Plan Review Details - Permit 20040077
Plan Review Stops For Permit 20040077
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-05-15 Cont ID  
Sent By rmcphers Date 2020-05-15 Time 09:08 Rev Time 0.00
Received By rmcphers Date 2020-05-15 Time 09:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-09 Cont ID  
Sent By rmcphers Date 2020-04-09 Time 14:38 Rev Time 0.00
Received By rmcphers Date 2020-04-09 Time 14:03 Sent To  
Notes
2020-04-09 14:37:55GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ENGINEERING NEEDS TO BE SIGNED AND SEALED.
 ENGINEERING NEEDS TO BE ELECTRONICALLY SIGNED AND
 SEALED TO BE USED IN ELECTRONIC PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-04-16 Cont ID  
Sent By jpearson Date 2020-04-16 Time 12:58 Rev Time 0.00
Received By jpearson Date 2020-04-16 Time 11:01 Sent To  
Notes
2020-04-16 12:58:06PASSED BY JAKE LEAHY.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-06-17 Cont ID  
Sent By ccole Date 2020-06-17 Time 08:57 Rev Time 0.00
Received By ccole Date 2020-06-17 Time 08:05 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-05-21 Cont ID  
Sent By ccole Date 2020-05-21 Time 07:16 Rev Time 0.00
Received By ccole Date 2020-05-20 Time 15:30 Sent To  
Notes
2020-05-21 07:25:15 
 1ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT #20040077
 5/20/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING:
 A) INDICATE THE TOTAL DEVELOPED LENGTH OF THE GAS
 PIPING SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET.
 THIS INCLUDES THE EXISTING AND THE NEW PIPING-
 SECTIONS- G2413.4.1 & G2413.4.2 FBC RES. THE CURRENT
 ISOMETRIC DOES NOT SHOW THE PIPING RUN AND BRANCH LINES
 TO THE EXISTING APPLIANCES IN THE HOUSE. A THOROUGH
 REVIEW OF THE PIPE SIZING CANNOT BE ACCOMPLISHED
 WITHOUT A COMPLETE DRAWING AND THE TOTAL DEVELOPED
 LENGTH OF THE SYSTEM- SECTIONS G2412.4 G2412.8, G2413.1
 & G2413.3 FBC RES.
 B) SHOW THE SHUT OFF VALVE LOCATIONS AT THE NEW METER,
 AND AT THE NEW 2 PSI-11" WC REGULATOR- SECTION 2420.1
 FBC RES. NOTE: WHERE CONNECTED TO RIGID PIPING, A UNION
 SHALL BE INSTALLED WITH 1 FT OF EITHER SIDE OF AN MP
 REGULATOR- SECTION G2421.2 FBC RES
 C) INDICATE THE SENSUS REGULATOR MODEL NUMBERS AND
 ORIFICE SIZES ON THE DRAWING. PLEASE PROVIDE A COMPLETE
 SUBMITTAL FOR THE REGULATORS. THERE ARE NO TECHNICAL
 DATA SHEETS PROVIDED TO VERIFY ORIFICE SIZING BASED ON
 OUTLET PRESSURES AND BODY SIZES- SECTION G2421.1 FBC
 RES.
 D) THERE IS A 3/4" PIPE TEED OFF INTO SPACE POSSIBLY
 FOR A FUTURE APPLIANCE- PLEASE INDICATE THE TYPE OF
 PIPING AND CLARIFY IT'S PURPOSE- SECTION 107.2.1 WPB.
 E) IDENTIFY THE TYPE OF PIPING FROM THE METER TO THE
 NEW HOUSE REGULATOR, AND SHOW THE CUT LENGTH OF THE
 PIPE FROM THE 1" TEE TO THE NEW REGULATOR- SECTION
 G2413.4.1 & G2413.4.2
  
 2) SURVEY: THE GENERATOR SHALL BE LOCATED AT A MINIMUM
 OF 5' FROM THE ADJACENT EXTERIOR WALL, OR VERIFY THE
 WALL HAS A 1-HR. FIRE RESISTANCE RATING- SECTION 4.1.4
 (1) NFPA 54. A) INDICATE A MINIMUM 10' CLEARANCE FROM
 THE GENERATOR TO AIR INTAKES AND OPERABLE OPENINGS INTO
 THE BUILDING WILL BE MAINTAINED PER SECTION R303.5.1
 FBC RES.
  
 3) PLEASE ADJUST THE COST VALUE OF THE PROJECT TO
 INCLUDE INSTALLATION OF THE NEW GAS METER- SECTION
 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-04-10 Cont ID  
Sent By tklarge Date 2020-04-10 Time 13:44 Rev Time 0.00
Received By tklarge Date 2020-04-10 Time 13:28 Sent To  
Notes
2020-04-10 13:43:401) THE SURVEY SHOWS A NEW GAS METER BUT THE GAS
 APPLICATION STATES THAT THE GENERATOR WILL BE
 CONNECTING TO AN EXISTING GAS LINE. CLARIFY. IF A NEW
 METER IS TO BE INSTALLED THE DESCRIPTION OF WORK ON THE
 GAS SUB APPLICATION SHALL BE REVISED. WPB AMEND. TO FBC
 SEC. 107.2.1.
 2) THE GAS PLAN CALLS OUT A TEE ON THE GAS LINE BUT NO
 TEE IS SHOWN. CLARIFY.
 3) A SHUTOFF VALVE IS REQUIRED IMMEDIATELY UPSTREAM OF
 THE GAS REGULATOR. THE GAS RISER SHOWS IT DOWNSTREAM.
 2017 FBC-FUEL GAS SEC.409.4.
 4) SUBMIT MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR
 THE REGULATOR. 2017 FBC-FUEL GAS SEC. 410.1.
 5) THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF THE EXISTING APPLIANCES THE BTU
 LOAD OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE
 TO EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST
 LENGTH OF PIPING FROM THE POINT OF DELIVERY TO THE MOST
 REMOTE OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-19 Cont ID  
Sent By cpuell Date 2020-06-19 Time 11:13 Rev Time 0.00
Received By cpuell Date 2020-06-12 Time 09:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-09 Cont ID  
Sent By lmarchan Date 2020-06-09 Time 15:55 Rev Time 0.00
Received By lmarchan Date 2020-05-05 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-21 Cont ID  
Sent By lmarchan Date 2020-04-21 Time 14:23 Rev Time 0.00
Received By lmarchan Date 2020-04-07 Time 11:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-06-17 Cont ID  
Sent By ccole Date 2020-06-17 Time 08:57 Rev Time 0.00
Received By ccole Date 2020-06-17 Time 08:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-05-20 Cont ID  
Sent By ccole Date 2020-05-20 Time 16:14 Rev Time 0.00
Received By ccole Date 2020-05-20 Time 15:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-04-10 Cont ID  
Sent By tklarge Date 2020-04-10 Time 13:29 Rev Time 0.00
Received By tklarge Date 2020-04-10 Time 10:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-17 Cont ID  
Sent By ccole Date 2020-06-17 Time 08:57 Rev Time 0.00
Received By ccole Date 2020-06-17 Time 08:25 Sent To  
Notes
2020-06-17 08:58:57SIGNATURE APPROVAL FOR GENERATOR PAD SPECS. ALL OTHER
 PLANS BY CONTRACTOR.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-05-15 Cont ID  
Sent By rmcphers Date 2020-05-15 Time 09:09 Rev Time 0.00
Received By rmcphers Date 2020-05-15 Time 09:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-09 Cont ID  
Sent By rmcphers Date 2020-04-09 Time 14:38 Rev Time 0.00
Received By rmcphers Date 2020-04-09 Time 14:38 Sent To  
Notes
2020-04-09 14:38:40SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 3 Status P Date 2020-06-19 Cont ID  
Sent By rthermid Date 2020-06-19 Time   Rev Time 0.00
Received By rthermid Date 2020-06-19 Time   Sent To I
Notes
2020-06-19 09:07:19MECHANICAL EQUIPMENT MUST BE SETBACK AT LEAST 4 FEET
 FROM ALL PROPERTY LINES

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2020-06-09 Time   Rev Time 0.00
Received By   Date 2020-06-09 Time   Sent To  
Notes
2020-06-09 15:45:02*************************ZONING
 FAILED*****************************
  
 PLEASE PROVIDE THE SETBACKS FOR THE PROPOSED GENERATOR
 ON THE SURVEY. (REPEAT COMMENT)
  
 NOTE: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN
 FOUR FEET INTO A SETBACK.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-04-21 Cont ID  
Sent By rfalcone Date 2020-04-21 Time 11:26 Rev Time 0.00
Received By rfalcone Date 2020-04-21 Time 11:26 Sent To  
Notes
2020-04-21 11:27:15ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 4/21/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE SETBACKS FROM THE GENERATOR AND PROPERTY
 LINES ON SURVEY.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved