2020-04-08 12:08:08 | PLAN REVIEW - BUILDING |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER ? BUILDING - PX3169 |
| PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. STATE HEIGHT OF WINDOWS ABOVE GRADE ON PLAN.FBC |
| CHPT. 16 |
| |
| 2. SHOW ORIENTATION OF BUILDING TO CARDINAL NORTH. STAE |
| EXSPOSURE CATEGORY ON PLAN. FBC CHPT. 16 |
| |
| 3. STATE ZONE WINDOWS ARE LOCATED IN ON PLAN. (4 OR 5) |
| FBC CHPT. 16 |
| |
| 4. PROVIDE DESIGN WIND CALCULATIONS PER ASCE-7. FBC |
| CHPT. 16 |
| |
| 5. SHOW SIZE OF EACH OPENING ON PLAN. FBC CHPT. 16 |
| |
| 6. STATE DESIGN PRESSURE OF EACH OPENING ON PLAN NEXT |
| TO APPROPRIATE OPENING. FBC CHPT. 16 |
| |
| 7. DESIGNER SHALL PRINT NAME AND SIGN PLAN AND DESIGN |
| WIND CALC'S. |
| |
| NON-DESIGN PROFESSIONALS |
| |
| 1. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A |
| TITLE BLOCK AND SIGNATURE ON PLAN SHEETS UNDER THEIR |
| AUTHORITY ? |
| 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, SECTION 107.2.1. |
| IF THE DESIGNER IS A FLORIDA LICENSED ARCHITECT OR |
| ENGINEER, HE/SHE SHALL ALSO PROVIDE AN ORIGINAL SEAL |
| AND WET SIGNATURE PER F.S. 61G15-16.003 AND FAC 23.002. |
| |
| 2. UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL WITH |
| SIGNATURE OF DESIGNER AS APPLICABLE; USE THE REQUIRED |
| NAMING CONVENTION FOR EACH DOCUMENT. |
| |
| |
| |