Plan Review Details - Permit 20040032
Plan Review Stops For Permit 20040032
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-04-16 Cont ID  
Sent By cthroop Date 2020-04-16 Time 08:49 Rev Time 0.00
Received By cthroop Date 2020-04-10 Time 15:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-04 Cont ID  
Sent By cthroop Date 2020-04-04 Time 07:51 Rev Time 0.00
Received By cthroop Date 2020-04-04 Time 07:51 Sent To  
Notes
2020-04-04 08:23:422ND BUILDING REVIEW OPENED DUE TO COMMUNITY PLUS CRASH
 1ST REVIEW LOCKED. CT
  
 PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 PROPERTY INFO: YEAR BUILT - 1928 ZONING - SF 14-C3
 MULTI-FAMULY 2 UNITS FLOOD ZONE AE 6.0 FEET NAVD
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. SEPERATE PERMITS REQUIRED FOR EACH STRUCTURE.
 PROVIDE DETAILED SCOPE OF WORK FOR EACH STRUCTURE. BOTH
 STRUCTURES MAY BE INCLUDED IN ONE PLAN SET.
 VALUE MAY BE APPORTIONED ACCORDINGLY.
  
 PERMITS
 105.1 REQUIRED.
  
  
 2. DIGITAL SIGNATURE INVALID - FLORIDA PROFESSIONAL
 ENGINEERS MAY NOT SELF CERTIFY DIGITAL SIGATURES AND
 SEALS PER FS 668.003. SEE SIGNATURE REVIEW COMMENTS.
  
 A. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
 B. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 3. PROVIDE A COMPREHENSIVE DETAILED CODE COMPLIANT PLAN
 SET. INCLUDE COVER PAGE WITH PROJECT INFORMATION AND
 DESIGNER SIGNATURE TITLE BLOCK.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 4. PROVIDE SITE PLAN AND COPY OF MOST CURRENT SURVEY
 WITH LOCATION OF PROPOSED PRIVACY WALLS.
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 5. IDENTIFY FLOOR PLANS ON PAGE A-1 AS EXISTING OR
 PROPOSED. PROVIDE BOTH EXISTING AND PROPOSED FLOOR
 PLANS FOR EACH STRUCTURE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. WHICH STRUCTURE DO THE WINDOWS LISTED IN WINDOW
 SCHEDULE APPLY TO, IDENTIFY LOCATION OF WINDOWS ON PLAN
 NEXT THE APPROPRIATE OPENING.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. PROVIDE PRODUCT APPROVALS FOR PROPOSED WINDOWS.
 DESIGNER SHALL REVIEW AND APPROVE IN WRITING - PROF.
 SEAL NOT REQUIRED.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 8. PROVIDE ELEVATION VIEWS FOR MAIN REIDENCE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-04 Cont ID  
Sent By cthroop Date 2020-04-04 Time 07:42 Rev Time 0.00
Received By cthroop Date 2020-04-03 Time 15:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2020-04-13 Cont ID  
Sent By cthroop Date 2020-04-13 Time 08:09 Rev Time 0.00
Received By cthroop Date 2020-04-13 Time 06:55 Sent To  
Notes
2020-04-13 08:22:42PLAN REVIEW - ELECTRICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW - GARAGE/APARTMENT
  
 RESULTS: PENDING STAND ALONE ELECTRICAL PERMIT PER EOR.
 THE FOLLOWING COMMENTS ARE FOR REFERENCE ONLY.
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 SCOPE OF WORK INCLUDES THE ADDITION OF A NEW SINK AND
 COUNTERTOP, WASHER & DRYER AND RE-LOCATION OF BATHROOM
 VANITY ON 1ST FLOOR AND ADDITION OF NEW SINK AND
 COUNTERTOP ON 2ND FLOOR.
  
 1. ELECTRICAL PERMIT REQUIRED.
 PERMITS 105.1 REQUIRED.
  
 2. PROVIDE AN ELECTRICAL PLAN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PROVIDE AN ELECTRICAL RISER DIAGRAHM.
 RISER:
  
 PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1
  
 PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5;
 WPB FBC 107.2.1
  
  
 4. PROVIDE NEW PANEL SCHEDULE.
 PANEL SCHEDULE:
  
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 5. PROVIDE NEW LOAD CALCULATIONS.
 LOAD CALC.:
  
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE E3602.2
  
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT EXISTING PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10 & FBC RE E3404.3
  
 PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. NEC
 110.3, 110.9; FBC RE E3606.4
  
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24 & FBC RE E3606.4
  
 NAME AND SIGNATURE OF DESIGNER OF RECORD SEC 107.3.4.1
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-04-15 Cont ID  
Sent By fmittner Date 2020-04-15 Time 10:41 Rev Time 0.00
Received By fmittner Date 2020-04-15 Time 10:41 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-04-09 Cont ID  
Sent By fmittner Date 2020-04-09 Time 14:42 Rev Time 0.00
Received By fmittner Date 2020-04-09 Time 14:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-16 Cont ID  
Sent By cthroop Date 2020-04-16 Time 08:49 Rev Time 0.00
Received By cthroop Date 2020-04-10 Time 11:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-10 Cont ID  
Sent By shill Date 2020-04-10 Time 06:12 Rev Time 0.00
Received By shill Date 2020-04-02 Time 16:46 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2020-04-03 Cont ID  
Sent By cthroop Date 2020-04-03 Time 15:10 Rev Time 0.00
Received By cthroop Date 2020-04-03 Time 14:55 Sent To  
Notes
2020-04-03 15:13:27 
 NOTE: 2 STRUCTURES PERMITTED SEPERATELY. 20040032 &
 2004 0362.
 STRUCTURES ARE LOCATED IN A SFHA AE WITH BFE 6.0 NAVD
 AND DFE 8.0 NAVD. PAPA IMPROVEMENT VALE IS $402,522.
 FEMA 50% RULE = $201,261.
 20040032 VALUE = $60,000, 20040362 = $40,000. FIVE YEAR
 CUMULATIVE IMPROVEMENTS = $4,850. TOTAL IMPROVEMENT =
 $104,850
 THIS PROPERTY DOES NOT QUALIFY AS A SUBSTANTIAL
 IMPROVEMENT PER FEMA S/I REQUIREMENTS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-04-13 Cont ID  
Sent By cthroop Date 2020-04-13 Time 07:55 Rev Time 0.00
Received By cthroop Date 2020-04-13 Time 06:55 Sent To  
Notes
2020-04-13 08:05:15PLAN REVIEW - PLUMBING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW - GARAGE/APARTMENT
  
 RESULTS: PENDING STAND ALONE PLUMBING PERMIT PER EOR.
 THE FOLLOWING COMMENTS ARE FOR REFERENCE ONLY.
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 SCOPE OF WORK INCLUDES THE ADDITION OF A NEW SINK,
 WASHER DRAIN AND RE-CONFIGURE OF BATH GROUP ON 1ST
 FLOOR AND THE ADDITION OF A NEW SINK ON THE 2ND FLOOR.
  
 PLUMBING PERMIT REQUIRED
 PERMITS 105.1 REQUIRED.
  
 1. PROVIDE A PLUMBING PLAN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE A PLUMBING RISER DIAGRAHM.
 PLUMBING RISER - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION SECTION
 107.3.5.3 (12)
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-04-20 Cont ID  
Sent By shill Date 2020-04-20 Time 08:45 Rev Time 0.00
Received By shill Date 2020-04-20 Time 08:45 Sent To  
Notes
2020-04-20 08:46:17PAPER ORIGINAL RECEIVED
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-04-11 Cont ID  
Sent By cthroop Date 2020-04-11 Time 10:12 Rev Time 0.00
Received By cthroop Date 2020-04-10 Time 15:18 Sent To  
Notes
2020-04-11 10:13:46EOR SHALL SUBMIT HARD COPIES OF PLANS AT PERMIT.
  
 PLACED PRINT HOLD.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-03 Cont ID  
Sent By cthroop Date 2020-04-03 Time 15:46 Rev Time 0.00
Received By cthroop Date 2020-04-03 Time 15:45 Sent To  
Notes
2020-04-03 15:48:21PLAN REVIEW - DIGITAL SIGNATURES
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DIGITAL SIGNATURES ARE NOT ISSUED IN A MANNER WHICH IS
 ACCEPTABLE TO EITHER FBPA OR FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS. THIS TYPE OF SELF CERTIFICATION
 IS NOT INTENDED TO BE USED FOR PROFESSIONAL PURPOSES.
 THIRD PARTY CERTIFICATION IS REQUIRED.
  
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-04-13 Cont ID  
Sent By rthermid Date 2020-04-13 Time 12:20 Rev Time 0.00
Received By rthermid Date 2020-04-13 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-04-09 Cont ID  
Sent By fmittner Date 2020-04-09 Time 14:42 Rev Time 0.00
Received By fmittner Date 2020-04-09 Time 14:42 Sent To  
Notes
***NONE***