Plan Review Details - Permit 20031435
Plan Review Stops For Permit 20031435
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-28 Cont ID  
Sent By rmcphers Date 2020-05-28 Time 16:53 Rev Time 0.00
Received By rmcphers Date 2020-05-28 Time 16:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-29 Cont ID  
Sent By rmcphers Date 2020-04-29 Time 16:16 Rev Time 0.00
Received By rmcphers Date 2020-04-29 Time 16:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-06 Cont ID  
Sent By rmcphers Date 2020-04-06 Time 15:39 Rev Time 0.00
Received By rmcphers Date 2020-04-06 Time 15:06 Sent To  
Notes
2020-04-06 15:37:35POOL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS NEED TO BE ELECTRONICALLY SIGNED AND SEALED
 TO BE USED IN ELECTRONIC PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-06-05 Cont ID  
Sent By jpearson Date 2020-06-05 Time 12:35 Rev Time 0.00
Received By jpearson Date 2020-06-05 Time 11:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-06 Cont ID  
Sent By jpearson Date 2020-05-06 Time 12:23 Rev Time 0.00
Received By jpearson Date 2020-05-06 Time 10:51 Sent To  
Notes
2020-05-06 12:23:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE INDICATING
 SIZE OF SERVICE. NEC 215.5; WPB FBC 107.2.1 (NOT
 PROVIDED.)
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2 (NOT PROVIDED.)
 3. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-10 Cont ID  
Sent By jpearson Date 2020-04-10 Time 16:38 Rev Time 0.00
Received By jpearson Date 2020-04-07 Time 07:26 Sent To  
Notes
2020-04-10 16:38:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE INDICATING
 SIZE OF SERVICE. NEC 215.5; WPB FBC 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 3. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-04-02 Cont ID  
Sent By jpearson Date 2020-04-02 Time 13:15 Rev Time 0.00
Received By jpearson Date 2020-04-02 Time 13:15 Sent To  
Notes
2020-04-02 13:15:47RESULTS ENTERED BY JOHNPEARSON FOR REVIEW BY JERRY
 SMITH:
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20031435 140 MONROE DR
  
 1ST REVIEW
  
 GAS COMMENTS: GAS PLAN AND PERMIT REQUIRED
  
 1. POOL HEATER IS GAS. A GAS PLAN HAS NOT BEEN INCLUDED
 IN THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT
 BEEN PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND
 PLANS WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS, APPLIANCE/
 EQUIPMENT SPECIFICATIONS AND GAS RISER THAT REFLECT THE
 ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC
 SEC. 107.2.1.
 2. GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 3. GAS APPLIANCES SHALL BE LISTED AND LABELED PER
 FBC-FUEL GAS SEC. 301.3.
 4. A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS REQUIREMENTS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-16 Cont ID  
Sent By tklarge Date 2020-06-16 Time 08:02 Rev Time 0.00
Received By tklarge Date 2020-05-18 Time 13:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-14 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-22 Time 15:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-22 Cont ID  
Sent By lmarchan Date 2020-04-22 Time 11:59 Rev Time 0.00
Received By lmarchan Date 2020-04-01 Time 09:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-06-16 Cont ID  
Sent By tklarge Date 2020-06-16 Time 08:01 Rev Time 0.00
Received By tklarge Date 2020-06-16 Time 06:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-05-14 Cont ID  
Sent By jpearson Date 2020-05-14 Time 10:42 Rev Time 0.00
Received By jpearson Date 2020-05-14 Time 07:58 Sent To  
Notes
2020-05-14 07:58:50REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20031435 140 MONROE DR
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 COMMENT #1: CORRECTED
 COMMENT #2: SECOND REQUEST
 A.(RE: HYDRAULIC CALCULATIONS; PER WPB FBC 107.2. 1 AND
 APSP-7-2013, INCLUDE THE HEAD LOSS FOR THE POOL HEATER
 AS WELL AS THE VALVES AND FITTINGS.) TO BE CLEAR AS
 REQUIRED BY WPB FBC 107.2. 1 AND APSP-7-2013,
 CALCULATIONS SHALL INCLUDE THE HEAD LOSS FOR THE POOL
 HEATER AS WELL AS THE VALVES AND FITTINGS.
 B.(ADDITIONALLY, ALL EQUIPMENT SUBMITTALS SHALL BE
 CLEAR, EASILY READ AND SHALL INCLUDE ALL PERTINENT
 TECHNICAL INFORMATION INCLUDING BUT NOT LIMITED TO
 HYDRAULIC FLOW AND HEAD LOSS.) TO BE CLEAR AS REQUIRED
 BY WPB FBC 107.2. 1 AND APSP-7-2013, EQUIPMENT
 SUBMITTALS SHALL
 1.INCLUDE HYDRAULIC FLOW AND HEAD LOSS
 2.BE EASILY READ
 3.INDICATE SELECTED MODEL NUMBER IF THERE IS MORE THAN
 ONE LISTED IN SUBMITTAL
  
 COMMENT #3: CORRECTED
  
  
 GAS COMMENTS: GAS PLAN AND PERMIT REQUIRED
 POOL HEATER IS GAS. A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS, APPLIANCE/
 EQUIPMENT SPECIFICATIONS AND GAS RISER THAT REFLECT THE
 ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC
 SEC. 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS REQUIREMENTS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20031435 140 MONROE DR
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-02 Cont ID  
Sent By jpearson Date 2020-04-02 Time 13:18 Rev Time 0.00
Received By jpearson Date 2020-04-02 Time 13:18 Sent To  
Notes
2020-04-02 13:13:39RESULTS ENTERED BY JOHN PEARSON FOR REVIEW BY JERRY
 SMITH:
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20031435 140 MONROE DR
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. PLAN APPEARS TO BE A SCANNED COPY OF PAPER PLAN WITH
 ENGINEER?S STAMP. PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. THE DIGITAL SIGNATURE MUST INCLUDE
 THE STATEMENT "SIGNED AND SEALED" AS PER FAC
 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481
 2. RE: HYDRAULIC CALCULATIONS; PER WPB FBC 107.2. 1 AND
 APSP-7-2013, INCLUDE THE HEAD LOSS FOR THE POOL HEATER
 AS WELL AS THE VALVES AND FITTINGS. ADDITIONALLY, ALL
 EQUIPMENT SUBMITTALS SHALL BE CLEAR, EASILY READ AND
 SHALL INCLUDE ALL PERTINENT TECHNICAL INFORMATION
 INCLUDING BUT NOT LIMITED TO HYDRAULIC FLOW AND HEAD
 LOSS.
 3. RE: PUMP PERFORMANCE CURVE CHART ON PLAN SHEET 3 OF
 4; TEXT IN DESCRIPTION BLOCKS AT END OF EACH CURVE IS
 BLURRED. PER WPB FBC 107.2.1, PROVIDE CLEAN CHART.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS REQUIREMENTS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-05-28 Cont ID  
Sent By rmcphers Date 2020-05-28 Time 16:53 Rev Time 0.00
Received By rmcphers Date 2020-05-28 Time 16:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-29 Cont ID  
Sent By rmcphers Date 2020-04-29 Time 16:22 Rev Time 0.00
Received By rmcphers Date 2020-04-29 Time 16:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-06 Cont ID  
Sent By rmcphers Date 2020-04-06 Time 15:39 Rev Time 0.00
Received By rmcphers Date 2020-04-06 Time 15:39 Sent To  
Notes
2020-04-06 15:41:11DRAWINGS NEED TO BE ELECTRONICALLY SIGNED AND SEALED TO
 BE USED IN ELECTRONIC PLAN REVIEW.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-05-04 Cont ID  
Sent By rthermid Date 2020-05-04 Time   Rev Time 0.00
Received By rthermid Date 2020-05-04 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-04-15 Cont ID  
Sent By rthermid Date 2020-04-15 Time   Rev Time  
Received By rthermid Date 2020-04-15 Time   Sent To I
Notes
***NONE***