Plan Review Details - Permit 20040366
Plan Review Stops For Permit 20040366
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2020-05-15 Cont ID  
Sent By rmcphers Date 2020-05-15 Time 08:46 Rev Time 0.00
Received By rmcphers Date 2020-05-15 Time 08:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-15 Cont ID  
Sent By rmcphers Date 2020-04-15 Time 16:25 Rev Time 0.00
Received By rmcphers Date 2020-04-15 Time 15:21 Sent To  
Notes
2020-04-15 16:24:47REPLACING AND ADDING BOILERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) PLEASE SHOW THE EXISTING HOURLY FIRE RATING FOR THE
 WALLS.
 2) PLEASE SHOW IF THE BUILDING HAS EXISTING FIRE
 SPRINKLERS.
 3) PLEASE SHOW PENETRATIONS THRU FIRE RATED WALLS TO
 COMPLY WITH FBC 714
 FBC EXISTING BUILDING 703.1GENERAL.
 ALTERATIONS SHALL BE DONE IN A MANNER THAT MAINTAINS
 THE LEVEL OF FIRE PROTECTION PROVIDED.
 PLANS DO NOT SHOW ANY NEW WALLS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-06-15 Cont ID  
Sent By jleahy Date 2020-06-15 Time 11:07 Rev Time 0.00
Received By jleahy Date 2020-06-15 Time 11:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-14 Cont ID  
Sent By jleahy Date 2020-05-14 Time 08:46 Rev Time 0.00
Received By jleahy Date 2020-05-14 Time 08:46 Sent To  
Notes
2020-05-14 08:47:33VALUE FOR THE WORK IS STILL SHOWN AS $400,000
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-20 Cont ID  
Sent By jleahy Date 2020-04-20 Time 13:55 Rev Time 0.00
Received By jleahy Date 2020-04-20 Time 13:55 Sent To  
Notes
2020-04-20 13:59:34FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR THE AMOUNT OF WORK SHOWN SEEMS LOW, PLEASE
 SUBMIT A SIGNED CONTRACT WITH THE OWNERS SIGNATURE.
 (400,000)
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) AIC RATING FOR DOWN STREAM FROM TRANSFORMER REQUIRED
 AND LABELING.
  
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-05-06 Cont ID  
Sent By pleduc Date 2020-05-06 Time   Rev Time 0.00
Received By pleduc Date 2020-05-06 Time 16:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-04-10 Cont ID  
Sent By pleduc Date 2020-04-10 Time   Rev Time 0.00
Received By pleduc Date 2020-04-10 Time 14:23 Sent To  
Notes
2020-04-10 14:34:47THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS NO CLEAR SCOPE OF WORK. THE COVER PAGE
 INDICATES BOILER UPGRADE.
  
 WITH MULTIPLE DEMO PLAN SHEETS, PLEASE PROVIDE A SCOPE
 OF WORK FOR CLRIFICATION PURPOSES.
  
 PLEASE INCLUDE WHAT IS/WILL BE EXISTING AND WHAT
 IS/WILL BE NEW.
  
  
  
 2) THERE IS NO INDICATIONS OF COMPLIANCE WITH ANY LIFE
 SAFETY CODE.
  
 THE PROPOSED SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 6TH ED AND ALL APPLICABLE, INCLUDING,
 BUT NOT LIMITED TO, NFPA 85
 BOILER AND COMBUSTION SYSTEMS HAZARDS CODE, 2015
 EDITION.
  
 WITH NOT FULLY KNOWING THE SCOPE AND PER # 1 ABOVE, IT
 IS UNCLEAR IF THERE IS COMPLIANCE WITH NFPA.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 3) THERE ARE NO SPEC/EQUIPMENT SHEETS PROVIDED.
  
 PLEASE REVIEW AND PROVIDE AS APPLICABLE FOR REVIEW AND
 CONFIRMATION WITH # 1 & 2 ABOVE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
 CHAPTER 1 ADMINISTRATION
 1.1* SCOPE. THIS CODE APPLIES TO THE FOLLOWING:
 (1) SINGLE BURNER BOILERS, MULTIPLE BURNER BOILERS,
 STOKERS,
 AND ATMOSPHERIC FLUIDIZED BED BOILERS WITH A FUEL INPUT
 RATING OF 3.7 MWT (12.5 MILLION BTU/HR) OR GREATER
 (2) PULVERIZED FUEL SYSTEMS AT ANY HEAT INPUT RATE
 (3) FIRED OR UNFIRED STEAM GENERATORS USED TO RECOVER
 HEAT
 FROM COMBUSTION TURBINES [HEAT RECOVERY STEAM
 GENERATORS
 (HRSGS)] AND OTHER COMBUSTION TURBINE EXHAUST SYSTEMS
 AT ANY HEAT INPUT RATE
 1.1.1 THIS CODE COVERS DESIGN, INSTALLATION, OPERATION,
 MAINTENANCE,
 AND TRAINING.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-06-11 Cont ID  
Sent By ccole Date 2020-06-11 Time 10:56 Rev Time 0.00
Received By ccole Date 2020-06-11 Time 07:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-05-14 Cont ID  
Sent By ccole Date 2020-05-14 Time 16:34 Rev Time 0.00
Received By ccole Date 2020-05-14 Time 16:34 Sent To  
Notes
2020-05-14 16:36:422ND REVIEW FBC-2017 FUEL GAS
 PERMIT #20040366
 5/14/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
 BASED ON THE RESUMBITTED PLANS AND THE NARRATIVE
 RESPONSES BY THE ENGINEER OF RECORD, THE 1ST REVIEW
 COMMENTS LISTED BELOW WILL BE MARKED AS PASSED OR
 FAILED.
  
 1) FAILED. GAS DRAWING DOES NOT SHOW TOTAL DEVELOPED
 LENGTH OF THE SYSTEM, TYPE OF PIPINGS, TOTAL BTUH GAS
 LOAD OF THE SYSTEM, CUT LENGTHS OF PIPINGS, DELIVERY
 PRESSURES AT THE METER AND AT REGULATORS, GAS PIPE
 SIZING TABLES, LOCATIONS OF DRIP LEGS, UNIONS. PROVIDE
 A GAS ISOMETRIC DRAWING THAT SHOWS THE TYPE AND
 DIAMETERS OF PIPING, THE MEASUREMENTS OF EACH CUT
 LENGTH OF PIPE, THE TOTAL DEVELOPED LENGTH OF THE
 PIPING RUN FROM THE POINT OF DELIVERY AT THE METER TO
 THE MOST REMOTE OUTLET IN THE BUILDING AND TO THE
 BOILERS; GAS DELIVERY PRESSURE OF THE SYSTEM AT THE
 METER AND AT EACH STEPDOWN REGULATOR; LOCATIONS OF
 REQUIRED SHUTOFF VALVES, AND THE BTUH LOADS OF THE NEW
 BOILERS, AND ALL OTHER GAS-FIRED APPLIANCES AND
 EQUIPMENT BEING SERVED BY THE SYSTEM- SECTIONS 402.2
 AND 402.3 FBC FG. PLEASE INDICATE WHICH PIPE SIZING
 TABLES WERE USED IN THE DESIGN- SECTION 402.3.
 A) FAILED. CONCERNING THE REGULATORS PLEASE REFER TO
 SECTIONS 410.1, 410.2, & 410.3 FBC FG FOR LINE AND MP
 REGULATOR INSTALLATION AND VENTING REQUIREMENTS. PLEASE
 VERIFY SUBMITTALS ARE COMPLIANT AND SHOW ALL REGULATOR
 AND SHUTOFF VALVES IN THE ISOMETRIC DRAWING, AND
 REGULATOR VENT RUNS AND TERMINATION LOCATIONS WHERE
 REQUIRED.
  
 2) PASSED-DEFERRED SUBMITTALS. PROVIDE A SUBMITTAL
 PACKAGE THAT INCLUDES MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION GUIDELINES FOR THE BOILERS, PUMPS,
 EXPANSION TANK, CONTROL VALVES, RELIEF VALVES, CHEMICAL
 FEEDER, CHEMICAL NEUTRALIZERS, VENT FLUE AND VENT CAP,
 COMBUSTION AIR DUCTS, GAS AND HYDRONIC PIPING, AND THE
 GAS REGULATORS AND SHUT OFF VALVES- SECTION 107.2.1
 WPB. REVIEW ALL REQUIRED COMPLIANCES AND UL LISTINGS
 FOR THE PRODUCTS AS NOTED ON THE SPECIFICATIONS SHEETS
 M101, 102, & 103 AS THEY WILL BE CROSS CHECKED IN THE
 2ND REVIEW. THE DESIGN PROFESSIONAL OF RECORD SHALL
 PROVIDE APPROVAL STAMPS ON EACH SUBMITTAL DOC, OR
 PROVIDE A STAMPED COVER PAGE WITH AN INDEX LISTING ALL
 PRODUCT SUBMITTALS.
  
 A) PASSED-DEFERRED SUBMITTALS. PLEASE NOTE THE GAS
 BOILER SPECIFICATIONS SHALL INDICATE THAT THE UNITS ARE
 LISTED IN ACCORDANCE WITH THE REQUIREMENTS OF ANSI
 Z21.13 OR UL 795, AND DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH THE REQUIREMENTS OF ASME CSD-1 AND AS
 APPLICABLE, THE ASME BOILER AND PRESSURE VESSEL CODE,
 SECTIONS I, II, IV, V AND IX AND NFPA 85- SECTION 631.1
 FBC FG AND SECTION 1004.1 FBC M
  
 3) FAILED. REFER TO SECTIONS 406.4, THROUGH 406.6 FBC
 FG AND PROVIDE A GAS PIPING TESTING PROCEDURE ON THE
 PLAN.
  
 4) MECH COMMENT #9) FAILED. A) THE VENT SIZING
 CALCULATIONS WERE NOT PROVIDED- SECTION 501.14 FBC FG.
 B) SHEETS M-301 & M-903 SHOW THE VENT FLUE FREESTANDING
 ABOVE THE ROOF. SHEET M-501 INDICATES THE VENT TO BE IN
 A CHIMNEY ENCLOSURE- WHICH IS IT? , IF THE VENT IS
 FREESTANDING, SHOW THE ACTUAL HEIGHT OF THE VENT FLUE
 ABOVE THE ROOF AND PROVIDE ENGINEERING FOR ANCHORING
 THE FLUE TO THE ROOF STRUCTURE TO RESIST WIND
 PRESSURES- SECTION 301.15- FBC M. C) INDICATE THE
 REQUIRED CLEARANCE FROM THE VENT PENETRATION TO THE
 COMBUSTIBLE ROOFING MATERIAL. D) PROVIDE A SUBMITTAL
 FOR THE VENT FLUES AND COMBUSTION AIR DUCTS OR REQUEST
 DEFERRED. PROVIDE A VENT FLUE DIAGRAM THAT SHOWS THE
 LENGTHS OF THE CONNECTORS, HORIZONTAL AND VERTICAL RUN
 LENGTHS, TOTAL RUN LENGTH OF THE SYSTEM, AND LOCATIONS
 OF OFFSETS, FITTINGS ETC. PER THE NOTES ON SHEET M102
 THE PROPOSED SYSTEM REQUIRES ENGINEERED SIZING
 CALCULATIONS WHICH SHALL ACCOMPANY THE VENTING DIAGRAM-
 SEE SECTION 506.6.9.3 FBC FG. PLEASE INDICATE THE
 "VENTING APPLIANCE CATEGORY" - I, II, III, OR IV THAT
 THE SYSTEM IS BEING DESIGNED FOR, AND IF THE SYSTEM IS
 POSITIVE OR NEGATIVE AND PRODUCES CONDENSATION- SEE
 SECTION 202 FBC FG. CURRENTLY, A THOROUGH REVIEW OF THE
 SYSTEM CANNOT BE ACCOMPLISHED WITHOUT THE DIAGRAM, AND
 ADDITIONAL SPECIFICATIONS AND INFORMATION- SECTION
 107.2.1 WPB. PLEASE REFER BACK TO COMMENT #1 FOR
 SUBMITTAL REQUIREMENTS AND REQUIRED UL LISTING AND
 LABELING. A) M502: REFER TO SECTION 503.8 FBC FG AND
 SHOW THE REQUIRED CLEARANCES FROM THE VENT FLUE
 TERMINATION TO MECHANICAL AND GRAVITY AIR INTAKES OR
 ANY OPERABLE OPENINGS INTO THE BUILDING.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-04-14 Cont ID  
Sent By ccole Date 2020-04-14 Time 13:17 Rev Time 0.00
Received By ccole Date 2020-04-14 Time 12:56 Sent To  
Notes
2020-04-14 13:21:131ST REVIEW FBC-2017 FUEL GAS
 PERMIT #20040366
 4/142020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS #1 & 2 LISTED BELOW ARE ALSO IN THE MECHANICAL
 REVIEW. PLEASE REFER TO MECHANICAL REVIEW COMMENTS FOR
 ADDITIONAL PLAN CORRECTIONS.
  
 1) PROVIDE A GAS ISOMETRIC DRAWING THAT SHOWS THE TYPE
 AND DIAMETERS OF PIPING, THE MEASUREMENTS OF EACH CUT
 LENGTH OF PIPE, THE TOTAL DEVELOPED LENGTH OF THE
 PIPING RUN FROM THE POINT OF DELIVERY AT THE METER TO
 THE MOST REMOTE OUTLET IN THE BUILDING AND TO THE
 BOILERS; GAS DELIVERY PRESSURE OF THE SYSTEM AT THE
 METER AND AT EACH STEPDOWN REGULATOR; LOCATIONS OF
 REQUIRED SHUTOFF VALVES, AND THE BTUH LOADS OF THE NEW
 BOILERS, AND ALL OTHER GAS-FIRED APPLIANCES AND
 EQUIPMENT BEING SERVED BY THE SYSTEM- SECTIONS 402.2
 AND 402.3 FBC FG. PLEASE INDICATE WHICH PIPE SIZING
 TABLES WERE USED IN THE DESIGN- SECTION 402.3.
 A) CONCERNING THE REGULATORS PLEASE REFER TO SECTIONS
 410.1, 410.2, & 410.3 FBC FG FOR LINE AND MP REGULATOR
 INSTALLATION AND VENTING REQUIREMENTS. PLEASE VERIFY
 SUBMITTALS ARE COMPLIANT AND SHOW ALL REGULATOR AND
 SHUTOFF VALVES IN THE ISOMETRIC DRAWING, AND REGULATOR
 VENT RUNS AND TERMINATION LOCATIONS WHERE REQUIRED.
  
 2) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES FOR THE BOILERS, PUMPS, EXPANSION TANK,
 CONTROL VALVES, RELIEF VALVES, CHEMICAL FEEDER,
 CHEMICAL NEUTRALIZERS, VENT FLUE AND VENT CAP,
 COMBUSTION AIR DUCTS, GAS AND HYDRONIC PIPING, AND THE
 GAS REGULATORS AND SHUT OFF VALVES- SECTION 107.2.1
 WPB. REVIEW ALL REQUIRED COMPLIANCES AND UL LISTINGS
 FOR THE PRODUCTS AS NOTED ON THE SPECIFICATIONS SHEETS
 M101, 102, & 103 AS THEY WILL BE CROSS CHECKED IN THE
 2ND REVIEW. THE DESIGN PROFESSIONAL OF RECORD SHALL
 PROVIDE APPROVAL STAMPS ON EACH SUBMITTAL DOC, OR
 PROVIDE A STAMPED COVER PAGE WITH AN INDEX LISTING ALL
 PRODUCT SUBMITTALS.
  
 A) PLEASE NOTE THE GAS BOILER SPECIFICATIONS SHALL
 INDICATE THAT THE UNITS ARE LISTED IN ACCORDANCE WITH
 THE REQUIREMENTS OF ANSI Z21.13 OR UL 795, AND DESIGNED
 AND CONSTRUCTED IN ACCORDANCE WITH THE REQUIREMENTS OF
 ASME CSD-1 AND AS APPLICABLE, THE ASME BOILER AND
 PRESSURE VESSEL CODE, SECTIONS I, II, IV, V AND IX AND
 NFPA 85- SECTION 631.1 FBC FG AND SECTION 1004.1 FBC M
  
 3) REFER TO SECTIONS 406.4, THROUGH 406.6 FBC FG AND
 PROVIDE A GAS PIPING TESTING PROCEDURE ON THE PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-15 Cont ID  
Sent By jleahy Date 2020-06-15 Time 11:08 Rev Time 0.00
Received By jleahy Date 2020-06-08 Time 13:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-15 Cont ID  
Sent By rmcphers Date 2020-05-15 Time 08:57 Rev Time 0.00
Received By rmcphers Date 2020-05-05 Time 11:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-20 Cont ID  
Sent By jleahy Date 2020-04-20 Time 14:15 Rev Time 0.00
Received By jleahy Date 2020-04-09 Time 13:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-06-11 Cont ID  
Sent By ccole Date 2020-06-11 Time 10:55 Rev Time 0.00
Received By ccole Date 2020-06-11 Time 06:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-05-14 Cont ID  
Sent By ccole Date 2020-05-14 Time 16:21 Rev Time 0.00
Received By ccole Date 2020-05-14 Time 13:38 Sent To  
Notes
2020-05-14 16:23:272ND REVIEW FBC-2017 MECHANICAL
 PERMIT #20040366
 5/14/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
 BASED ON THE RESUMBITTED PLANS AND THE NARRATIVE
 RESPONSES BY THE ENGINEER OF RECORD, THE 1ST REVIEW
 COMMENTS LISTED BELOW WILL BE MARKED AS PASSED OR
 FAILED.
  
 1) PASSED- DEFERRED SUBMITTAL ACCEPTED. PROVIDE A
 SUBMITTAL PACKAGE THAT INCLUDES MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION GUIDELINES FOR THE
 BOILERS, PUMPS, EXPANSION TANK, CONTROL VALVES, RELIEF
 VALVES, CHEMICAL FEEDER, CHEMICAL NEUTRALIZERS, VENT
 FLUE AND VENT CAP, COMBUSTION AIR DUCTS, GAS AND
 HYDRONIC PIPING, AND THE GAS REGULATORS AND SHUT OFF
 VALVES- SECTION 107.2.1 WPB. REVIEW ALL REQUIRED
 COMPLIANCES AND UL LISTINGS FOR THE PRODUCTS AS NOTED
 ON THE SPECIFICATIONS SHEETS M101, 102, & 103 AS THEY
 WILL BE CROSS CHECKED IN THE 2ND REVIEW. THE DESIGN
 PROFESSIONAL OF RECORD SHALL PROVIDE APPROVAL STAMPS ON
 EACH SUBMITTAL DOC, OR PROVIDE A STAMPED COVER PAGE
 WITH AN INDEX LISTING ALL PRODUCT SUBMITTALS.
 A) PASSED- DEFERRED SUBMITTAL. PLEASE NOTE THE GAS
 BOILER SPECIFICATIONS SHALL INDICATE THAT THE UNITS ARE
 LISTED IN ACCORDANCE WITH THE REQUIREMENTS OF ANSI
 Z21.13 OR UL 795, AND DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH THE REQUIREMENTS OF ASME CSD-1 AND AS
 APPLICABLE, THE ASME BOILER AND PRESSURE VESSEL CODE,
 SECTIONS I, II, IV, V AND IX AND NFPA 85- SECTION 631.1
 FBC FG AND SECTION 1004.1 FBC M.
 B) PASSED- DEFERRED SUBMITTAL. COMMISSIONING OF THE
 BOILERS WILL REQUIRED AS NOTED UNDER ITEM 3.05 ON SHEET
 M103 WHICH LISTS THE AIR AND WATER TESTING AND
 BALANCING. COPIES OF THE TESTING REPORTS WILL BE
 REQUIRED FOR FINAL MECHANICAL APPROVAL- SECTION C408.2
 FBC EC.
 C) PASSED- DEFERRED SUBMITTAL. THE BOILER
 SPECIFICATIONS SHALL INDICATE THAT THE UNITS HAVE BEEN
 TESTED OR WILL BE TESTED TO A MAXIMUM LEVEL OF 50 PPM
 OF CARBON MONOXIDE PER OSHA GUIDELINES- SECTION
 1004.2.1 FBC M.
  
 2) FAILED. SHEET M401: PROVIDE THE EFFICIENCY RATINGS
 OF THE BOILERS IN THE EQUIPMENT SCHEDULES- SEE TABLE
 404,2 FBC EC.
  
 3) PASSED- DEFERRED SUBMITTAL. M401: VERIFY THE BOILER
 SERVICE WATER SYSTEM WILL BE CAPABLE OF AUTOMATIC
 TEMPERATURE RESET AND AUTOMATIC VARIABLE FLUID FLOW-
 SEE SECTION C403.4.2.2 FBC EC.
  
 4) PASSED- DEFERRED SUBMITTAL. M401: INDICATE THE
 BOILER TURNDOWN RATIO AS REQUIRED BY SECTION C403.4.2.5
 FBC EC.
  
 5) FAILED. WORKING CLEARANCES AT FRONTS, SIDES, REARS,
 AND IN BETWEEN THE BOILERS NOT PROVIDED. PLEASE PROVIDE
 FRONT AND TOP VIEW DRAWINGS OR DIAGRAMS OF THE BOILERS
 THAT SHOW A) REQUIRED WORKING CLEARANCES AS NOTED IN
 SECTIONS 1004.3 & 1004.3.1 FBC M. B) POTABLE WATER
 SUPPLY PIPING CONNECTION AND LOCATION OF BACKFLOW
 PREVENTERS AND SHUTOFF VALVES- SECTIONS 1005.1 &
 1005.2. C) WATER DISTRIBUTION PIPING AND CONNECTIONS
 AND VALVE LOCATIONS- 1005.2 D) LOCATIONS AND
 CONNECTIONS OF SAFETY RELIEF VALVES, PRESSURE RELIEF
 VALVES, DISCHARGE PIPING AND DISCHARGE LOCATIONS-
 SECTIONS 1006.2,1006.3, 1006.4, 1006.5, 1006.6, AND
 1006.7. E) LOCATION OF THE EXPANSION TANK- SECTION 1009
 FBC M. E) CONNECTION LOCATIONS OF THE GAS PIPING AND
 REGULATOR, COMBUSTION AIR DUCTS, AND VENT DUCT- SECTION
 107.2.1 WPB.
  
 6) PASSED. SHEET M501: SHOW THE LOCATION OF THE
 REQUIRED FLOOR DRAIN FOR THE BOILERS- SECTION 1004.6
 FBC M.
  
 7) PASSED. M501: SHOW THE GAS PIPING RUN INTO THE
 BOILER ROOM- SECTION 107.2.1 WPB.
  
 8) FAILED. GAS DRAWING DOES NOT SHOW TOTAL DEVELOPED
 LENGTH OF THE SYSTEM, TYPE OF PIPINGS, TOTAL BTUH GAS
 LOAD OF THE SYSTEM, CUT LENGTHS OF PIPINGS, DELIVERY
 PRESSURES AT THE METER AND AT REGULATORS, GAS PIPE
 SIZING TABLES, LOCATIONS OF DRIP LEGS, UNIONS. PROVIDE
 A GAS ISOMETRIC DRAWING THAT SHOWS THE TYPE AND
 DIAMETERS OF PIPING, THE MEASUREMENTS OF EACH CUT
 LENGTH OF PIPE, THE TOTAL DEVELOPED LENGTH OF THE
 PIPING RUN FROM THE POINT OF DELIVERY AT THE METER TO
 THE MOST REMOTE OUTLET IN THE BUILDING AND TO THE
 BOILERS; GAS DELIVERY PRESSURE OF THE SYSTEM AT THE
 METER AND AT EACH STEPDOWN REGULATOR; LOCATIONS OF
 REQUIRED SHUTOFF VALVES, AND THE BTUH LOADS OF THE NEW
 BOILERS, AND ALL OTHER GAS-FIRED APPLIANCES AND
 EQUIPMENT BEING SERVED BY THE SYSTEM- SECTIONS 402.2
 AND 402.3 FBC FG. PLEASE INDICATE WHICH PIPE SIZING
 TABLES WERE USED IN THE DESIGN- SECTION 402.3.
 A) FAILED. CONCERNING THE REGULATORS PLEASE REFER TO
 SECTIONS 410.1, 410.2, & 410.3 FBC FG FOR LINE AND MP
 REGULATOR INSTALLATION AND VENTING REQUIREMENTS. PLEASE
 VERIFY SUBMITTALS ARE COMPLIANT AND SHOW ALL REGULATOR
 AND SHUTOFF VALVES IN THE ISOMETRIC DRAWING, AND
 REGULATOR VENT RUNS AND TERMINATION LOCATIONS WHERE
 REQUIRED.
  
 9) FAILED. A) THE VENT SIZING CALCULATIONS WERE NOT
 PROVIDED- SECTION 501.14 FBC FG. B) SHEETS M-301 &
 M-903 SHOW THE VENT ROOF FREESTANDING ABOVE THE ROOF.
 SHEET M-501 INDICATES THE VENT TO BE IN A CHIMNEY
 ENCLOSURE- WHICH IS IT? , IF THE VENT IS FREESTANDING,
 SHOW THE ACTUAL HEIGHT OF THE VENT FLUE ABOVE THE ROOF
 AND PROVIDE ENGINEERING FOR ANCHORING THE FLUE TO THE
 ROOF STRUCTURE TO RESIST WIND PRESSURES- SECTION
 301.15- FBC M. C) INDICATE THE REQUIRED CLEARANCE FROM
 THE VENT PENETRATION TO THE COMBUSTIBLE ROOFING
 MATERIAL. D) PROVIDE A SUBMITTAL FOR THE VENT FLUES AND
 COMBUSTION AIR DUCTS OR REQUEST DEFERRED. PROVIDE A
 VENT FLUE DIAGRAM THAT SHOWS THE LENGTHS OF THE
 CONNECTORS, HORIZONTAL AND VERTICAL RUN LENGTHS, TOTAL
 RUN LENGTH OF THE SYSTEM, AND LOCATIONS OF OFFSETS,
 FITTINGS ETC. PER THE NOTES ON SHEET M102 THE PROPOSED
 SYSTEM REQUIRES ENGINEERED SIZING CALCULATIONS WHICH
 SHALL ACCOMPANY THE VENTING DIAGRAM- SEE SECTION
 506.6.9.3 FBC FG. PLEASE INDICATE THE "VENTING
 APPLIANCE CATEGORY" - I, II, III, OR IV THAT THE SYSTEM
 IS BEING DESIGNED FOR, AND IF THE SYSTEM IS POSITIVE OR
 NEGATIVE AND PRODUCES CONDENSATION- SEE SECTION 202 FBC
 FG. CURRENTLY, A THOROUGH REVIEW OF THE SYSTEM CANNOT
 BE ACCOMPLISHED WITHOUT THE DIAGRAM, AND ADDITIONAL
 SPECIFICATIONS AND INFORMATION- SECTION 107.2.1 WPB.
 PLEASE REFER BACK TO COMMENT #1 FOR SUBMITTAL
 REQUIREMENTS AND REQUIRED UL LISTING AND LABELING. A)
 M502: REFER TO SECTION 503.8 FBC FG AND SHOW THE
 REQUIRED CLEARANCES FROM THE VENT FLUE TERMINATION TO
 MECHANICAL AND GRAVITY AIR INTAKES OR ANY OPERABLE
 OPENINGS INTO THE BUILDING.
  
 10) PASSED. PROVIDE A COMBUSTION AIR DUCT DIAGRAM THAT
 SHOWS THE LENGTHS OF THE CONNECTORS, HORIZONTAL AND
 VERTICAL RUN LENGTHS, TOTAL RUN LENGTH OF THE SYSTEM,
 AND LOCATIONS OF OFFSETS, FITTINGS ETC.- SECTION 304.1
 AND 304.11 FBC FG. CURRENTLY, A THOROUGH REVIEW OF THE
 SYSTEM CANNOT BE ACCOMPLISHED WITHOUT THE DIAGRAM, AND
 ADDITIONAL SPECIFICATIONS AND INFORMATION- SECTION
 107.2.1 WPB. PLEASE REFER BACK TO COMMENT #1 FOR
 SUBMITTAL REQUIREMENTS AND REQUIRED UL LISTING AND
 LABELING.
  
 11) PASSED. M201: THE SCOPE OF WORK NOTES INDICATES
 DEMOLITION OF AIR CONDITIONING UNITS, DUCTS, TERMINAL
 BOXES ETC. HOWEVER THE DRAWINGS TO NOT SHOW ANY AC
 DEMOLITION OR REWORK. PLEASE PROVIDE THE DRAWINGS-
 SECTION 107.2.1 WPB.
  
 12) PASSED. M401: PLEASE PLACE A NOTE THAT THE WELDER'S
 CERTIFICATES AND WELDING PROCEDURES SHALL BE ONSITE AT
 TIME OF INSPECTION- SECTION 107.2.1 WPB.
  
 13) PASSED- SEE NOTE. PROVIDE UL LISTED FIRE STOPPING
 ASSEMBLIES FOR THE PENETRATIONS OF THE VENT FLUE, AND
 COMBUSTION AIR DUCTS THROUGH THE FIRE RATED WALLS AND
 FLOOR CEILING ASSEMBLIES- SECTION 714 FBC B. NOTE: THE
 PIPE PENETRATON FIRESTOPPING DETAIL ON M-903 DOES NOT
 INDICATE IT IS A UL LISTED AND LABELED ASSEMBLY.
  
 14) PASSED. INDICATE THE TYPE AND THICKNESSES OF THE
 BOILER SERVICE WATER PIPING INSULATIONS AND PROVIDE A
 PRODUCT SUBMITTAL- SEE TABLE C403.2.10 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-13 Cont ID  
Sent By ccole Date 2020-04-13 Time 13:43 Rev Time 0.00
Received By ccole Date 2020-04-13 Time 07:12 Sent To  
Notes
2020-04-13 13:47:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20040366
 4/142020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 1) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES FOR THE BOILERS, PUMPS, EXPANSION TANK,
 CONTROL VALVES, RELIEF VALVES, CHEMICAL FEEDER,
 CHEMICAL NEUTRALIZERS, VENT FLUE AND VENT CAP,
 COMBUSTION AIR DUCTS, GAS AND HYDRONIC PIPING, AND THE
 GAS REGULATORS AND SHUT OFF VALVES- SECTION 107.2.1
 WPB. REVIEW ALL REQUIRED COMPLIANCES AND UL LISTINGS
 FOR THE PRODUCTS AS NOTED ON THE SPECIFICATIONS SHEETS
 M101, 102, & 103 AS THEY WILL BE CROSS CHECKED IN THE
 2ND REVIEW. THE DESIGN PROFESSIONAL OF RECORD SHALL
 PROVIDE APPROVAL STAMPS ON EACH SUBMITTAL DOC, OR
 PROVIDE A STAMPED COVER PAGE WITH AN INDEX LISTING ALL
 PRODUCT SUBMITTALS.
  
 A) PLEASE NOTE THE GAS BOILER SPECIFICATIONS SHALL
 INDICATE THAT THE UNITS ARE LISTED IN ACCORDANCE WITH
 THE REQUIREMENTS OF ANSI Z21.13 OR UL 795, AND DESIGNED
 AND CONSTRUCTED IN ACCORDANCE WITH THE REQUIREMENTS OF
 ASME CSD-1 AND AS APPLICABLE, THE ASME BOILER AND
 PRESSURE VESSEL CODE, SECTIONS I, II, IV, V AND IX AND
 NFPA 85- SECTION 631.1 FBC FG AND SECTION 1004.1 FBC M.
  
 B) COMMISSIONING OF THE BOILERS WILL REQUIRED AS NOTED
 UNDER ITEM 3.05 ON SHEET M103 WHICH LISTS THE AIR AND
 WATER TESTING AND BALANCING. COPIES OF THE TESTING
 REPORTS WILL BE REQUIRED FOR FINAL MECHANICAL APPROVAL-
 SECTION C408.2 FBC EC.
  
 C) THE BOILER SPECIFICATIONS SHALL INDICATE THAT THE
 UNITS HAVE BEEN TESTED OR WILL BE TESTED TO A MAXIMUM
 LEVEL OF 50 PPM OF CARBON MONOXIDE PER OSHA GUIDELINES-
 SECTION 1004.2.1 FBC M.
  
 2) SHEET M401: PROVIDE THE EFFICIENCY RATINGS OF THE
 BOILERS IN THE EQUIPMENT SCHEDULES- SEE TABLE 404,2 FBC
 EC.
  
 3) M401: VERIFY THE BOILER SERVICE WATER SYSTEM WILL BE
 CAPABLE OF AUTOMATIC TEMPERATURE RESET AND AUTOMATIC
 VARAIBLE FLUID FLOW- SEE SECTION C403.4.2.2 FBC EC.
  
 4) M401: INDICATE THE BOILER TURNDOWN RATIO AS REQUIRED
 BYU SECTION C403.4.2.5 FBC EC.
  
 5) PLEASE PROVIDE FRONT AND TOP VIEW DRAWINGS OR
 DIAGRAMS OF THE BOILERS THAT SHOW A) REQUIRED WORKING
 CLEARANCES AS NOTED IN SECTIONS 1004.3 & 1004.3.1 FBC
 M. B) POTABLE WATER SUPPLY PIPING CONNECTION AND
 LOCATION OF BACKFLOW PREVENTERS AND SHUTOFF VALVES-
 SECTIONS 1005.1 & 1005.2. C) WATER DISTRIBUTION PIPING
 AND CONNECTIONS AND VALVE LOCATIONS- 1005.2 D)
 LOCATIONS AND CONNECTIONS OF SAFETY RELIEF VALVES,
 PRESSURE RELIEF VALVES, DISCHARGE PIPING AND DISCHARGE
 LOCATIONS- SECTIONS 1006.2,1006.3, 1006.4, 1006.5,
 1006.6, AND 1006.7. E) LOCATION OF THE EXPANSION TANK-
 SECTION 1009 FBC M. E) CONNECTION LOCATIONS OF THE GAS
 PIPING AND REGULATOR, COMBUSTION AIR DUCTS, AND VENT
 DUCT- SECTION 107.2.1 WPB.
  
 6) SHEET M501: SHOW THE LOCATION OF THE REQUIRED FLOOR
 DRAIN FOR THE BOILERS- SECTION 1004.6 FBC M.
  
 7) M501: SHOW THE GAS PIPING RUN INTO THE BOILER ROOM-
 SECTION 107.2.1 WPB.
  
 8) PROVIDE A GAS ISOMETRIC DRAWING THAT SHOWS THE TYPE
 AND DIAMETERS OF PIPING, THE MEASUREMENTS OF EACH CUT
 LENGTH OF PIPE, THE TOTAL DEVELOPED LENGTH OF THE
 PIPING RUN FROM THE POINT OF DELIVERY AT THE METER TO
 THE MOST REMOTE OUTLET IN THE BUILDING AND TO THE
 BOILERS; GAS DELIVERY PRESSURE OF THE SYSTEM AT THE
 METER AND AT EACH STEPDOWN REGULATOR; LOCATIONS OF
 REQUIRED SHUTOFF VALVES, AND THE BTUH LOADS OF THE NEW
 BOILERS, AND ALL OTHER GAS-FIRED APPLIANCES AND
 EQUIPMENT BEING SERVED BY THE SYSTEM- SECTIONS 402.2
 AND 402.3 FBC FG. PLEASE INDICATE WHICH PIPE SIZING
 TABLES WERE USED IN THE DESIGN- SECTION 402.3.
 A) CONCERNING THE REGULATORS PLEASE REFER TO SECTIONS
 410.1, 410.2, & 410.3 FBC FG FOR LINE AND MP REGULATOR
 INSTALLATION AND VENTING REQUIREMENTS. PLEASE VERIFY
 SUBMITTALS ARE COMPLIANT AND SHOW ALL REGULATOR AND
 SHUTOFF VALVES IN THE ISOMETRIC DRAWING, AND REGULATOR
 VENT RUNS AND TERMINATION LOCATIONS WHERE REQUIRED.
  
 9) PROVIDE A VENT FLUE DIAGRAM THAT SHOWS THE LENGTHS
 OF THE CONNECTORS, HORIZONTAL AND VERTICAL RUN LENGTHS,
 TOTAL RUN LENGTH OF THE SYSTEM, AND LOCATIONS OF
 OFFSETS, FITTINGS ETC. PER THE NOTES ON SHEET M102 THE
 PROPOSED SYSTEM REQUIRES ENGINEERED SIZING CALCULATIONS
 WHICH SHALL ACCOMPANY THE VENTING DIAGRAM- SEE SECTION
 506.6.9.3 FBC FG. PLEASE INDICATE THE "VENTING
 APPLIANCE CATEGORY" - I, II, III, OR IV THAT THE SYSTEM
 IS BEING DESIGNED FOR, AND IF THE SYSTEM IS POSITIVE OR
 NEGATIVE AND PRODUCES CONDENSATION- SEE SECTION 202 FBC
 FG. CURRENTLY, A THOROUGH REVIEW OF THE SYSTEM CANNOT
 BE ACCOMPLISHED WITHOUT THE DIAGRAM, AND ADDITIONAL
 SPECIFICATIONS AND INFORMATION- SECTION 107.2.1 WPB.
 PLEASE REFER BACK TO COMMENT #1 FOR SUBMITTAL
 REQUIREMENTS AND REQUIRED UL LISTING AND LABELING. A)
 M502: REFER TO SECTION 503.8 FBC FG, AND SHOW THE
 REQUIRED CLEARANCES FROM THE VENT FLUE TERMINATION TO
 MECHANICAL AND GRAVITY AIR INTAKES OR ANY OPERABLE
 OPENINGS INTO THE BUILDING.
  
 10) PROVIDE A COMBUSTION AIR DUCT DIAGRAM THAT SHOWS
 THE LENGTHS OF THE CONNECTORS, HORIZONTAL AND VERTICAL
 RUN LENGTHS, TOTAL RUN LENGTH OF THE SYSTEM, AND
 LOCATIONS OF OFFSETS, FITTINGS ETC.- SECTION 304.1 AND
 304.11 FBC FG. CURRENTLY, A THOROUGH REVIEW OF THE
 SYSTEM CANNOT BE ACCOMPLISHED WITHOUT THE DIAGRAM, AND
 ADDITIONAL SPECIFICATIONS AND INFORMATION- SECTION
 107.2.1 WPB. PLEASE REFER BACK TO COMMENT #1 FOR
 SUBMITTAL REQUIREMENTS AND REQUIRED UL LISTING AND
 LABELING.
  
 11) M201: THE SCOPE OF WORK NOTES INDICATE DEMOLITION
 OF AIR CONDITIONING UNITS, DUCTS, TERMINAL BOXES ETC.
 HOWEVER THE DRAWINGS TO NOT SHOW ANY AC DEMOLITION OR
 REWORK. PLEASE PROVIDE THE DRAWINGS- SECTION 107.2.1
 WPB.
  
 12) M401: PLEASE PLACE A NOTE THAT THE WELDER'S
 CETIFICATES AND WELDING PROCEDURES SHALL BE ONSITE AT
 TIME OF INSPECTION- SECTION 107.2.1 WPB.
  
 13) PROVIDE UL LISTED FIRE STOPPING ASSEMBLIES FOR THE
 PENETRATIONS OF THE VENT FLUE, AND COMBUSTION AIR DUCTS
 HROUGH THE FIRE RATED WALLS AND FLOOR CEILING
 ASSEMBLIES- SECTION 714 FBC B.
  
 14) INDICATE THE TYPE AND THICKNESSES OF THE BOILER
 SERVICE WATER PIPING INSULATIONS AND PROVIDE A PRODUCT
 SUBMITTAL- SEE TABLE C403.2.10 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-06-11 Cont ID  
Sent By ccole Date 2020-06-11 Time 10:55 Rev Time 0.00
Received By ccole Date 2020-06-11 Time 06:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-05-14 Cont ID  
Sent By ccole Date 2020-05-14 Time 14:34 Rev Time 0.00
Received By ccole Date 2020-05-14 Time 13:38 Sent To  
Notes
2020-05-14 14:36:332ND REVIEW FBC-2017 PLUMBING
 PERMIT #20040366
 5/14/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENT #2 FROM THE 1ST REVIEW PRINTED BELOW WAS NOT
 COMPLETELY ADDRESSED.
  
 2) PROVIDE A CONDENSATE DISPOSAL DIAGRAM SHOWING HOW
 CONDENSATE FROM THE VENT FLUE, AND FROM THE BOILER
 NEUTRALIZERS WILL BE DRAINED AND DISPOSED OF- SECTION
 107.2.1 WPB. SEE MECHANICAL COMMENT #1 FOR NEUTRALIZER
 PRODUCT SUBMITTAL REQUIREMENT.
  
 THE REQUESTED DIAGRAM WAS NOT PROVIDED ON SHEET P-001.
 AS STATED IN THE NARRATIVE RESPONSE BY THE EOR. SHEETS
 P-001 & P-501:
 A) PLEASE PROVIDE THE CONDENSATE DRAINAGE DIAGRAM
 SHOWING THE DRAIN LINE RUN FROM THE VENT TO THE ACID
 NEUTRALIZING TANK, AND THE WASTE LINE RUN FROM THE TANK
 TO THE FLOOR DRAIN- SECTION 107.2.1 WPB.
 B) P-501: SHOW THE CONDENSATE DRAIN LINE RUN TO THE
 ACID TANK, AND THE WASTE LINE RUN TO THE FLOOR DRAIN ON
 THE PLAN.
 C) 2ND REQUEST TO SUBMIT SPECS FOR THE TANK. PLEASE
 NOTE THAT SECTION 803.1 FBC P REQUIRES THAT AN
 AUTOMATIC SUFFICIENT SUPPLY OF DILUTING WATER IS
 REQUIRED SO AS TO MAKE THE CONTENTS NONINJURIOUS BEFORE
 DISCHARGE INTO THE DRAINAGE SYSTEM. THE NATURE OF THE
 CORROSIVE OR HARMFUL WASTE AND THE METHOD OF ITS
 TREATMENT OR DILUTION SHALL BE APPROVED PRIOR TO
 INSTALLATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-14 Cont ID  
Sent By ccole Date 2020-04-14 Time 14:10 Rev Time 0.00
Received By ccole Date 2020-04-14 Time 12:56 Sent To  
Notes
2020-04-14 14:34:521ST REVIEW FBC-2017 PLUMBING
 PERMIT #20040366
 4/14/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 608.16.2 FBC P AND PROVIDE A
 PRODUCT SUBMITTAL FOR THE RPZ BACKFLOW PREVENTER. THE
 POTABLE SUPPLY TO THE BOILER SHALL BE EQUIPPED WITH A
 BACKFLOW PREVENTER WITH AN INTERMEDIATE ATMOSPHERIC
 VENT COMPLYING WITH ASSE 1012 OR CSA B64.3. WHERE
 CONDITIONING CHEMICALS ARE INTRODUCED INTO THE SYSTEM,
 THE POTABLE WATER CONNECTION SHALL BE PROTECTED BY AN
 AIR GAP OR A REDUCED PRESSURE PRINCIPLE BACKFLOW
 PREVENTER, COMPLYING WITH ASSE 1013, CSA B64.4 OR AWWA
 C511.
  
 2) PROVIDE A CONDENSATE DISPOSAL DIAGRAM SHOWING HOW
 CONDENSATE FROM THE VENT FLUE, AND FROM THE BOILER
 NEUTRALIZERS WILL BE DRAINED AND DISPOSED OF- SECTION
 107.2.1 WPB. SEE MECHANICAL COMMENT #1 FOR NEUTRALIZER
 PRODUCT SUBMITTAL REQUIREMENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-11 Cont ID  
Sent By ccole Date 2020-06-11 Time 11:28 Rev Time 0.00
Received By ccole Date 2020-06-11 Time 11:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-05-15 Cont ID  
Sent By rmcphers Date 2020-05-15 Time 08:54 Rev Time 0.00
Received By rmcphers Date 2020-05-15 Time 08:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-15 Cont ID  
Sent By ccole Date 2020-04-15 Time 11:24 Rev Time 0.00
Received By ccole Date 2020-04-15 Time 11:24 Sent To  
Notes
***NONE***