Plan Review Details - Permit 20040036
Plan Review Stops For Permit 20040036
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-05-29 Cont ID  
Sent By rmcdouga Date 2020-05-29 Time 09:56 Rev Time 0.00
Received By rmcdouga Date 2020-05-29 Time 10:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-05-26 Cont ID  
Sent By rmcdouga Date 2020-05-26 Time 12:19 Rev Time 0.00
Received By rmcdouga Date 2020-05-26 Time 12:02 Sent To  
Notes
2020-05-26 12:19:45PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) REPEAT COMMENT. THE CHART ON THE ENGINEERED DRAWINGS
 HAS A MAXIMUM WINDSPEED OF 163 MPH IN EXPOSURE D FOR
 THIS GENERATOR. A 170 MPH WIND SPEED IS REQUIRED. THE
 GENERATOR PAD ENGINEERING FOR THE 22 KW GENERAC
 GENERATOR WEIGHING 466 LBS DOES MEET THE 170 MPH WIND
 LOAD IN EXPOSURE D. THIS PROPERTY IS LOCATED IN
 EXPOSURE D. FBC-R301.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-20 Cont ID  
Sent By rmcdouga Date 2020-05-20 Time 14:08 Rev Time 0.00
Received By rmcdouga Date 2020-05-20 Time 13:22 Sent To  
Notes
2020-05-20 14:08:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEERING FOR THE 22 KW GENERAC
 GENERATOR WEIGHING 466 LBS DOES MEET THE 170 MPH WIND
 LOAD IN EXPOSURE D. THIS PROPERTY IS LOCATED IN
 EXPOSURE D. FBC-R301.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-16 Cont ID  
Sent By rmcdouga Date 2020-04-16 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2020-04-16 Time 11:33 Sent To  
Notes
2020-04-16 11:45:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROJECT IS LOCATED IN AN SPECIAL FLOOD HAZARD
 AREA , "AE". THE NEW GENERATOR IS REQUIRED TO BE
 LOCATED AT OR ABOVE 9' NAVD88. FBC R322 AND CITY FLOOD
 ORDINANCE
  
 2) SUBMIT ORIGINAL SIGNED AND SEALED WINDLOAD
 ENGINEERING FOR THE PROPOSED PREFABRICATED GENERATOR
 PAD. FBC R301.1

Review Stop E ELECTRICAL
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2020-06-10 Time   Rev Time 0.00
Received By jpearson Date 2020-06-10 Time 13:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-04-28 Cont ID  
Sent By jpearson Date 2020-04-28 Time 10:03 Rev Time 0.00
Received By jpearson Date 2020-04-28 Time 09:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-07-14 Cont ID  
Sent By medwards Date 2020-07-14 Time 13:36 Rev Time 0.00
Received By medwards Date 2020-07-14 Time 13:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-06-11 Cont ID  
Sent By medwards Date 2020-06-11 Time 11:25 Rev Time 0.00
Received By medwards Date 2020-06-11 Time 11:08 Sent To  
Notes
2020-06-11 11:26:031ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20040036
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE EXISTING GENERATOR INFORMATION I.E.:
 GENERATOR BTU?S, NAME BRAND AND MODEL. PLEASE SHOW THE
 BTU?S OF THE NEW GENERATOR. PLEASE SHOW LOCATION OF
 EXISTING GENERATOR. IF THE BTU?S OF THE NEW GENERATOR
 ARE LARGER THAN THE EXISTING GENERATOR, PLEASE PROVIDE
 A GAS LINE DIAGRAM OF THE COMPLETE GAS SYSTEM STARTING
 FROM THE METER AND INCLUDING ANY EXISTING GAS
 APPLIANCES. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-07-30 Cont ID  
Sent By shill Date 2020-07-30 Time 07:34 Rev Time 0.00
Received By shill Date 2020-06-29 Time 08:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-06-11 Cont ID  
Sent By lmarchan Date 2020-06-11 Time 11:42 Rev Time 0.00
Received By lmarchan Date 2020-05-27 Time 09:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-26 Cont ID  
Sent By rmcdouga Date 2020-05-26 Time 12:22 Rev Time 0.00
Received By rmcdouga Date 2020-05-21 Time 13:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-20 Cont ID  
Sent By rmcdouga Date 2020-05-20 Time 14:09 Rev Time 0.00
Received By rmcdouga Date 2020-05-08 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-08 Cont ID  
Sent By ajones Date 2020-05-08 Time 14:47 Rev Time 0.00
Received By ajones Date 2020-04-13 Time 12:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-07-14 Cont ID  
Sent By medwards Date 2020-07-14 Time 13:35 Rev Time 0.00
Received By medwards Date 2020-07-14 Time 13:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-11 Cont ID  
Sent By medwards Date 2020-06-11 Time 11:27 Rev Time 0.00
Received By medwards Date 2020-06-11 Time 11:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status N Date 2020-07-14 Cont ID  
Sent By medwards Date 2020-07-14 Time 13:36 Rev Time 0.00
Received By medwards Date 2020-07-14 Time 13:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status N Date 2020-05-29 Cont ID  
Sent By rmcdouga Date 2020-05-29 Time 09:57 Rev Time 0.00
Received By rmcdouga Date 2020-05-29 Time 09:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-05-26 Cont ID  
Sent By rmcdouga Date 2020-05-26 Time 12:21 Rev Time 0.00
Received By rmcdouga Date 2020-05-26 Time 12:21 Sent To  
Notes
2020-05-26 12:21:10THE GENERATOR PAD ENGINEERING DOES NOT HAVE THE
 ENGINEER'S DIGITAL SIGNATURE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-20 Cont ID  
Sent By rmcdouga Date 2020-05-20 Time 13:51 Rev Time 0.00
Received By rmcdouga Date 2020-05-20 Time 13:51 Sent To  
Notes
2020-05-20 13:53:28THE GENERATOR PAD ENGINEERING DOES NOT HAVE THE
 ENGINEER'S DIGITAL SIGNATURE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-28 Cont ID  
Sent By jpearson Date 2020-04-28 Time 10:03 Rev Time 0.00
Received By jpearson Date 2020-04-28 Time 10:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-07-29 Cont ID  
Sent By ajones Date 2020-07-29 Time 15:36 Rev Time 0.00
Received By ajones Date 2020-07-29 Time 15:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-05-08 Cont ID  
Sent By rfalcone Date 2020-05-08 Time 14:47 Rev Time 0.00
Received By ajones Date 2020-05-08 Time 14:47 Sent To  
Notes
***NONE***