Plan Review Details - Permit 20040149
Plan Review Stops For Permit 20040149
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-12 Cont ID  
Sent By rmcdouga Date 2021-04-12 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2021-04-12 Time 09:18 Sent To  
Notes
2021-04-12 09:12:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE REVISION APPLICATION STATES THAT THE NUMBER OF
 OVERFLOW SCUPPERS IS TO BE REDUCED FROM (4) FOUR TO (3)
 THREE. THE PLAN SHEET THAT WAS SUBMITTED ONLY SHOWS THE
 SCUPPER DETAILS. IN ORDER TO SHOW COMPLIANCE WITH THE
 FBC YOU WILL NEED TO SUBMIT THE ROOF PLANS THAT SHOW
 THE LOCATIONS OF THE OVERFLOW SCUPPERS AND SHOW THAT
 THEY CAN PROVIDE THE REQUIRED ROOF DRAINAGE. INDICATE
 THE LOCATION OF THE (1) ONE THAT IS BEING ELIMINATED
 AND THE LOCATIONS OF THE (3) THAT WILL REMAIN. FBC
 AMENDMENTS 107.2.1
  
 2) SUBMIT CALCULATIONS TO SHOW THAT THE (3) THREE
 REMAINING OVERFLOW SCUPPERS WILL PROVIDE THE REQUIRED
 AMOUNT OF ROOF DRAINAGE. FBC 1503.4
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-04-16 Time   Rev Time 0.00
Received By shill Date 2021-04-07 Time 18:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-16 Cont ID  
Sent By ccole Date 2021-04-16 Time 12:13 Rev Time 0.00
Received By ccole Date 2021-04-16 Time 11:23 Sent To  
Notes
2021-04-16 12:15:561ST REVIEW FBC-2020 PLUMBING
 PERMIT- 20040149
 4/16/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A REVISED ROOF DRAINAGE PLAN SHOWING THE
 LOCATION OF THE REMOVED SCUPPER. PLEASE INCLUDE THE
 ROOF AREA CALCULATIONS AND SHOW THE REMAINING SCUPPERS-
 LOCATIONS AND SIZES- WILL PROVIDE ADEQUATE EMERGENCY
 OVERFLOW DRAINAGE BASED ON THE RAINFALL RATE FOR WHICH
 THE PRIMARY SYSTEM IS SIZED- SECTION 1108.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-12 Cont ID  
Sent By rmcdouga Date 2021-04-12 Time 09:20 Rev Time 0.00
Received By rmcdouga Date 2021-04-12 Time 09:20 Sent To  
Notes
***NONE***