Plan Review Details - Permit 20040596
Plan Review Stops For Permit 20040596
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-05-01 Cont ID  
Sent By dbattles Date 2020-05-01 Time 11:55 Rev Time 0.00
Received By rmcphers Date 2020-05-01 Time 10:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-05-05 Cont ID  
Sent By jleahy Date 2020-05-05 Time 14:39 Rev Time 0.00
Received By jleahy Date 2020-05-05 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-04-21 Cont ID  
Sent By pleduc Date 2020-04-21 Time   Rev Time 0.00
Received By pleduc Date 2020-04-21 Time 14:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-04 Cont ID  
Sent By tklarge Date 2020-06-04 Time 08:00 Rev Time 0.00
Received By tklarge Date 2020-05-20 Time 14:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-11 Cont ID  
Sent By lmarchan Date 2020-05-11 Time 13:18 Rev Time 0.00
Received By lmarchan Date 2020-04-16 Time 14:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-06-03 Cont ID  
Sent By hmoser Date 2020-06-03 Time 11:44 Rev Time 0.00
Received By hmoser Date 2020-06-03 Time 09:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-22 Cont ID  
Sent By ccole Date 2020-04-22 Time 16:29 Rev Time 0.00
Received By ccole Date 2020-04-22 Time 12:35 Sent To  
Notes
2020-04-22 16:30:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20040596
 4/22/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.1 NOTES 7 A. & B: THE PLANS SHOW FLEX DUCTS
 BUT THE SPECIFICATIONS FOR THE DUCTS WAS REMOVED FROM
 THE REVISED PLAN SHEET- SECTION 107.2.1 WPB.
  
 2) M2.1 NOTE #5: SHOW THE REQUIRED FIRE/SMOKE DAMPER AT
 THE PENETRATION OF THE O/A DUCT AT THE SHAFT- SECTION
 607.5.5 FBC M. CORRECT THE NOTE INDICATING O/A FOR
 RESTROOM EXHAUST- SECTION 107.2.1 WPB.
  
 3) M2.1: PROVIDE O/A TO THE HP-2 SYSTEM SUPPLYING
 OFFICES 734, 735, 736- SECTION 403.3 FBC M.
  
 4) M2.2 NOTE #4: SHOW THE REQUIRED FIRE/SMOKE DAMPER AT
 THE PENETRATION OF THE RESTROOM EXHAUST DUCT AT THE
 SHAFT- SECTION 607.5.5 FBC M.
  
 5) M2.2: PROVIDE A THERMOSTAT FOR THE NEW AHU-1 SYSTEM
 IN THE IT 715 ROOM- SECTION C403.2.4.1 FBC EC.
  
 6) M2.2: SHOW THE LOCATION OF THE CHASE FOR THE NEW
 REFRIGERANT LINES- SECTION 107.2.1 PROVIDE A NOTE TO
 INDICATE THE NEW SYSTEM AND REFRIGERANT LINES WILL
 INSTALLED PER MANUFACTURER'S SPECIFICATIONS- SECTION
 304.1 FBC M.
  
 7) M7.1: SHOW THE LOCATION OF THE NEW AC CONDENSER-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-06-04 Cont ID  
Sent By tklarge Date 2020-06-04 Time 07:54 Rev Time 0.00
Received By tklarge Date 2020-06-04 Time 07:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-05-11 Cont ID  
Sent By tklarge Date 2020-05-11 Time 12:25 Rev Time 0.00
Received By tklarge Date 2020-05-11 Time 10:05 Sent To  
Notes
2020-05-11 12:25:171) SHT. A3.2 - DETAIL D6 - SHOW THE HEIGHT OF THE SINK
 CABINET. MAXIMUM HEIGHT IS 34 INCHES ABOVE THE FINISH
 FLOOR TO THE HIGHER OF THE RIM OR COUNTER SURFACE.
 FBC-ACCESS. SEC.606.3.
 2) SHT. A1.1 - ADA MOUNTING HEIGHT DETAILS - GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE,
 TO TO THE CENTERLINE AS SHOWN. FBC-ACCESS. SEC. 609.4.
 3) THE TOILET PAPER DISPENSER IS SHOWN AS 17-19 INCHES
 ABOVE THE FINISH FLOOR. THE OUTLET OF THE DISPENSER
 SHALL BE LOCATED 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISHED FLOOR.FBC-ACCESS. SEC.604.7
 4) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9
 INCHES TO THE CENTERLINE FROM THE FRONT OF THE BOWL.
 FBC-ACCESS. SEC. 604.7.
 5) THE WATER CLOSET IS SHOWN AS 18 INCHES MINIMUM FROM
 THE WALL. THE WATER CLOSET SHALL BE LOCATED 16-18
 INCHES FROM A SIDE WALL OR PARTITION. FBC-ACCESS.
 SEC.604.2.
 6) THE DETAILS SHOW VERTICAL GRAB BARS. THE GRAB BARS
 SHALL BE INSTALLED IN THE HORIZONTAL POSITION PER
 FBC-ACCESS. SEC. 609.4. THERE IS NO EXCEPTION IN THE
 COULD FOR GRAB BARS INSTALLED IN THE VERTICAL POSITION.
 7) SHT. A1.1 - SHOW THE DISTANCE UNDER THE LAVATORIES
 ON DETAIL E13. COMPLY WITH FBC-ACCESS. SEC. 306.
 8) SHOW THE LOCATION OF THE MOP SINK ON THE PLANS.
 TABLE 403.1.
 9) THE CONNECTION OF THE SUMP DRAIN TO THE BUILDING
 DRAIN SHALL BE LOCATED A MINIMUM OF 10 PIPE DIAMETERS
 AWAY FROM THE BASE OF THE STACK FOR SK-1 PER
 FBC-PLUMBING SEC. 712.3.5.
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SUMP
 FOR THE SINK AND FOR THE CONDENSATE PUMP. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-04 Cont ID  
Sent By tklarge Date 2020-06-04 Time 07:59 Rev Time 0.00
Received By tklarge Date 2020-06-04 Time 07:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-01 Cont ID  
Sent By rmcphers Date 2020-05-01 Time 11:55 Rev Time 0.00
Received By rmcphers Date 2020-05-01 Time 11:55 Sent To  
Notes
***NONE***