Plan Review Details - Permit 20040115
Plan Review Stops For Permit 20040115
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-28 Cont ID  
Sent By dbattles Date 2020-08-28 Time 11:09 Rev Time 0.00
Received By dbattles Date 2020-08-28 Time 11:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-15 Cont ID  
Sent By rmcphers Date 2020-04-15 Time 10:00 Rev Time 0.00
Received By rmcphers Date 2020-04-15 Time 09:34 Sent To  
Notes
2020-04-15 10:00:47CHANGE OF OCCUPANCY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE OCCUPANCY CLASSIFICATION PER FBC
 CHAPTER 3.
 2) PLEASE PROVIDE A LIFE SAFETY PLAN SHOWING MEANS OF
 EGRESS FBC CHAPTER10, FIRE SPRINKLERS FBC 420.5, FIRE
 ALARMS AND SMOKE ALARMS FBC 420.6 ETC.
 3) PLEASE SHOW THE NUMBER OF OCCUPANTS.
 4) PLEASE SHOW THE FIRE RATING OF THE SEPARATION WALLS
 TO COMPLY WITH FBC 420.2
 5) PLEASE DESCRIBE THE USE FOR THE BUILDING - WHAT ARE
 THE OCCUPANTS THERE FOR?
  
 GROUP R-4 OCCUPANCIES SHALL MEET THE REQUIREMENTS FOR
 CONSTRUCTION AS DEFINED FOR GROUP R-3, EXCEPT AS
 OTHERWISE PROVIDED FOR IN THIS CODE OR SHALL COMPLY
 WITH THE FLORIDA BUILDING CODE, RESIDENTIAL PROVIDED
 THE BUILDING IS PROTECTED BY AN AUTOMATIC SPRINKLER
 SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.2.8.
  
 310.6.1CONDITION 1.
 THIS OCCUPANCY CONDITION SHALL INCLUDE BUILDINGS IN
 WHICH ALL PERSONS RECEIVING CUSTODIAL CARE, WITHOUT ANY
 ASSISTANCE, ARE CAPABLE OF RESPONDING TO AN EMERGENCY
 SITUATION TO COMPLETE BUILDING EVACUATION. 310.6.2
 CONDITION 2. THIS OCCUPANCY CONDITION SHALL INCLUDE
 BUILDINGS IN WHICH THERE ARE ANY PERSONS RECEIVING
 CUSTODIAL CARE WHO REQUIRE LIMITED VERBAL OR PHYSICAL
 ASSISTANCE WHILE RESPONDING TO AN EMERGENCY SITUATION
 TO COMPLETE BUILDING EVACUATION.
  
 310.6.2CONDITION 2.
 THIS OCCUPANCY CONDITION SHALL INCLUDE BUILDINGS IN
 WHICH THERE ARE ANY PERSONS RECEIVING CUSTODIAL CARE
 WHO REQUIRE LIMITED VERBAL OR PHYSICAL ASSISTANCE WHILE
 RESPONDING TO AN EMERGENCY SITUATION TO COMPLETE
 BUILDING EVACUATION.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2020-08-28 Cont ID  
Sent By dbattles Date 2020-08-28 Time 11:09 Rev Time 0.00
Received By dbattles Date 2020-08-28 Time 11:09 Sent To  
Notes
2020-08-28 11:10:39NO ELECTRICAL WORK.
 LOW VOLTAGE UNDER FA 20020852

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-15 Cont ID  
Sent By jleahy Date 2020-04-15 Time 09:35 Rev Time 0.00
Received By jleahy Date 2020-04-15 Time 09:21 Sent To  
Notes
2020-04-15 09:36:40FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE PROVIDE MORE DETAIL AS TO THE CHANGE OF USE AND
 OR OCCUPNACY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-08-28 Cont ID  
Sent By pleduc Date 2020-08-28 Time   Rev Time 0.00
Received By pleduc Date 2020-08-28 Time 11:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-04-09 Cont ID  
Sent By bwoods Date 2020-04-09 Time   Rev Time  
Received By bwoods Date 2020-04-09 Time   Sent To  
Notes
2020-04-09 12:22:22PERMIT #20040115
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 PROVIDED CLARIFICATION ON THE CHANGE OF OCCUPANCY THAT
 DESCRIBES THE OCCUPANCY USE OF
 STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL
 BE CLASSIFIED IN ACCORDANCE WITH 6.1.2 THROUGH 6.1.13.
 OCCUPANCY CLASSIFICATION.
  
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, EXIT SIGNS, EMERGENCY LIGHTING, TRAVEL
 DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 ENGINEERED FIRE ALARM CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
 BRITTANY WOODS
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4754
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-28 Cont ID  
Sent By dbattles Date 2020-08-28 Time 12:42 Rev Time 0.00
Received By dbattles Date 2020-08-28 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-15 Cont ID  
Sent By rmcphers Date 2020-04-15 Time 10:14 Rev Time 0.00
Received By rmcphers Date 2020-04-06 Time 14:36 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2020-08-28 Cont ID  
Sent By dbattles Date 2020-08-28 Time 11:04 Rev Time 0.00
Received By dbattles Date 2020-08-28 Time 11:04 Sent To  
Notes
2020-08-28 11:06:02NO CHANGE IN SQ. FOOTAGE OR OCCUPANT COUNT.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-04-15 Cont ID  
Sent By rmcphers Date 2020-04-15 Time 10:01 Rev Time 0.00
Received By rmcphers Date 2020-04-15 Time 10:01 Sent To  
Notes
2020-04-15 10:02:06PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-08-28 Cont ID  
Sent By dbattles Date 2020-08-28 Time 11:06 Rev Time 0.00
Received By dbattles Date 2020-08-28 Time 11:06 Sent To  
Notes
2020-08-28 11:07:35NO MECHANICAL
 R-3 USING RESIDENTIAL CODE AND NO ADDITIONAL
 REQUIREMENTS APPLY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-07 Cont ID  
Sent By medwards Date 2020-04-07 Time 13:50 Rev Time 0.00
Received By medwards Date 2020-04-07 Time 13:50 Sent To  
Notes
2020-04-07 13:52:41PLEASE PROVIDE MORE INFORMATION FOR THIS CHANGE OF USE.
 IS IT ALSO GOING TO BE A CHANGE OF OCCUPANCY? WHAT WILL
 THE NEW OCCUPANCY CLASSIFICATION BE? FBC WPB 107.2.1

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-28 Cont ID  
Sent By dbattles Date 2020-08-28 Time 11:07 Rev Time 0.00
Received By dbattles Date 2020-08-28 Time 11:07 Sent To  
Notes
2020-08-28 11:09:11NO PLUMBING PROPOSED
 R-3 5 OR FEWER TO FOLLOW RESIDENTIAL AND NO ADDITIONAL
 REQUIREMENTS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-08 Cont ID  
Sent By lcrespo Date 2020-04-08 Time 06:40 Rev Time 0.00
Received By lcrespo Date 2020-04-07 Time 18:09 Sent To  
Notes
2020-04-08 06:40:5804/07/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE DETAIL ABOUT THE CHANGE OF OCCUPANCY
 IN ACCORDANCE WITH 2017 FBC SEC 201.1 SCOPE AND THAT
 WHICH ARE CONVERTED FROM RESIDENTIAL TO NONRESIDENTIAL
 OR MIXED USE AS DEFINED BY THE FLORIDA BUILDING CODE
 WHERE SUCH BUILDING OR FACILITY MUST, AT A MINIMUM,
 COMPLY WITH S. 553.508, FS.
  
 2. THE PLAN IS TOO SMALL TO READ NOTES, PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE PER THE WPB AMENDMENT
 TO FBC SEC. 107.2.1.3 QUALITY OF BUILDING PLANS.
  
 3. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL
 PLUMBING.
  
 4. PLEASE SHOW THE SOURCE OF HOT WATER AND LOCATION PER
 THE 2017 FBC SEC P 607.4. WATER HEATER MEANS A PRODUCT
 WHICH UTILIZES OIL, GAS, OR ELECTRICITY TO HEAT POTABLE
 WATER FOR USE OUTSIDE THE HEATER UPON DEMAND, INCLUDING
 -
 (1) STORAGE TYPE UNITS WHICH HEAT AND STORE WATER AT A
 THERMOSTATICALLY CONTROLLED TEMPERATURE, INCLUDING GAS
 STORAGE WATER HEATERS WITH AN INPUT OF 75,000 BTU PER
 HOUR OR LESS, OIL STORAGE WATER HEATERS WITH AN INPUT
 OF 105,000 BTU PER HOUR OR LESS, AND ELECTRIC STORAGE
 WATER HEATERS WITH AN INPUT OF 12 KILOWATTS OR LESS;
  
 (2) INSTANTANEOUS TYPE UNITS WHICH HEAT WATER BUT
 CONTAIN NO MORE THAN ONE GALLON OF WATER PER 4,000 BTU
 PER HOUR OF INPUT, INCLUDING GAS INSTANTANEOUS WATER
 HEATERS WITH AN INPUT OF 200,000 BTU PER HOUR OR LESS,
 OIL INSTANTANEOUS WATER HEATERS WITH AN INPUT OF
 210,000 BTU PER HOUR OR LESS, AND ELECTRIC
 INSTANTANEOUS WATER HEATERS WITH AN INPUT OF 12
 KILOWATTS OR LESS; AND
  
 (3) HEAT PUMP TYPE UNITS, WITH A MAXIMUM CURRENT RATING
 OF 24 AMPERES AT A VOLTAGE NO GREATER THAN 250 VOLTS,
 WHICH ARE PRODUCTS DESIGNED TO TRANSFER THERMAL ENERGY
 FROM ONE TEMPERATURE LEVEL TO A HIGHER TEMPERATURE
 LEVEL FOR THE PURPOSE OF HEATING WATER, INCLUDING ALL
 ANCILLARY EQUIPMENT SUCH AS FANS, STORAGE TANKS, PUMPS,
 OR CONTROLS NECESSARY FOR THE DEVICE TO PERFORM ITS
 FUNCTION.
  
 5. THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS PER THE 2017
 FBC WPB AMENDMENTS SEC. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.
  
 6. THERE IS NO CLAIMED VALUE ON THE APPLICATION, PLEASE
 PROVIDE A BONA FIDE SIGNED CONTRACT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 109.3 BUILDING PERMIT
 VALUATIONS. IF IN THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF BUILDING, ALTERATION,
 STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, THE VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS
 PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL
 BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING
 OFFICIAL.
  
 7. PLANS MAY BE REQUIRED TO BE DESIGNED AND SIGNED AND
 SEALED BY A LICENSED ENGINEER OR ARCHITECT. PLANS
 FURNISHED BY AN INTERIOR DESIGNER ARE NOT ACCEPTABLE.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC
 107.2.1, 107.3.5.
  
 8. ALL PLUMBING MUST COMPLY WITH THE FLORIDA BUILDING
 CODE 2017 6TH EDITION.
  
 9. PLEASE PROVIDE WHAT TYPE OF OCCUPANCY THIS INTERIOR
 BUILD-OUT WILL BE AND THE OCCUPANCY LOAD WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 10. PLEASE GIVE THE LEVEL OF ALTERATION PER 2017
 FLORIDA EXISTING BUILDING CODE 301.1.
  
 11. PROVIDE MINIMUM SANITARY FACILITIES ACCORDING TO
 2017 FBC P TABLE 403.1.
  
 12. PLEASE IDENTIFY ALL THE USE OF ROOMS ON PLANS. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 13. PLEASE PROVIDE ACCESSIBILITY PLUMBING FACILITIES
 AND ADA DETAIL OF HEIGHTS AND DIMENSIONS REQUIRED,
 PLEASE PROVIDE DETAIL DRAWINGS PER 2017 FBC
 ACCESSIBILITY CODE 2017 FBC P404.1.
  
 14. THE SCOPE OF THE PLUMBING TO BE DONE IS UNCLEAR
 PLEASE PROVIDE A PLUMBING PLAN INCLUDING A SANITARY AND
 WATER ISOMETRIC DRAWING. PER WPB AMEND TO FBC
 107.3.5.1.3(13).
  
 15. PLEASE PROVIDE PRICE BREAK DOWN FOR WORK BEING DONE
 TO INCREASE ACCESSIBILITY TO COMPLY WITH THE 2017 FBC
 ACC 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE-HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
  
 16. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 17. THE MAIN WATER SERVICE WHICH HAS ITS OWN METER MAY
 REQUIRE A REDUCE PRESSURE ZONE VACUUM BREAKER INSTALLED
 BY A LICENSED CONTRACTOR AND THIS DEVICE REQUIRES A
 PERMIT, REVIEWS BY PLUMBING DEPARTMENT AS WELL AS THE
 UTILITIES DEPARTMENT AND IT NEEDS TO BE CERTIFIED BY
 THE UTILITIES DEPARTMENT. THIS IS A CONTAINMENT DEVICE
 AS THE CITY OF WEST PALM BEACH UTILITIES DEPARTMENT HAS
 JURISDICTION OF IT. THIS PERMIT MAY BE COMBINED WITH
 LAWN SPRINKLERS A RPZ?S TYPE, A SEPARATE FIRE SPRINKLER
 SYSTEM REQUIRES A DOUBLE CHECK DETECTOR ASSEMBLY
 INSTALLED BY A LICENSED CONTRACTOR PER THE
 2017 FLORIDA STATUTES 633.102, INSURANCE, CHAPTER 633,
 FIRE PREVENTION AND CONTROL MAY BE REQUIRED AS WELL.
  
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-28 Cont ID  
Sent By dbattles Date 2020-08-28 Time 11:09 Rev Time 0.00
Received By dbattles Date 2020-08-28 Time 11:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-15 Cont ID  
Sent By rmcphers Date 2020-04-15 Time 10:13 Rev Time 0.00
Received By rmcphers Date 2020-04-15 Time 10:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status N Date 2020-08-28 Cont ID  
Sent By dbattles Date 2020-08-28 Time 11:11 Rev Time 0.00
Received By dbattles Date 2020-08-28 Time 11:11 Sent To  
Notes
2020-08-28 11:13:13NO WORK BEING DONE, NO ADDITIONAL SQ. FOOTAGE.
 CHANGE TO R-3 FOR SPRINKLERS ONLY.
 THIS FALLS UNDER FBC 2017 RESIDENTIAL

Review Stop Z ZONING
Rev No 1 Status F Date 2020-04-07 Cont ID  
Sent By rfalcone Date 2020-04-07 Time 15:11 Rev Time 0.00
Received By rfalcone Date 2020-04-07 Time 15:11 Sent To I
Notes
2020-04-07 15:15:37ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 04/07/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. CLARIFY EXACTLY WHAT THE SCOPE OF WORK IS.
  
 - ARE YOU ADDING AN ADDITIONAL ROOM?
 - ARE YOU CHANGING THE FOOTPRINT OF THE STRUCTURE? IF
 SO, PROVIDE A SURVEY OF THE SUBJECT SITE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved