Plan Review Details - Permit 20040725
Plan Review Stops For Permit 20040725
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-05-15 Cont ID  
Sent By rmcdouga Date 2020-05-15 Time 11:50 Rev Time 0.00
Received By rmcdouga Date 2020-05-15 Time 11:50 Sent To  
Notes
2020-05-15 11:51:20ASBESTOS COMPLIANCE LETTER WAS SUBMITTED WITH THE
 SEPARATE INTERIOR DEMO PERMIT #20030920.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-04-30 Cont ID  
Sent By rmcdouga Date 2020-04-30 Time 11:42 Rev Time 0.00
Received By rmcdouga Date 2020-04-30 Time 11:42 Sent To  
Notes
2020-04-30 11:44:22PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-05-15 Cont ID  
Sent By rmcdouga Date 2020-05-15 Time 11:30 Rev Time 0.00
Received By rmcdouga Date 2020-05-15 Time 11:30 Sent To  
Notes
2020-05-15 11:34:57BUILDING PROVISO
  
 1) ALL SALES AND SERVICE COUNTERS SHALL COMPLY WITH FBC
 ACCESSIBILITY SECTION 904.4.1.
 2) HANDRAILS AT THE BOTTOM OF STAIRS SHALL COMPLY WITH
 FBC ACCESSIBILITY SECTION 505.10.3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-04 Cont ID  
Sent By rmcdouga Date 2020-05-04 Time 13:09 Rev Time 0.00
Received By rmcdouga Date 2020-04-30 Time 11:44 Sent To  
Notes
2020-05-04 13:09:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEITHER THE LIFE SAFETY SHEET A1.1 OR THE FLOOR PLAN
 SHEETS A2.1 & A2.2 SHOW ANY ACCESSIBILITY ELEMENTS FOR
 DINING, PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-EXISTING BUILDING SECTION 806.1 A BUILDING, OR
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE,
 ACCESSIBILITY CODE. THE LIFE SAFETY SHEET DOES NOT SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE;
 1A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 1B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 1C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, BAR TOPS, HIGH TOPS AND OR OUTDOOR
 DINING AREAS.
  
 1D) 902.1 DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, BABY CHANGING AND
 OTHER TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS.
  
 1D) - (1)CLEAR FLOOR SPACE SHALL BE PROVIDED FOR A
 PARALLEL OR FORWARD APPROACH. FORWARD APPROACHES
 REQUIRE KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL
 BE PROVIDED OF THE 2017 FBC-ACCESSIBILITY CODE.
  
 1D) - (2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND, 2017
 FBC-ACCESSIBILITY CODE.
  
 2) THE PLANS DO NOT SHOW ACCESSIBILITY COMPLIANCE WITH
 THE REQUIRED COUNTER HEIGHT FOR THE BAR/POINT OF SALE
 LOCATED IN THE STUDENT ENGAGEMENT AREA. 2017
 ACCESSIBILITY CODE. SALES & SERVICE COUNTERS. 904.4.1.
 A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES LONG
 MINIMUM AND 36 INCHES HIGH MAXIMUM ABOVE THE FINISH
 FLOOR SHALL BE PROVIDED. A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 SHALL BE POSITIONED FOR A PARALLEL
 APPROACH ADJACENT TO THE 36 INCH MINIMUM LENGTH
 COUNTER.
  
 3) THE EXISTING BATHROOMS THAT SERVICE THE PRIMARY
 FUNCTION AREA FOR THIS PROJECT ARE REQUIRED TO COMPLY
 WITH THE 2017 FBC ACCESSIBILITY CODE UNLESS SHOWN TO BE
 A DISPROPORTIONATE COST. FBC ACCESSIBILITY 603 & 604
  
 4) THE PERMIT APPLICATION INDICATES THAT $4,700,000.00
 DOLLARS OF WORK IS TO BE ACCOMPLISHED UNDER THIS
 PERMIT. PLEASE PROVIDE A LETTER EITHER FROM THE
 CONTRACTOR OR DESIGNER OF RECORD ON THEIR LETTERHEAD
 WHERE UP TO 20 % OF THE CONTRACT VALUE IS GOING TO BE
 SPENT IN ACCESSIBLE UPGRADES TO THE PROJECT. IF ALL
 EXISTING CONDITIONS ARE COMPLETED (COMPLIED) BEFORE
 DISPROPORTIONATION COST IS MET A LETTER IS NOT
 REQUIRED. SHOW COMPLIANCE WITH THE:
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 5) DOOR 103 ON SHEET A1.1 IS SHOWN SWINGING INWARD
 AGAINST THE DIRECTION OF EGRESS TRAVEL FROM THE
 BUILDING. FBC 1010.1.2.1
  
 6) UNDER CODE INFORMATION ON SHEET A01 THE PROJECT
 OCCUPANT LOAD IS SPECIFIED AS 48 PERSONS. THE
 CALCULATED OCCUPANT LOAD IS SPECIFIED AS 628 PERSONS ON
 SHEET A1.1. PLEASE CORRECT. FBC 107.2.1 & FBC
 1004.1.1.1
  
 7) SHEET A4.2 HAS AN EXTERIOR STAIR DETAIL #13 AND A
 STAIR SECTION #14. SUBMIT COMPLETE STRUCTURAL DETAILS
 FOR THESE STAIRS. FBC 107.2.1
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-05-14 Cont ID  
Sent By jpearson Date 2020-05-14 Time 16:24 Rev Time 0.00
Received By jpearson Date 2020-05-14 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-29 Cont ID  
Sent By jpearson Date 2020-04-29 Time 17:56 Rev Time 0.00
Received By jpearson Date 2020-04-29 Time 14:10 Sent To  
Notes
2020-04-29 17:50:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-05-13 Cont ID  
Sent By pleduc Date 2020-05-13 Time   Rev Time 0.00
Received By pleduc Date 2020-05-13 Time 14:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-04-29 Cont ID  
Sent By pleduc Date 2020-04-29 Time   Rev Time 0.00
Received By pleduc Date 2020-04-28 Time 12:09 Sent To  
Notes
2020-04-29 09:15:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.1 & A 4.1 - THERE IS AN INDICATION THAT
 DOOR 103 IS AN EXIT DOOR; HOWEVER, IT SWINGS AGAINST
 EGRESS.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE
 OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING
 IN THE
 DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS
 THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS
 DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT OR REMOVE THE EXIT SIGN ABOVE
 IT AS IT DOES NOT APPEAR TO BE A REQUIRED EXIT.
  
  
 2) SHEET A 4.1 - THE DOOR SCHEDULE INDICATES THAT DOORS
 101 THROUGH104 DO NOT HAVE PANIC HARDWARE.
  
 PER NFPA 101, CH 13, EXISTING ASSEMBLY OCCUPANCIES & CH
 7, MEANS OF EGRESS
  
 13.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR
 LOCK IS PANIC HARDWARE OR FIRE EXIT HARDWARE COMPLYING
 WITH
 7.2.1.7, UNLESS OTHERWISE PERMITTED BY ONE OF THE
 FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 13.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS
 DOORS AS PERMITTED IN 13.2.2.2.6.
  
  
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED WITH
 PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET
 ALL OF THE
 FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING
 PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF
 OF THE
 WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED
 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND
 LATCHES.
  
 PLEASE REVIEW AND CORRECT
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-05-15 Cont ID  
Sent By thunt Date 2020-05-15 Time 07:26 Rev Time 0.00
Received By rmcdouga Date 2020-05-14 Time 13:51 Sent To  
Notes
2020-05-15 07:27:27APPROVED BY TIM HUNT,

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-05-05 Cont ID  
Sent By rmcdouga Date 2020-05-05 Time 07:35 Rev Time 0.00
Received By rmcdouga Date 2020-05-05 Time 07:35 Sent To  
Notes
2020-05-05 07:36:50GAS 1ST REVIEW**DENIED**20040725
  
  
 1) THE BTU?S DON?T ADD UP WHEN COMPARING THE GAS
 ISOMETRIC AND FIXTURE SCHEDULE ON SHT. P2.3. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3
  
  
 TIM HUNT
  
 CITY OF WEST PALM BEACH
  
 (CAP GOVERNMENT)
  
 PLUMBING INSPECTOR
  
 PLUMBING PLAN EXAMINER [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-21 Cont ID  
Sent By pvalenti Date 2020-05-21 Time 08:21 Rev Time 0.00
Received By pvalenti Date 2020-05-20 Time 14:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-15 Cont ID  
Sent By rmcdouga Date 2020-05-15 Time 11:50 Rev Time 0.00
Received By rmcdouga Date 2020-05-11 Time 07:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-05 Cont ID  
Sent By rmcdouga Date 2020-05-05 Time 07:40 Rev Time 0.00
Received By rmcdouga Date 2020-04-24 Time 13:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-05-04 Cont ID  
Sent By rmcdouga Date 2020-05-04 Time 13:09 Rev Time 0.00
Received By rmcdouga Date 2020-05-04 Time 13:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-05-13 Cont ID  
Sent By medwards Date 2020-05-13 Time 11:16 Rev Time 0.00
Received By medwards Date 2020-05-13 Time 10:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-29 Cont ID  
Sent By medwards Date 2020-04-29 Time 13:30 Rev Time 0.00
Received By medwards Date 2020-04-28 Time 15:44 Sent To  
Notes
2020-04-29 13:31:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20040725
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.2- IN THE KITCHEN HOOD MAKE-UP AIR UNIT
 SCHEDULE REMARKS, BOTH KSF-1 AND KSF-3 CALL FOR A NOTE
 12. THERE IS NO NOTE 12 IN THE REMARKS. PLEASE SHOW
 NOTE 12 IN THE REMARKS SECTION. FBC FS 107.2.1
  
 2) SHEET M1.2- VENTILATION NOTE; VENTILATION SHOULD BE
 BASED ON ASHRAE 62.1 ? 2013, NOT 2010 VERSION. FBC M
 403.3.1.1.2.3.2
  
 3) SHEET M1.2- PLEASE SHOW AN AIR BALANCE REPORT FOR
 THIS FACILITY. I DO NOT SEE THE HOOD EXHAUST RATES IN
 YOUR CHARTS. FBC M 508.1.2
  
 4) SHEET M1.2- TG-1 IN THE BATHROOM AREA IS USING THE
 RETURN SYMBOL, PLEASE CORRECT THIS AS YOU CANNOT USE
 THE BATHROOMS AS RETURN AIR. FBC M TABLE 403.3.1.1
 (NOTE G)
  
 5) SHEET M3.2- PLEASE SHOW A DETAIL DRAWING OF HOW
 KSF-2 IS COMPLYING WITH THE MAKEUP AIR TEMPERATURE
 REQUIREMENT. FBC M 508.1.1
  
 6) CAPTIVE AIRE HOODS SHEETS ARE NOT INCLUDED IN THIS
 PROJECT PACKAGE. SEPARATE PLAN REVIEWS AND PERMITS WILL
 BE REQUIRED FOR THE HOOD SYSTEMS ON THIS PROJECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-05-21 Cont ID  
Sent By shill Date 2020-05-21 Time 08:03 Rev Time 0.00
Received By shill Date 2020-05-21 Time 08:03 Sent To  
Notes
2020-05-21 08:03:59REVIEWED REMOTELY BY TIM HUNT
 SHT P3.1 PLUMBING ISOMETRIC NEW DRY VENTS ADDED MUST BE
 WASHED AT THE BASE OF EACH STACK. A VENT MUST BE ADDED
 BETWEEN THE LAST 2 FIXTURES AS REDLINED ON THE PLAN.

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-05-14 Cont ID  
Sent By thunt Date 2020-05-14 Time 16:45 Rev Time 0.00
Received By shill Date 2020-05-14 Time 13:51 Sent To  
Notes
2020-05-14 16:46:09PLUMBING 1ST REVIEW DENIED**20040725
  
 1) SHT. P0.1 NOTE # 13 CALLS OUT ALL HOT WATER PIPING
 TO HAVE 1? WALL INSULATION. WHILE THIS IS CORRECT BUT
 ONLY UP TO 1 ?" PIPING. BEING YOUR PLAN SHOW SOME 1 ?"
 HOT WATER PIPE THAT WILL REQUIRED 1.5? THICK INSULATION
 THE NOTE COULD BE MISS LEADING. PLEASE CORRECT SHOW
 TABLE FBC-ENERGY C 403.2.10.
  
 2) PROVIDE SIZING AND HOW THIS GREASE TRAP IS SIZED FOR
 THE CURRENT KITCHEN USE. PLEASE PROVIDE HOW YOU SIZED
 BASE ON PDI G101 OR 64E-6
  
 3) PLEASE SHOWING TEMPERING ASSE1070 COMPLAINT. FBC-PLB
 607.1.2
  
 4) SHT P3.1 WATER ISOMETRIC IS MISSING THE REQUIRED
 SHUT OFF VALVES ON ALL DOWN FEED LINES. FBC-PLB 606.1
  
 5) THE SANITARY ISOMETRIC NEW FIXTURE ADDED DO NOT
 APPEAR TO BE PROPERLY VENTED. PLEASE CLARIFY WHICH
 VENTING METHOD IS YOUR DESIGN BASE ON FROM FBC-PLB
 CHAPTER 9. FBC 107.2.1
  
 TIM HUNT
  
 CITY OF WEST PALM BEACH
  
 (CAP GOVERNMENT)
  
 PLUMBING INSPECTOR
  
 PLUMBING PLAN EXAMINER [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-05-05 Cont ID  
Sent By thunt Date 2020-05-05 Time 07:40 Rev Time 0.00
Received By rmcdouga Date 2020-05-04 Time 14:04 Sent To  
Notes
2020-05-05 07:40:16GAS 1ST REVIEW**DENIED**20040725
  
  
 1) THE BTU?S DON?T ADD UP WHEN COMPARING THE GAS
 ISOMETRIC AND FIXTURE SCHEDULE ON SHT. P2.3. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3
  
  
 TIM HUNT
  
 CITY OF WEST PALM BEACH
  
 (CAP GOVERNMENT)
  
 PLUMBING INSPECTOR
  
 PLUMBING PLAN EXAMINER [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2020-05-20 Cont ID  
Sent By shill Date 2020-05-20 Time 11:04 Rev Time 0.00
Received By shill Date 2020-05-20 Time 11:04 Sent To  
Notes
2020-05-20 11:05:11OK PER REG
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-05-21 Cont ID  
Sent By pvalenti Date 2020-05-21 Time 08:20 Rev Time 0.00
Received By pvalenti Date 2020-05-21 Time 08:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-05-15 Cont ID  
Sent By pvalenti Date 2020-05-15 Time 09:06 Rev Time 0.00
Received By pvalenti Date 2020-05-15 Time 08:19 Sent To  
Notes
2020-05-14 16:08:28ELECTRICAL SHEETS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-03 Cont ID  
Sent By shill Date 2020-05-03 Time 09:53 Rev Time 0.00
Received By shill Date 2020-05-03 Time 09:53 Sent To  
Notes
2020-04-29 15:23:11ELECTRICAL SHEETS OK.