Plan Review Details - Permit 20040269
Plan Review Stops For Permit 20040269
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-04-30 Cont ID  
Sent By rmcphers Date 2020-04-30 Time 10:01 Rev Time 0.00
Received By rmcphers Date 2020-04-30 Time 10:01 Sent To  
Notes
2020-04-30 09:49:53ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 THE ENGINEERING PROVIDED COVERS THE CONNECTION FOR THE
 ROOF METAL PANELS. THE ENGINEERS DIGITAL SIGNATURE
 NEEDS TO BE VERIFIED FAC 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE
 THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY.
  
 THE BUILDING NEEDS TO BE EVALUATED BY AN ENGINEER OR
 ARCHITECT (ROOF-TO-WALL CONNECTIONS SHALL BE EVALUATED
 FOR THE WIND LOADS SPECIFIED IN THE FLORIDA BUILDING
 CODE, BUILDING, INCLUDING WIND UPLIFT. IF THE
 DIAPHRAGMS AND CONNECTIONS IN THEIR CURRENT CONDITION
 ARE NOT CAPABLE OF RESISTING AT LEAST 75 PERCENT OF
 THOSE WIND LOADS, THEY SHALL BE REPLACED OR
 STRENGTHENED IN ACCORDANCE WITH THE LOADS SPECIFIED IN
 THE FLORIDA BUILDING CODE, BUILDING) PLEASE HAVE YOUR
 ENGINEER SEE THE CODE SECTION BELOW AND PROVIDE A
 SIGNED AND SEALED LETTER TO ADDRESS THE ROOF TO WALL
 CONNECTIONS AS NOTED IN THE CODE SECTION.
 MAYBE THE BUILDING MEETS ONE OF THE EXCEPTIONS LISTED
 UNDER THAT CODE SECTION (FBC EXISTING BUILDING -
 707.3.2) PLEASE PROVIDE A SIGNED AND SEALED LETTER FROM
 THE ENGINEER STATING WHICH EXCEPTION.
  
 1) FOR A BUILDING WITH THE ROOF METAL PANELS ACTING AS
 THE DIAPHRAGM ( NO ROOF SHEATHING) FOR THE ROOF
 FRAMING. THE 2017 FBC EXISTING BUILDING CODE REQUIRES
 AN EVALUATION FROM AN ARCHITECT OR ENGINEER.
 2) PLEASE PROVIDE A SIGNED AND SEALED BUILDING WIND
 DESIGN VALUATION FROM AN ARCHITECT OR ENGINEER PER FBC
 EXISTING BUILDING - 707.3.2 ROOF DIAPHRAGMS RESISTING
 WIND LOADS IN HIGH-WIND REGIONS.
 WHERE ROOFING MATERIALS ARE REMOVED FROM MORE THAN 50
 PERCENT OF THE ROOF DIAPHRAGM OR SECTION OF A BUILDING
 LOCATED WHERE THE ULTIMATE DESIGN WIND SPEED, VULT,
 DETERMINED IN ACCORDANCE WITH FIGURE 1609.3(1) OF THE
 FLORIDA BUILDING CODE, BUILDING, IS GREATER THAN 115
 MPH (51 M/S), AS DEFINED IN SECTION 1609 (THE
 HIGH-VELOCITY HURRICANE ZONE SHALL COMPLY WITH SECTION
 1620) OF THE FLORIDA BUILDING CODE, BUILDING, ROOF
 DIAPHRAGMS, CONNECTIONS OF THE ROOF DIAPHRAGM TO ROOF
 FRAMING MEMBERS, AND ROOF-TO-WALL CONNECTIONS SHALL BE
 EVALUATED FOR THE WIND LOADS SPECIFIED IN THE FLORIDA
 BUILDING CODE, BUILDING, INCLUDING WIND UPLIFT. IF THE
 DIAPHRAGMS AND CONNECTIONS IN THEIR CURRENT CONDITION
 ARE NOT CAPABLE OF RESISTING AT LEAST 75 PERCENT OF
 THOSE WIND LOADS, THEY SHALL BE REPLACED OR
 STRENGTHENED IN ACCORDANCE WITH THE LOADS SPECIFIED IN
 THE FLORIDA BUILDING CODE, BUILDING.
 3) SIGNED AND SEALED DRAWINGS OR DOCUMENTS NEED TO BE
 ELECTRONICALLY SIGNED AND SEALED TO BE USED IN
 ELECTRONIC PLAN REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-24 Cont ID  
Sent By rmcphers Date 2020-04-24 Time 11:35 Rev Time 0.00
Received By rmcphers Date 2020-04-24 Time 11:06 Sent To  
Notes
2020-04-24 11:34:44ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) FOR A BUILDING WITH THE ROOF METAL PANELS ACTING AS
 THE DIAPHRAGM ( NO ROOF SHEATHING) FOR THE ROOF
 FRAMING. THE 2017 FBC EXISTING BUILDING CODE REQUIRES
 AN EVALUATION FROM AN ARCHITECT OR ENGINEER.
 2) PLEASE PROVIDE A SIGNED AND SEALED BUILDING WIND
 DESIGN VALUATION FROM AN ARCHITECT OR ENGINEER PER FBC
 EXISTING BUILDING - 707.3.2 ROOF DIAPHRAGMS RESISTING
 WIND LOADS IN HIGH-WIND REGIONS.
 WHERE ROOFING MATERIALS ARE REMOVED FROM MORE THAN 50
 PERCENT OF THE ROOF DIAPHRAGM OR SECTION OF A BUILDING
 LOCATED WHERE THE ULTIMATE DESIGN WIND SPEED, VULT,
 DETERMINED IN ACCORDANCE WITH FIGURE 1609.3(1) OF THE
 FLORIDA BUILDING CODE, BUILDING, IS GREATER THAN 115
 MPH (51 M/S), AS DEFINED IN SECTION 1609 (THE
 HIGH-VELOCITY HURRICANE ZONE SHALL COMPLY WITH SECTION
 1620) OF THE FLORIDA BUILDING CODE, BUILDING, ROOF
 DIAPHRAGMS, CONNECTIONS OF THE ROOF DIAPHRAGM TO ROOF
 FRAMING MEMBERS, AND ROOF-TO-WALL CONNECTIONS SHALL BE
 EVALUATED FOR THE WIND LOADS SPECIFIED IN THE FLORIDA
 BUILDING CODE, BUILDING, INCLUDING WIND UPLIFT. IF THE
 DIAPHRAGMS AND CONNECTIONS IN THEIR CURRENT CONDITION
 ARE NOT CAPABLE OF RESISTING AT LEAST 75 PERCENT OF
 THOSE WIND LOADS, THEY SHALL BE REPLACED OR
 STRENGTHENED IN ACCORDANCE WITH THE LOADS SPECIFIED IN
 THE FLORIDA BUILDING CODE, BUILDING.
 3) SIGNED AND SEALED DRAWINGS OR DOCUMENTS NEED TO BE
 ELECTRONICALLY SIGNED AND SEALED TO BE USED IN
 ELECTRONIC PLAN REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-22 Cont ID  
Sent By rmcphers Date 2020-04-22 Time 13:07 Rev Time 0.00
Received By rmcphers Date 2020-04-22 Time 11:45 Sent To  
Notes
2020-04-22 13:25:16ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL PROVIDED FOR THE METAL ROOFING
 PANELS SHOWS METAL PANEL TO BE OVER PLYWOOD ROOF
 SHEATHING. CONTRACT PROVIDED DOES NOT MENTION ROOF
 SHEATHING. PLEASE PROVIDE DETAILS FOR THE EXISTING
 BUILDING - IS THERE PLYWOOD ROOF SHEATHING?
 2) PLEASE PROVIDE THE UL ROOFING SYSTEMS FIRE DIRECTORY
 SHOWING THE ROOFING SYSTEM FIRE CLASSIFICATION A,B,
 OR,C FBC 1505.1
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-30 Cont ID  
Sent By rmcphers Date 2020-04-30 Time 10:42 Rev Time 0.00
Received By rmcphers Date 2020-04-29 Time 13:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-24 Cont ID  
Sent By rmcphers Date 2020-04-24 Time 11:36 Rev Time 0.00
Received By rmcphers Date 2020-04-23 Time 10:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-22 Cont ID  
Sent By rmcphers Date 2020-04-22 Time 13:25 Rev Time 0.00
Received By rmcphers Date 2020-04-21 Time 10:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-04-30 Cont ID  
Sent By rmcphers Date 2020-04-30 Time 10:42 Rev Time 0.00
Received By rmcphers Date 2020-04-30 Time 10:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-04-24 Cont ID  
Sent By rmcphers Date 2020-04-24 Time 11:35 Rev Time 0.00
Received By rmcphers Date 2020-04-24 Time 11:35 Sent To  
Notes
2020-04-24 11:35:47SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-22 Cont ID  
Sent By rmcphers Date 2020-04-22 Time 13:25 Rev Time 0.00
Received By rmcphers Date 2020-04-22 Time 13:25 Sent To  
Notes
***NONE***