOOR TO THE CENTER LINE OF THE GRAB
 BAR. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION
 OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 3C) THERE IS A DETAIL FOR THE DUMPSTER ENCLOSURE,
 PLEASE NOTE THE DUMPSTER ENCLOSURE TAKES A SEPARATE,
 REVIEW AND ASSOCIATED FEES.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE 105.1.
  
 3D) JUST TO THE RIGHT OF THE FLOOR PLAN SHOWS A
 CONCRETE SLAB WITH A ICE MACHINE AND (3) 500 GALLON
 FUEL TANKS. FUEL TANKS ALSO TAKE SEPARATE PERMITS
 REVIEWS AND ASSOCIATED FEES. 2017 FLORIDA BUILDING CODE
 W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE 105.1.
  
 3E) THERE IS A NOTE ON THE PLANS THAT THE FIRE
 SPRINKLER SYSTEM IS TO MEET THE CODE REQUIREMENTS AND
 FIRE MARSHAL REQUIREMENTS.
 IN THE 2017 FBC-B THE REQUIREMENTS FOR FIRE SPRINKLERS
 FOR REPAIR GARAGES IS FOUND UNDER 903.2.9.1 FOR REPAIR
 GARAGES & 903.2.10.1 FOR COMMERCIAL PARKING GARAGES, IN
 BOTH CASES THE REQUIREMENT FOR FIRE SPRINKLERS WOULD BE
 IF THE FIRE AREA EXCEEDED 5,000 FEET. NOTE THE NFPA
 REQUIREMENTS MAYBE MORE RESTRICTIVE, IF SO WE ALWAYS
 USE THE MORE RESTRICTIVE CODE REQUIREMENT.
  
 4) SHEET 003 4.1 DOES SHOW A COMPONENTS AND CLADDING
 CHART FOR WALL ZONES 4 & 5 BUT THERE IS NO WIND DESIGN
 CRITERIA GIVEN.
 WITHIN THE PLANS DRAWN BY GCP ARCHITECTURAL GROUP THERE
 IS NO ROOF PLAN WITH THE ASSOCIATED COMPONENTS AND
 CLADDING FOR ROOF ZONES 1, 2, OR 3.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 4.2. RISK CATEGORY.
  
 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 4.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5) WELDED OR BOLTED CONNECTIONS, THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 6A) COMPONENTS & CLADDING PLEASE SUPPLY THE PRODUCT
 APPROVAL FULL REPORTS. IF IN THE PRODUCT APPROVAL THERE
 ARE MULTIPLE SUB-SYSTEMS APPROVED IDENTIFY (CIRCLE)
 WHICH APPLICATION IS TO BE INSTALLED.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: METAL WALL PANELS, STOREFRONTS,
 CURTAIN WALLS, WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, METAL ROOF PANELS,
 LIGHTWEIGHT CONCRETE INSULATION, ROOF TOP VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 6B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6C) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 7) THE SHEETS SUBMITTED BY MBMI 4/ 10 WALL FRAMING &
 GIRTS AND SHEET 5/10 END WALL AND ROOF FRAMING WITH
 PURLINS ARE SHOWN.
 THE MISSING INFORMATION IS THE PRODUCT APPROVAL FOR THE
 METAL EXTERIOR WALL SYSTEM AND METAL ROOF SYSTEM.
 WITHOUT THE PRODUCT APPROVALS BEING SUBMITTED,
 IDENTIFYING THE TYPE OF WALL AND ROOF PANELS BEING
 INSTALLED, WITH THEIR ALLOWABLE SPACING BETWEEN
 SUPPORTS AND ASSOCIATED PRESSURES NO REVIEW FOR THE
 STRUCTURAL PORTION OF THE BUILDING CAN BE COMPLETED.
  
 8) THE OTHER UNKNOWN IS IF THE ENGINEER OF RECORD FOR
 MBMI HAS DESIGNED THE ROOF SYSTEM TO SECTION 2211.5 OF
 THE FBC-B AISI S210 OR AISI S 100? WITH A GREATER
 DEDUCTION IN PRESSURES THAN ALLOWED IN VASD?
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-12-17 Cont ID  
Sent By jleahy Date 2021-12-17 Time 10:59 Rev Time 0.00
Received By jleahy Date 2021-12-17 Time 10:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-19 Cont ID  
Sent By jleahy Date 2021-08-19 Time 16:32 Rev Time 0.00
Received By jleahy Date 2021-08-19 Time 16:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By jleahy Date 2020-07-31 Time 16:13 Rev Time 0.00
Received By jleahy Date 2020-07-31 Time 16:13 Sent To  
Notes
2020-07-31 16:16:54ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-2
  
 1) AIC RATING OF SERVICE AND PANEL PER 110.9, 110,10
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.
  
 PAGE E-1
  
 1) LIGHTING CONTROL PER FBC EEC REQUIRED
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2021-12-09 Cont ID  
Sent By rrossano Date 2021-12-09 Time   Rev Time 0.00
Received By rrossano Date 2021-12-09 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2021-08-04 Cont ID  
Sent By rrossano Date 2021-08-04 Time   Rev Time 0.00
Received By rrossano Date 2021-08-04 Time   Sent To  
Notes
2021-08-04 13:26:57PLEASE ADDRESS BUILDING COMMENTS.
 ARE THERE PROPOSED UTILITIES (WATER/SEWER)?
  
 FOR QUESTIONS ABOUT YOUR FAILED PLAN REVIEW COMMENTS OR
 HOW TO RESUBMIT, EMAIL [email protected] AND A BUILDING
 DIVISION TEAM MEMBER WILL HELP YOU.
  
 THANKS,
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By rrossano Date 2020-07-28 Time   Rev Time  
Received By rrossano Date 2020-07-28 Time   Sent To  
Notes
2020-07-28 12:07:13PLEASE ADDRESS BUILDING COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-11-30 Cont ID  
Sent By pleduc Date 2021-11-30 Time   Rev Time 0.00
Received By pleduc Date 2021-11-30 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-07-27 Cont ID  
Sent By pleduc Date 2021-07-27 Time   Rev Time 0.00
Received By pleduc Date 2021-07-27 Time 10:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-06-29 Cont ID  
Sent By pleduc Date 2020-06-29 Time   Rev Time 0.00
Received By pleduc Date 2020-06-29 Time 14:16 Sent To  
Notes
2020-06-29 14:28:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 3.1 - THEE IS AN INDICATION OF A FIRE
 SPRINKLER SYSTEM; HOWEVER, THERE ARE NO REQUIRED F.A.C.
 61G DOCUMENTS.
  
 AN ENGINEER OF RECORD IS REQUIRED TO SUBMITT F.A.C. 61G
 DOCUMENTS FOR WATER BASED FIRE PROTECTION
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 61G15-30.003 MINIMUM REQUIREMENTS FOR ENGINEERING
 DOCUMENTS.
 (1) ENGINEERING DOCUMENTS ARE PREPARED IN THE COURSE OF
 PERFORMING ENGINEERING SERVICES. WHEN PREPARED FOR
 INCLUSION WITH AN APPLICATION FOR A GENERAL BUILDING
 PERMIT, THE DOCUMENTS SHALL MEET ALL ENGINEER?S
 RESPONSIBILITY RULES, SET FORTH IN CHAPTERS 61G15-31,
 61G15-32, 61G15-33, AND 61G15-34, F.A.C., AND BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ADOPTED IN SECTION 553.73, F.S., AND APPLICABLE
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE AHJ. THE DOCUMENTS SHALL INCLUDE:
 (A) INFORMATION THAT PROVIDES MATERIAL SPECIFICATIONS
 REQUIRED FOR THE SAFE OPERATION OF THE SYSTEM THAT IS A
 RESULT OF ENGINEERING CALCULATIONS, KNOWLEDGE AND
 EXPERIENCE.
 (B) LIST FEDERAL, STATE, MUNICIPAL, AND COUNTY
 STANDARDS, CODES, ORDINANCES, LAWS, AND RULES, WITH
 THEIR EFFECTIVE DATES, THAT THE ENGINEERING DOCUMENTS
 ARE INTENDED TO CONFORM TO.
 (C) INFORMATION, AS DETERMINED BY THE ENGINEER OF
 RECORD, NEEDED FOR THE SAFE AND EFFICIENT OPERATION OF
 THE SYSTEM.
 (D) LIST ENGINEERING DESIGN CRITERIA; REFERENCE PROJECT
 SPECIFIC STUDIES, REPORTS, AND DELEGATED ENGINEERING
 DOCUMENTS.
 (E) IDENTIFY CLEARLY ELEMENTS OF THE DESIGN THAT VARY
 FROM THE GOVERNING STANDARDS AND DEPICT/IDENTIFY THE
 ALTERNATE METHOD USED TO ENSURE COMPLIANCE WITH THE
 STATED PURPOSE OF THESE RESPONSIBILITY RULES.
 (2) ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND
 BUSINESS ADDRESS, ON ENGINEERING DOCUMENTS. ENGINEERING
 DOCUMENTS WHICH ARE ISSUED FOR PRELIMINARY OR
 CONCEPTUAL USE, SHALL CLEARLY NOTE THE INTENDED PURPOSE
 OF SUCH DOCUMENTS.
 (3) WHEN ELEMENTS OF THE PROJECT ARE SHOWN ON AN
 ENGINEERING DOCUMENT ONLY FOR INFORMATION OR
 CLARIFICATION AND THE ENGINEER DOES NOT INTEND TO
 ACCEPT RESPONSIBILITY FOR THE ELEMENTS, THE ENGINEER
 SHALL CLEARLY NOTE ON THE DOCUMENTS THE EXTENT OF HIS
 RESPONSIBILITY.
 (4) ENGINEERING DRAWINGS SHALL BE LEGIBLE AND CLEARLY
 DEFINE AND DELINEATE THE WORK IN THE PROJECT. THEY MUST
 ALSO COMPLY WITH CHAPTER 61G15-23, F.A.C., SEALS.
 (5) ENGINEERS SHALL CLEARLY NOTE ON ANY PRELIMINARY
 ENGINEERING DOCUMENTS THAT SUCH DOCUMENTS ARE NOT IN
 FINAL FORM, BUT ARE BEING TRANSMITTED TO THE PUBLIC
 AGENCY TO RECEIVE AGENCY REVIEWS, COMMENTS AND
 INTERPRETATIONS. THE DOCUMENTS MAY SUBSEQUENTLY BE
 REVISED BY THE ENGINEER TO REFLECT RESOLUTION OF ISSUES
 WITH THE PUBLIC AGENCY PRIOR TO FINAL ACTION BY THE
 AGENCY. CHANGES, REVISIONS AND MODIFICATIONS TO A
 PROJECT MAY PROMPT ADDITIONAL DOCUMENT SUBMITTAL FOR
 AGENCY APPROVAL ACTION ON THE SAME PROJECT.
  
 SEPARATE SHOP DRAWINGS SHALL THEN BE SUBMITTED UNDER A
 SEPARATE PERMIT FOR INSTALLATION PURPOSES.
  
 PLEASE REVIEW AND PROVIDE
  
  
  
  
 2) SHEET E 1 & E 2 - THE FIRE SPRINKLER SYSTEM IS
 REQUIRED TO BE MONITORED.
  
 PER NFPA 101 CH 9
  
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE
 SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS CODE
 OR WHERE
 SUPERVISION OF A NEW FIRE SPRINKLER SYSTEM OR NEW FIRE
 ALARM
 SYSTEM IS REQUIRED BY THE FLORIDA BUILDING CODE.
  
 ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT
  
  
  
  
 3) SHEET 3.1 - THERE IS AN INDICATION OF 3 FUEL TANKS
 BU OTHERS.
  
 THE INSTALLATION OF THESE TANKS IS NOT APPROVIDE UNDER
 THIS PERMIT AND ANY WORK INVLOVING THESE TANKS SHALL BE
 DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-02-11 Cont ID  
Sent By vbroglia Date 2022-02-11 Time 11:51 Rev Time 0.00
Received By vbroglia Date 2022-02-11 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-17 Cont ID  
Sent By jleahy Date 2021-12-17 Time 10:59 Rev Time 0.00
Received By jleahy Date 2021-11-29 Time 17:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-28 Cont ID  
Sent By lmarchan Date 2021-09-28 Time 08:15 Rev Time 0.00
Received By lmarchan Date 2021-07-26 Time 10:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-10 Cont ID  
Sent By cpuell Date 2020-08-10 Time 14:37 Rev Time 0.00
Received By cpuell Date 2020-06-25 Time 09:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-04-26 Cont ID  
Sent By aoliver Date 2022-04-26 Time 11:03 Rev Time 0.00
Received By aoliver Date 2022-02-02 Time 12:29 Sent To  
Notes
2022-04-26 10:09:03RECEIPT MU-2022-007750 - $2862.63 PAID
2022-02-02 12:29:152/2/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-07-12 Cont ID  
Sent By jwitmer Date 2020-07-12 Time 13:43 Rev Time 0.00
Received By jwitmer Date 2020-07-12 Time 08:15 Sent To  
Notes
2020-07-12 13:36:01IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-01-24 Cont ID  
Sent By medwards Date 2022-01-24 Time 09:08 Rev Time 0.00
Received By medwards Date 2022-01-24 Time 09:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-12-09 Cont ID  
Sent By medwards Date 2021-12-09 Time 06:15 Rev Time 0.00
Received By medwards Date 2021-12-09 Time 06:14 Sent To  
Notes
2021-12-09 06:15:242ND REVIEW FBC-2020 MECHANICAL
 PERMIT-20040867
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ORIGINAL SHEET 1.1 COVER SHEET LISTED OCCUPANCY
 GROUP AS S1 (MAINTENANCE), THE REVISED SHEET 1.1 LISTS
 THE OCCUPANCY GROUP AS S1 (MAINTENANCE BUILDING) MOTOR
 VEHICLE REPAIR GARAGE. THIS IS A BIG CHANGE AS FAR AS
 THE MECHANICAL CODE GOES. PLEASE SHOW THAT THIS REPAIR
 GARAGE ALSO MEETS FBC M 502.14 FOR HAVING A SOURCE
 CAPTURE SYSTEM OR THAT IT MEETS ONE OF THE EXCEPTIONS.
 IF IT DOES MEET ONE OF THE EXCEPTIONS PLEASE ADD A NOTE
 ON THE DRAWING STATING THIS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-07-27 Cont ID  
Sent By medwards Date 2020-07-27 Time 09:55 Rev Time 0.00
Received By medwards Date 2020-07-27 Time 09:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-01-25 Cont ID  
Sent By jesmith Date 2022-01-25 Time 15:15 Rev Time 0.00
Received By jesmith Date 2022-01-25 Time 08:41 Sent To  
Notes
2022-01-25 15:13:4620040867 976 27TH ST
  
 PLUMBING COMMENTS: APPROVED
  
 A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 CERTIFICATION OF BACKFLOW PREVENTER SHALL BE ONSITE AT
 TIME OF INSPECTION
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-12-16 Cont ID  
Sent By ccole Date 2021-12-16 Time 14:39 Rev Time 0.00
Received By ccole Date 2021-12-16 Time 12:40 Sent To  
Notes
2021-12-16 14:42:031ST REVIEW FBC-2020 PLUMBING
 PERMIT- 20040867
 12/16/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 WPB CROSS CONNECTION CONTROL MANUAL- WPB CCCM
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: 3RD REQUEST FOR CIVIL DRAWINGS AND
 BACKFLOW PREVENTER SPECIFICATIONS. COPIED BELOW ARE THE
 1ST AND 2ND PLUMBING REVIEW COMMENTS REQUESTING THE
 DRAWINGS AND BACKFLOW PREVENTER LOCATION AND SPECS. THE
 ENGINEER'S RESPONSE NARRATIVE INDICATE THE PDF'S WERE
 SUBMITTED HOWEVER IT APPEARS THEY WERE NOT UPLOADED FOR
 REVIEW. THE PLANS SETS SHALL INCLUDE WATER/SEWER AND
 DRAINAGE PLANS. WATER/SEWER SHALL SHOW LOCATIONS OF
 WATER MAIN, POINT OF WATER SERVICE CONNECTION, METER
 AND BACKFLOW LOCATION, SEWER LATERAL, SEWER/BUILDING
 DRAIN POINT OF CONNECTION. DRAINAGE PLANS SHALL SHOW
 STORM DRAIN LATERAL AND BUILDING STORM DRAIN POINTS OF
 CONNECTION, AND/OR LOCATIONS OF ROOF DRAINAGE AREAS,
 AND CATCH BASINS- SECS. 107.2.1, 110.9 WPB AND SEC.
 1101.2 FBC P.
  
 PREVIOUS PLUMBING COMMENTS:
 D. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, WPB CCCM
 AND FBC PL 608, PROVIDE SPECIFICATION, DETAIL AND
 LOCATION FOR THE WATER SERVICE BACKFLOW PREVENTER.
 RESPONSE: CIVIL DRAWINGS TO ADDRESS.
 NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE CIVIL
 DRAWINGS; PROVIDE SPECIFICATION, DETAIL AND LOCATION
 FOR THE WATER SERVICE BACKFLOW PREVENTER COMPLYING WITH
 WPB CCCM AND FBC PL 608.
 E. SECOND REQUEST; SEE PLAN SHEET P.1: PER WPB FBC
 107.2.1, PROVIDE CIVIL DRAWINGS NOTED AT SERVICE
 CONNECTIONS.
 PLEASE NOTE: A PLUMBING PERMIT WILL NOT BE ISSUED WITH
 OUT THE CIVIL DRAWINGS SHOWING THE REQUESTED
 INFORMATION FOR THE BACKFLOW PREVENTER. WPB FBC
 107.2.1.2.
  
 NEW COMMENT: A SEPARATE PERMIT IS REQUIRED FOR
 ISTALLATION OF THE POTABLE WATER SERVICE BACKFLOW
 PRVENTER.
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-05 Cont ID  
Sent By pvalenti Date 2021-08-05 Time 16:26 Rev Time 0.00
Received By jesmith Date 2022-01-13 Time 12:27 Sent To  
Notes
2021-08-05 16:27:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20040867 936 27TH ST
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 A.NEW COMMENTS REGARDING ICE MACHINE IN SCOPE OF WORK:
 1.PER WPB FBC 107.2.1, SHOW COLD WATER ROUTING TO ICE
 MACHINE ON FLOOR PLAN TO MATCH RISER DIAGRAM.
 2.PER FBC PL 606.2.2 AND 606.3, PROVIDE DEDICATED,
 ACCESSIBLE SHUT OFF VALVE FOR HOSE BIB AT ICE MACHINE
 VICINITY
 3.PER FBC PL 606.2.3 AND 606.3, PROVIDE DEDICATED,
 ACCESSIBLE SHUT OFF VALVE FOR ICE MACHINE.
  
  
 B.NEW COMMENT REGARDING RECIRCULATING PUMP PIPING
 DETAIL:
 PER FBC 107.2.1,
 1.SHOW COLD WATER TO WATER HEATER; SHOW SHUT OFF VALVE
 AT UPSTREAM END, FOLLOWED BY CHECK VALVE, THEN
 EXPANSION TANK THEN RETURN CONNECTION, THEN CONNECTION
 TO WATER HEATER.
 2.SHOW RETURN WITH BALL VALVE AT UPSTREAM END, FOLLOWED
 BY CHECK VALVE THEN THE PUMP AND CONNECTION TO COLD
 WATER
  
 C. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, PROVIDE A
 NOTE STATING ?ALL PIPING SHALL BE SUPPORTED IN
 ACCORDANCE WITH 2017 FBC PLUMBING CODE SECTION 308?.
 COMPLIED
 NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE HANGER DETAIL
 WITH HANGER TYPE, ROD AND ATTACHMENTS TO STRUCTURE.
  
 D. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, WPB CCCM
 AND FBC PL 608, PROVIDE SPECIFICATION, DETAIL AND
 LOCATION FOR THE WATER SERVICE BACKFLOW PREVENTER.
 RESPONSE: CIVIL DRAWINGS TO ADDRESS.
 NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE CIVIL
 DRAWINGS; PROVIDE SPECIFICATION, DETAIL AND LOCATION
 FOR THE WATER SERVICE BACKFLOW PREVENTER COMPLYING WITH
 WPB CCCM AND FBC PL 608.
  
 E. SECOND REQUEST; SEE PLAN SHEET P.1: PER WPB FBC
 107.2.1, PROVIDE CIVIL DRAWINGS NOTED AT SERVICE
 CONNECTIONS.
 PLEASE NOTE: A PLUMBING PERMIT WILL NOT BE ISSUED WITH
 OUT THE CIVIL DRAWINGS SHOWING THE REQUESTED
 INFORMATION FOR THE BACKFLOW PREVENTER. WPB FBC
 107.2.1.2.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 20040867 936 27TH ST

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-30 Cont ID  
Sent By jesmith Date 2020-07-30 Time 17:37 Rev Time 0.00
Received By jesmith Date 2020-07-30 Time 15:49 Sent To  
Notes
2020-07-30 17:36:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20040867 936 27TH ST
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 2. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS
 HAS BEEN MADE BASED UPON INFORMATION PROVIDED ON PLAN
 SHEET 1.1; CODE SUMMARY.
 3. SEE PLAN SHEET 3.1: PER WPB FBC 107.2.1, SHOW
 TURNING SPACE FOR WATER CLOSET COMPLYING WITH FBC ACC
 304.3.1 OR 304.3.2.
 4. 5. SEE PLAN SHEET 3.1: THE FLOOR PLAN DETAIL THE
 DOOR SWINGS INTO THE CLEAR FLOOR SPACE OF THE LAVATORY
 AND WATER CLOSET; PLEASE SHOW COMPLIANCE WITH FBC ACC
 603.2.3 AND OR EXCEPTIONS ON THE DETAIL FLOOR PLAN
 6. SEE PLAN SHEET 3.1: JUST TO THE RIGHT OF THE FLOOR
 PLAN SHOWS A CONCRETE SLAB WITH AN ICE MACHINE AND (3)
 500 GALLON FUEL TANKS. IS THE CONCRETE SLAB AND
 EQUIPMENT IN THE SCOPE OF WORK? PER WPB FBC 107.2.1,
 CLARIFY. PLEASE NOTE THAT WATER SUPPLY TO THE ICE
 MACHINE IS REQUIRED AND RISER AND PLAN VIEW OF PIPING
 WITH REQUIRED BACKFLOW PROTECTION IS REQUIRED PER FBC
 PL CHAPTER 6. FUEL TANKS ALSO TAKE SEPARATE PERMITS
 REVIEWS AND ASSOCIATED FEES. 2017 FLORIDA BUILDING CODE
 W/2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE 105.1.
 7. SEE PLAN SHEET P.1: THE PLUMBING LEGEND TEXT IS NOT
 LEGIBLE. PER WPB FBC 107.2.1, CORRECT DEFICIENCY.
 8. SEE PLAN SHEET P.1: PER FBC PL 608.1, MOP SERVICE
 SINK FAUCET SHALL BE PROVIDED WITH A BACKFLOW
 PREVENTIVE DEVICE.
 9. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, PROVIDE
 MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 THE ELECTRIC WATER HEATER.
 10. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, PROVIDE
 MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 THE WATER HEATER SUPPORT BRACKET AND ON THE PLAN
 PROVIDE A DETAIL FOR SAME TO INCLUDE ANCHORING.
 12. 11. SEE PLAN SHEET P.1: WATER RISER; PER WPB FBC
 107.2.1, SHOW WATER SUPPLY TO P-1 WATER CLOSET.
 13. SEE PLAN SHEET P.1: COMPRESSED AIR; PER WPB FBC
 107.2.1,PROVIDE A RISER DIAGRAM.
 14. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, PROVIDE A
 NOTE STATING "ALL PIPING SHALL BE SUPPORTED IN
 ACCORDANCE WITH 2017 FBC PLUMBING CODE SECTION 308".
 15. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, WPB CCCM
 AND FBC PL 608, PROVIDE SPECIFICATION, DETAIL AND
 LOCATION FOR THE WATER SERVICE BACKFLOW PREVENTER.
 16. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, PROVIDE
 CIVIL DRAWINGS NOTED AT SERVICE CONNECTIONS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20040867 936 27TH ST
  
  

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status N Date 2021-12-16 Cont ID  
Sent By ccole Date 2021-12-16 Time 14:50 Rev Time 0.00
Received By ccole Date 2021-12-16 Time 14:49 Sent To  
Notes
2021-12-16 14:51:30NO IRRIGATION PLANS SUBMITTED. A SEPARATE PRIMARY
 PERMIT AND PLANS ARE REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2022-01-26 Cont ID  
Sent By jwitmer Date 2022-01-26 Time 06:44 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-01-26 06:48:00ROOFING PRODUCT APPROVAL: FL 17700.5 R2
 WHIRLWIND STEEL BUILDING
 SUPER SPAN X ROOF PANEL MIN. 26 GA. STEEL, 36 INCH WIDE
 PANEL, THROUGH FASTENED STRUCTURAL ROF PANELS.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2021-12-01 Cont ID  
Sent By jwitmer Date 2021-12-01 Time 09:16 Rev Time 0.00
Received By jwitmer Date 2021-12-01 Time 07:49 Sent To  
Notes
2021-12-01 09:16:48ROOF SEE BUILDING REVIEW NOTES. 3RD REVIEW NO ROOFING
 PRODUCT APPROVAL WERE SUBMITTED TO VERIFY SPANS VERSES
 PRESSURES, DESIGNER IS DESIGNEING THE ROOF TO AISI S
 100!!!!!!

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-08-03 Cont ID  
Sent By jwitmer Date 2021-08-03 Time 14:20 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-08-03 14:20:40SEE BUILDING REVIEW.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-07-12 Cont ID  
Sent By jwitmer Date 2020-07-12 Time 13:43 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-07-12 13:34:38ROOF SEE BUILDING REVIEW NOTES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-01-26 Cont ID  
Sent By jwitmer Date 2022-01-26 Time 06:55 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-11-30 Cont ID  
Sent By rmcdouga Date 2021-11-30 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2021-11-30 Time 09:29 Sent To  
Notes
2021-11-30 09:31:02PAPER PLANS WITH ORIGINAL SIGNATURES AND SEALS WERE
 SUBMITTED FOR THE FOLLOWING SHEETS: 1.1, 3.1, 4.1, 6.1,
 10.1, 11.1, 11.2, 11.3, S-1, P-1, E-1, E-2 AND M-1.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-07-27 Cont ID  
Sent By medwards Date 2021-07-27 Time 10:15 Rev Time 0.00
Received By medwards Date 2021-07-27 Time 10:15 Sent To  
Notes
2021-07-27 10:21:29THE FOLLOWING SHEETS HAVE A PRINTED COPY OF A DIGITAL
 SIGNATURE. PLEASE PROVIDE ORIGINAL SIGNED DIGITAL
 SEALED DRAWINGS BY THE ENGINEER AND ARCHITECT OF
 RECORD. YOU MAY BRING ORIGINAL SIGNED AND SEALED PAPER
 DRAWINGS TO OUR OFFICE.
 SHEETS: 1.1, 3.1, 4.1, 6.1, 10.1, 11.1, 11.2, 11.3,
 S-1, P-1, E-1, E-2,
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By jleahy Date 2020-07-31 Time 16:17 Rev Time 0.00
Received By jleahy Date 2020-07-31 Time 16:17 Sent To  
Notes
2020-07-31 16:18:26PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED (AND SEALED FOR DESIGN
 PROFESSIONALS) BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED OR SIGNED/SEALED
 PAPER SET MAY BE SUPPLIED TO THE BUILDING DEPARTMENT
 WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
2020-07-12 13:38:54THERE ARE NO SIGNATURE NOR SEALS ON THE ARCHITECTURAL
 PLANS BY GCP ARCHITECTURE NOR ON THE SHEETS PRODUCED BY
 MBMI METAL BUILDINGS. J. W. 7/12/2020

Review Stop Z ZONING
Rev No 3 Status P Date 2022-02-11 Cont ID  
Sent By vbroglia Date 2022-02-11 Time 11:28 Rev Time 0.00
Received By vbroglia Date 2022-02-11 Time 11:28 Sent To  
Notes
2022-02-11 11:50:582/11/22-
  
 SEPARATE PERMIT REQUIRED FOR LANDSCAPING, MECHANICAL,
 DUMPSTER ENCLOSURE AND FENCE/WALLS
 PLEASE SUBMIT A LANDSCAPE PERMIT TO ALLOW STAFF TO MOVE
 FORWARD WITH PERMIT
  
 DUMPSTER ENCLOSURE REQUIRES A MINIMUM OF 13 FEET
 OPENING WIDTH
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-09-27 Cont ID  
Sent By rthermid Date 2021-09-27 Time   Rev Time 0.00
Received By rthermid Date 2021-09-27 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-08-10 Cont ID  
Sent By rthermid Date 2020-08-10 Time   Rev Time  
Received By rthermid Date 2020-08-10 Time   Sent To I
Notes
2020-08-10 12:26:38ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 8/10/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A SURVEY OF THE PROPERTY SHOWING
 SETBACKS OF THE PROPOSED STRUCTURE TO THE PROPERTY
 LINES
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved