Plan Review Details - Permit 20040726
Plan Review Stops For Permit 20040726
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-09-04 Cont ID  
Sent By cthroop Date 2021-09-04 Time 10:09 Rev Time 0.00
Received By cthroop Date 2021-09-03 Time 14:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-08-04 Cont ID  
Sent By cthroop Date 2021-08-04 Time 08:54 Rev Time 0.00
Received By cthroop Date 2021-08-02 Time 17:46 Sent To  
Notes
2021-08-04 09:00:20PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
  
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES.
 ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
  
 NOTICE: THE PROPOSED STRUCTURES ARE LOCATED IN A
 SPECIAL FLOOD HAZARD AREA (SFHA) WITH A BASE FLOOR
 ELEVATION (BFE) OF 7.0 FEET NAVD. BUILDINGS AND
 STRUCTURES LOCATED IN SFHA'S SHALL BE DESIGNED PER FBC
 R322.
  
 DESIGNER SHALL PLACE NOTE ON PLAN:
  
 R322.1.2STRUCTURAL SYSTEMS.
 STRUCTURAL SYSTEMS OF BUILDINGS AND STRUCTURES SHALL BE
 DESIGNED, CONNECTED AND ANCHORED TO RESIST FLOTATION,
 COLLAPSE OR PERMANENT LATERAL MOVEMENT DUE TO
 STRUCTURAL LOADS AND STRESSES FROM FLOODING EQUAL TO
 THE DESIGN FLOOD ELEVATION.
  
 1. SITE PLAN. CORRECTED
  
 2. FOUNDATIONS FOR WALLS AND COLUMNS AT PROPERTY LINE
 SHALL NOT ENCROACH ONTO ADJOINING PROPERTY. CORRECTED
  
 3. NOTE ON PLAN STATES SLIDING GATES WILL BE MOTORIZED.
 (PROVIDE ELCTRICAL PLAN).
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 NEW COMMENTS:
  
 4. PROVIDE UTILITY EASEMENT RELEASE FORMS. (PROVIDE
 RELEASE FORMS FROM FPL AND FPU)
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 5. FRONT GATES (CORRECTED)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-02-02 Cont ID  
Sent By cthroop Date 2021-02-02 Time 13:55 Rev Time 0.00
Received By cthroop Date 2021-02-02 Time 08:10 Sent To  
Notes
2021-02-02 14:06:12PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES.
 ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
  
 NOTICE: THE PROPOSED STRUCTURES ARE LOCATED IN A
 SPECIAL FLOOD HAZARD AREA (SFHA) WITH A BASE FLOOR
 ELEVATION (BFE) OF 7.0 FEET NAVD. BUILDINGS AND
 STRUCTURES LOCATED IN SFHA'S SHALL BE DESIGNED PER FBC
 R322.
  
 DESIGNER SHALL PLACE NOTE ON PLAN:
  
 R322.1.2STRUCTURAL SYSTEMS.
 STRUCTURAL SYSTEMS OF BUILDINGS AND STRUCTURES SHALL BE
 DESIGNED, CONNECTED AND ANCHORED TO RESIST FLOTATION,
 COLLAPSE OR PERMANENT LATERAL MOVEMENT DUE TO
 STRUCTURAL LOADS AND STRESSES FROM FLOODING EQUAL TO
 THE DESIGN FLOOD ELEVATION.
  
 1. SITE PLAN. CORRECTED
  
 2. FOUNDATIONS FOR WALLS AND COLUMNS AT PROPERTY LINE
 SHALL NOT ENCROACH ONTO ADJOINING PROPERTY. CORRECTED
  
 3. NOTE ON PLAN STATES SLIDING GATES WILL BE MOTORIZED.
 (PERMIT 20040727 FOR GATES SHOULD BE CLOSED)
 PROVIDE ELCTRICAL PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 NEW COMMENTS:
  
 4. PROVIDE UTILITY EASEMENT RELEASE FORMS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-06-12 Cont ID  
Sent By cthroop Date 2020-06-12 Time 14:57 Rev Time 0.00
Received By cthroop Date 2020-06-12 Time 11:57 Sent To  
Notes
2020-06-12 15:04:07PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES.
 ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
  
 NOTICE: THE PROPOSED STRUCTURES ARE LOCATED IN A
 SPECIAL FLOOD HAZARD AREA (SFHA) WITH A BASE FLOOR
 ELEVATION (BFE) OF 7.0 FEET NAVD. BUILDINGS AND
 STRUCTURES LOCATED IN SFHA'S SHALL BE DESIGNED PER FBC
 R322.
  
 R322.1.2STRUCTURAL SYSTEMS.
 STRUCTURAL SYSTEMS OF BUILDINGS AND STRUCTURES SHALL BE
 DESIGNED, CONNECTED AND ANCHORED TO RESIST FLOTATION,
 COLLAPSE OR PERMANENT LATERAL MOVEMENT DUE TO
 STRUCTURAL LOADS AND STRESSES FROM FLOODING EQUAL TO
 THE DESIGN FLOOD ELEVATION.
  
 1. SITE PLAN. CORRECTED
  
 2. FOUNDATIONS FOR WALLS AND COLUMNS AT PROPERTY LINE
 SHALL NOT ENCROACH ONTO ADJOINING PROPERTY. PROVIDE
 STRUCTURAL DETAIL FOR FOUNDATIONS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 (NOTE ON PLAN PAGE L2 STATES FACE OF WALL WILL BE 6
 INCHES INSIDE PROPERTY LINE. WALL TYPE 1 PAGE AL-1
 ALONG N FLAGLER DRIVE HAS A 24 INCH FOUNDATION WITH AN
 8 INCH WALL. THIS FOUNDATION WILL ENCROACH ONTO
 ADJACENT PROPERTY)
  
 3. NOTE ON PLAN STATES SLIDING GATES WILL BE MOTORIZED.
 PROVIDE ELCTRICAL PLAN. (NOT APPLICABLE - SEE PERMIT
 20040727 FOR GATES)
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-14 Cont ID  
Sent By cthroop Date 2020-05-14 Time 09:52 Rev Time 0.00
Received By cthroop Date 2020-05-14 Time 06:54 Sent To  
Notes
2020-05-14 09:59:03PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 NOTICE: THE PROPOSED STRUCTURES ARE LOCATED IN A
 SPECIAL FLOOD HAZARD AREA (SFHA) WITH A BASE FLOOR
 ELEVATION (BFE) OF 7.0 FEET NAVD. BUILDINGS AND
 STRUCTURES LOCATED IN SFHA'S SHALL BE DESIGNED PER FBC
 R322.
  
 R322.1.2STRUCTURAL SYSTEMS.
 STRUCTURAL SYSTEMS OF BUILDINGS AND STRUCTURES SHALL BE
 DESIGNED, CONNECTED AND ANCHORED TO RESIST FLOTATION,
 COLLAPSE OR PERMANENT LATERAL MOVEMENT DUE TO
 STRUCTURAL LOADS AND STRESSES FROM FLOODING EQUAL TO
 THE DESIGN FLOOD ELEVATION.
  
 1. SITE PLAN. IDENTIFY LOCATION OF PROPOSED STRUCTURES.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 2. FOUNDATIONS FOR WALLS AND COLUMNS AT PROPERTY LINE
 SHALL NOT ENCROACH ONTO ADJOINING PROPERTY. PROVIDE
 STRUCTURAL DETAIL FOR FOUNDATIONS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. NOTE ON PLAN STATES SLIDING GATES WILL BE MOTORIZED.
 PROVIDE ELCTRICAL PLAN.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-09-04 Cont ID  
Sent By jleahy Date 2021-09-04 Time 11:42 Rev Time 0.00
Received By jleahy Date 2021-07-27 Time 11:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-12 Cont ID  
Sent By cthroop Date 2020-06-12 Time 15:04 Rev Time 0.00
Received By cthroop Date 2020-06-12 Time 14:34 Sent To  
Notes
2020-06-12 15:07:22PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTE ON PLAN STATES SLIDING GATES WILL BE MOTORIZED.
 (PERMIT 20040727 FOR GATES SHOULD BE CLOSED)
  
 1. ELECTRICAL SUB-PERMIT REQUIRED.
 PERMITS 105.1 REQUIRED.
  
 2. PROVIDE AN ELCTRICAL PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE AN UPDATED PANEL SCHEDULE.
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2021-08-04 Cont ID  
Sent By rrossano Date 2021-08-04 Time   Rev Time 0.00
Received By rrossano Date 2021-08-04 Time   Sent To  
Notes
2021-08-04 11:22:40PASSED WITH PROVISO:
  
 PLEASE ADDRESS BUILDING COMMENTS.
  
 CALL FOR LOCATES, DIAL 811 BEFORE YOU DIG. FOR MORE
 INFO ON "CALL BEFORE YOU DIG", GO TO
 HTTP://WWW.SUNSHINE811.COM (REF: UNDERGROUND FACILITY
 DAMAGE PREVENTION AND SAFETY ACT, FLORIDA STATUTE,
 CHAPTER 556.)
  
 THANKS,
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2021-02-15 Cont ID  
Sent By rrossano Date 2021-02-15 Time   Rev Time 0.00
Received By rrossano Date 2021-02-15 Time   Sent To I
Notes
2021-02-15 19:40:05PLEASE RESPOND TO PREVIOUS ENGINEERING COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-11-16 Cont ID  
Sent By rrossano Date 2020-11-16 Time   Rev Time 0.00
Received By rrossano Date 2020-11-16 Time   Sent To I
Notes
2020-11-16 09:59:51CONFIRM RIGHT OF WAY IS SHOWN CORRECTLY ON SHEET L2 AND
 PLEASE PROVIDE SURVEY SHOWING PLACEMENT OF PROPOSED
 PAVERS RELATIVE TO RIGHT OF WAY.
  
 THE PAVER DRIVEWAY AGREEMENT IS A REQUIREMENT IF PAVERS
 ARE USED IN THE RIGHT OF WAY PORTION OF THE DRIVEWAY.
 THE AGREEMENT MUST BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE - RECORDING DEPT. 4.25. A RECORDED COPY OF
 THIS DOCUMENT SHOULD BE FAXED TO (561) 494-1116.
 ATTENTION: DRIVEWAY REVIEWER. DOCUMENT NEEDS TO BE
 RECORDED PRIOR TO FINAL SIGN OFF.
  
 FOR A PDF COPY OF THE PAVER DRIVEWAY AGREEMENT, FEEL
 FREE TO EMAIL ME AT [email protected]
  
 THANKS,
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-09-04 Cont ID  
Sent By jleahy Date 2021-09-04 Time 10:32 Rev Time 0.00
Received By jleahy Date 2021-08-26 Time 07:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-08-13 Cont ID  
Sent By cthroop Date 2021-08-13 Time 17:40 Rev Time 0.00
Received By ccarvaja Date 2021-07-20 Time 13:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-16 Cont ID  
Sent By shill Date 2021-02-16 Time 14:55 Rev Time 0.00
Received By shill Date 2021-01-20 Time 16:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-12 Cont ID  
Sent By cthroop Date 2020-06-12 Time 15:07 Rev Time 0.00
Received By cthroop Date 2020-06-01 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-22 Cont ID  
Sent By shill Date 2020-05-22 Time 11:52 Rev Time 0.00
Received By shill Date 2020-05-05 Time 10:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-09-04 Cont ID  
Sent By cthroop Date 2021-09-04 Time 10:09 Rev Time 0.00
Received By cthroop Date 2021-09-03 Time 14:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-08-04 Cont ID  
Sent By cthroop Date 2021-08-04 Time 09:00 Rev Time 0.00
Received By cthroop Date 2021-08-02 Time 17:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-02-02 Cont ID  
Sent By cthroop Date 2021-02-02 Time 13:55 Rev Time 0.00
Received By cthroop Date 2021-02-02 Time 08:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-12 Cont ID  
Sent By cthroop Date 2020-06-12 Time 14:35 Rev Time 0.00
Received By cthroop Date 2020-06-12 Time 11:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-14 Cont ID  
Sent By cthroop Date 2020-05-14 Time 09:35 Rev Time 0.00
Received By cthroop Date 2020-05-14 Time 06:54 Sent To  
Notes
2020-05-14 09:37:51NOTICE: P.E. SELF CERTIFIED DIGITAL SIG. & SEAL ON SITE
 PLAN. NOTIFIED P.E. THAT THIS WILL ONLY BE ALLOWED ONE
 TIME. ADDED NAME TO SPREAD SHEET ON F-DRIVE. CT

Review Stop Z ZONING
Rev No 4 Status P Date 2021-08-13 Cont ID  
Sent By awooten Date 2021-08-13 Time   Rev Time 0.00
Received By llouie Date 2021-08-13 Time   Sent To  
Notes
2021-08-13 16:40:20* SEPARATE PERMIT REQUIRED FOR SITE LIGHTING. PERMIT
 FOR HARDSCAPE ONLY.
  
 * EASEMENT CONSENT FORMS FROM ATT, WPB, FPU, FPL AND
 COMCAST RECEVIED.

Review Stop Z ZONING
Rev No 3 Status F Date 2021-02-01 Cont ID  
Sent By llouie Date 2021-02-01 Time   Rev Time 0.00
Received By llouie Date 2021-02-01 Time   Sent To  
Notes
2021-02-01 16:41:51** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PLAN SHOWS THAT THE 5 FT. WIDE UTILITY EASEMENT
 ALONG THE EAST PROPERTY LINE HAS BEEN ABANDONED. PLEASE
 PROVIDE DOCUMENTATION THAT THE EASEMENT HAS BEEN
 ABANDONED AS THERE SEEMS TO BE STRUCTURES LOCATED
 WITHIN THE ABANDONED EASEMENT.
  
 2.) THE MODIFIED DRIVEWAY SHALL NOT EXCEED 20 FEET AT
 THE PROPERTY LINE. THE REVISED PLAN SHOWS THAT THAT THE
 DRIVEWAY EXCEEDS 20 FT. AT THE PROPERTY LINE INTO THE
 PROPERTY.
  
 3.) THE PROPOSED ENTRY WALKWAY GATE ON THE NORTH SIDE
 OF THE PROPERTY SHALL NOT SWING OUT INTO THE PUBLIC
 RIGHT-OF-WAY (MUST SWING INTERIOR TO THE PROPERTY). ALL
 STRUCTURAL ELEMENTS MUST BE LOCATED ON PRIVATE PROPERTY
 AND CANNOT EXTEND BEYOND THE PROPERTY LINE.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  
 * MASTER PERMIT: #19050386.

Review Stop Z ZONING
Rev No 2 Status F Date 2020-06-12 Cont ID  
Sent By awooten Date 2020-06-12 Time   Rev Time 0.00
Received By awooten Date 2020-06-12 Time   Sent To  
Notes
2020-06-12 12:49:04*********ZONING REVIEW FAILED********** REPEAT COMMENT
  
 PROVIDE A COPY OF THE SURVEY.
  
 THE PROPOSED FENCE/WALL LOCATION FALLS INSIDE OF THE
 FIVE FOOT EASMENT. PROVIDE FIVE EASEMENT RELEASE FORMS
 FOR FENCE/WALL.
  
 IS THE HEIGHT OF THE ENITRE FENCE/WALL SIX FEET?
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By awooten Date 2020-05-21 Time   Rev Time  
Received By   Date 2020-05-21 Time   Sent To  
Notes
2020-05-21 16:31:09*********ZONING REVIEW FAILED**********
  
 PROVIDE A COPY OF THE SURVEY.
  
 THE PROPOSED FENCE/WALL LOCATION FALLS INSIDE OF THE
 FIVE FOOT EASMENT. PROVIDE FIVE EASEMENT RELEASE FORMS
 FOR FENCE/WALL.
  
 IS THE HEIGHT OF THE ENITRE FENCE/WALL SIX FEET?
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  
  
  
  