Plan Review Details - Permit 20040148
Plan Review Stops For Permit 20040148
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-16 Cont ID  
Sent By rmcdouga Date 2020-04-16 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2020-04-16 Time 10:43 Sent To  
Notes
2020-04-16 11:03:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT CALCULATIONS, DETAILS AND ANY OTHER DOCMENTS
 NECESSARY TO SHOW THAT REDUCING THE OVERFLOW SCUPPERS
 FROM 4" TO 3" WILL NOT REDUCE THE REQUIRED AMOUNT OF
 RAIN WATER DISCHARGE FORM THE ROOF MORE THAN REQUIRED
 BY CODE. FBC 107.2.1.2
  
 2) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-23 Cont ID  
Sent By tklarge Date 2020-04-23 Time 13:38 Rev Time 0.00
Received By tklarge Date 2020-04-13 Time 16:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-23 Cont ID  
Sent By tklarge Date 2020-04-23 Time 13:35 Rev Time 0.00
Received By tklarge Date 2020-04-23 Time 13:29 Sent To  
Notes
2020-04-23 13:35:261) SCUPPERS SHALL HAVE AN OPENING DIMENSION OF NOT LESS
 THAN 4 INCHES PER FBC-PLUMBING SEC.1108.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-16 Cont ID  
Sent By rmcdouga Date 2020-04-16 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2020-04-16 Time 11:03 Sent To  
Notes
2020-04-16 11:05:26THE CURRENT DRAWING IS DIGITALLY SIGNED. THE SIGNATURES
 WILL HAVE TO BE VERIFIED ON ANY NEW SUBMITTALS.