Plan Review Stops For Permit 20040077 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-05-15 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-05-15 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-05-15 |
Time |
09:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-04-09 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-04-09 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-04-09 |
Time |
14:03 |
Sent To |
|
|
Notes |
2020-04-09 14:37:55 | GENERATOR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) ENGINEERING NEEDS TO BE SIGNED AND SEALED. | | ENGINEERING NEEDS TO BE ELECTRONICALLY SIGNED AND | | SEALED TO BE USED IN ELECTRONIC PLAN REVIEW. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2020-04-16 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2020-04-16 |
Time |
12:58 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-04-16 |
Time |
11:01 |
Sent To |
|
|
Notes |
2020-04-16 12:58:06 | PASSED BY JAKE LEAHY. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2020-06-17 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-06-17 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-06-17 |
Time |
08:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2020-05-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-05-21 |
Time |
07:16 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-05-20 |
Time |
15:30 |
Sent To |
|
|
Notes |
2020-05-21 07:25:15 | | | 1ST REVIEW FBC-2017 RES. FUEL GAS | | PERMIT #20040077 | | 5/20/2020 | | | | CODES IN EFFECT: | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) GAS RISER DRAWING: | | A) INDICATE THE TOTAL DEVELOPED LENGTH OF THE GAS | | PIPING SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET. | | THIS INCLUDES THE EXISTING AND THE NEW PIPING- | | SECTIONS- G2413.4.1 & G2413.4.2 FBC RES. THE CURRENT | | ISOMETRIC DOES NOT SHOW THE PIPING RUN AND BRANCH LINES | | TO THE EXISTING APPLIANCES IN THE HOUSE. A THOROUGH | | REVIEW OF THE PIPE SIZING CANNOT BE ACCOMPLISHED | | WITHOUT A COMPLETE DRAWING AND THE TOTAL DEVELOPED | | LENGTH OF THE SYSTEM- SECTIONS G2412.4 G2412.8, G2413.1 | | & G2413.3 FBC RES. | | B) SHOW THE SHUT OFF VALVE LOCATIONS AT THE NEW METER, | | AND AT THE NEW 2 PSI-11" WC REGULATOR- SECTION 2420.1 | | FBC RES. NOTE: WHERE CONNECTED TO RIGID PIPING, A UNION | | SHALL BE INSTALLED WITH 1 FT OF EITHER SIDE OF AN MP | | REGULATOR- SECTION G2421.2 FBC RES | | C) INDICATE THE SENSUS REGULATOR MODEL NUMBERS AND | | ORIFICE SIZES ON THE DRAWING. PLEASE PROVIDE A COMPLETE | | SUBMITTAL FOR THE REGULATORS. THERE ARE NO TECHNICAL | | DATA SHEETS PROVIDED TO VERIFY ORIFICE SIZING BASED ON | | OUTLET PRESSURES AND BODY SIZES- SECTION G2421.1 FBC | | RES. | | D) THERE IS A 3/4" PIPE TEED OFF INTO SPACE POSSIBLY | | FOR A FUTURE APPLIANCE- PLEASE INDICATE THE TYPE OF | | PIPING AND CLARIFY IT'S PURPOSE- SECTION 107.2.1 WPB. | | E) IDENTIFY THE TYPE OF PIPING FROM THE METER TO THE | | NEW HOUSE REGULATOR, AND SHOW THE CUT LENGTH OF THE | | PIPE FROM THE 1" TEE TO THE NEW REGULATOR- SECTION | | G2413.4.1 & G2413.4.2 | | | | 2) SURVEY: THE GENERATOR SHALL BE LOCATED AT A MINIMUM | | OF 5' FROM THE ADJACENT EXTERIOR WALL, OR VERIFY THE | | WALL HAS A 1-HR. FIRE RESISTANCE RATING- SECTION 4.1.4 | | (1) NFPA 54. A) INDICATE A MINIMUM 10' CLEARANCE FROM | | THE GENERATOR TO AIR INTAKES AND OPERABLE OPENINGS INTO | | THE BUILDING WILL BE MAINTAINED PER SECTION R303.5.1 | | FBC RES. | | | | 3) PLEASE ADJUST THE COST VALUE OF THE PROJECT TO | | INCLUDE INSTALLATION OF THE NEW GAS METER- SECTION | | 109.3 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2020-04-10 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-04-10 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-04-10 |
Time |
13:28 |
Sent To |
|
|
Notes |
2020-04-10 13:43:40 | 1) THE SURVEY SHOWS A NEW GAS METER BUT THE GAS | | APPLICATION STATES THAT THE GENERATOR WILL BE | | CONNECTING TO AN EXISTING GAS LINE. CLARIFY. IF A NEW | | METER IS TO BE INSTALLED THE DESCRIPTION OF WORK ON THE | | GAS SUB APPLICATION SHALL BE REVISED. WPB AMEND. TO FBC | | SEC. 107.2.1. | | 2) THE GAS PLAN CALLS OUT A TEE ON THE GAS LINE BUT NO | | TEE IS SHOWN. CLARIFY. | | 3) A SHUTOFF VALVE IS REQUIRED IMMEDIATELY UPSTREAM OF | | THE GAS REGULATOR. THE GAS RISER SHOWS IT DOWNSTREAM. | | 2017 FBC-FUEL GAS SEC.409.4. | | 4) SUBMIT MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR | | THE REGULATOR. 2017 FBC-FUEL GAS SEC. 410.1. | | 5) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE | | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | THAT SHOWS THE TYPE OF THE EXISTING APPLIANCES THE BTU | | LOAD OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE | | TO EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST | | LENGTH OF PIPING FROM THE POINT OF DELIVERY TO THE MOST | | REMOTE OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-06-19 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2020-06-19 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2020-06-12 |
Time |
09:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-06-09 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-06-09 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-05-05 |
Time |
14:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-04-21 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-04-21 |
Time |
14:23 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-04-07 |
Time |
11:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
N |
Date |
2020-06-17 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-06-17 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-06-17 |
Time |
08:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2020-05-20 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-05-20 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-05-20 |
Time |
15:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2020-04-10 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-04-10 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-04-10 |
Time |
10:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2020-06-17 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-06-17 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2020-06-17 |
Time |
08:25 |
Sent To |
|
|
Notes |
2020-06-17 08:58:57 | SIGNATURE APPROVAL FOR GENERATOR PAD SPECS. ALL OTHER | | PLANS BY CONTRACTOR. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2020-05-15 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-05-15 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-05-15 |
Time |
09:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-04-09 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2020-04-09 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2020-04-09 |
Time |
14:38 |
Sent To |
|
|
Notes |
2020-04-09 14:38:40 | SEE BUILDING PLAN REVIEW |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2020-06-19 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2020-06-19 |
Time |
|
Rev Time |
0.00 |
Received By |
rthermid |
Date |
2020-06-19 |
Time |
|
Sent To |
I |
|
Notes |
2020-06-19 09:07:19 | MECHANICAL EQUIPMENT MUST BE SETBACK AT LEAST 4 FEET | | FROM ALL PROPERTY LINES |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2020-06-09 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
2020-06-09 |
Time |
|
Sent To |
|
|
Notes |
2020-06-09 15:45:02 | *************************ZONING | | FAILED***************************** | | | | PLEASE PROVIDE THE SETBACKS FOR THE PROPOSED GENERATOR | | ON THE SURVEY. (REPEAT COMMENT) | | | | NOTE: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN | | FOUR FEET INTO A SETBACK. | | | | ALANA WOOTEN | | PLANNER | | PLANNING DIVISION | | 561-822-1449 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-04-21 |
|
|
Cont ID |
|
Sent By |
rfalcone |
Date |
2020-04-21 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
rfalcone |
Date |
2020-04-21 |
Time |
11:26 |
Sent To |
|
|
Notes |
2020-04-21 11:27:15 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 4/21/2020 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PROVIDE SETBACKS FROM THE GENERATOR AND PROPERTY | | LINES ON SURVEY. | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST | | THAT IT BE SENT TO YOU BY EMAILING [email protected] | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1442 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|