Plan Review Details - Permit 20031308
Plan Review Stops For Permit 20031308
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-30 Cont ID  
Sent By cthroop Date 2021-04-30 Time 13:02 Rev Time 0.00
Received By cthroop Date 2021-04-30 Time 09:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-29 Cont ID  
Sent By cthroop Date 2020-04-29 Time 09:39 Rev Time 0.00
Received By cthroop Date 2020-04-28 Time 11:18 Sent To  
Notes
2020-04-29 10:02:32PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REIDENTIAL ELEVATORS AND PLATFORM LIFTS SHALL COMPLY
 WITH ASME A17.1/CSA B44 AND FBC R 321.1
  
 R321.1ELEVATORS.
 WHERE PROVIDED, PASSENGER ELEVATORS, LIMITED-USE AND
 LIMITED-APPLICATION ELEVATORS OR PRIVATE RESIDENCE
 ELEVATORS SHALL COMPLY WITH ASME A17.1/CSA B44.
  
 2. ADVISORY ONLY -
 PROPOSED AREA OF CONSTRUCTION IS LOCATED IN A SPECIAL
 FLOOD HAZAR ARE WITH A CLASSIFICATION OF FLOOD ZONE AE
 WITH A BASE FLOOD ELEVATION OF 7.0 FEET NAVD.
 CONSTRUCTION SHALL COMPLY WITH FBC R 322.
  
 R322.1.3FLOOD-RESISTANT CONSTRUCTION.
 BUILDINGS AND STRUCTURES ERECTED IN AREAS PRONE TO
 FLOODING SHALL BE CONSTRUCTED BY METHODS AND PRACTICES
 THAT MINIMIZE FLOOD DAMAGE.
  
 3. PROVIDE THE FOLLOWING INFORMATION ON SITE PLAN.
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 4. DESCRIPTION OF WORK ON APPLICATION STATES LOCATION
 OF PROPOSED ELEVATOR IS LOCATED IN THE FRONT SIDE. SITE
 PLAN INDICATES LOCATION OF ELEVATOR IS LOCATED IN THE
 REAR SIDE.
 PLEASE CLARIFY.
  
 5. PROVIDE SOILS REPORT PER FBC 1803.1
  
 FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE
 CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 6. PROVIDE MANUFACTURERES INSTALLATION INSTRUCTIONS FOR
 PROPOSED ELEVATOR.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. PROVIDE PRODUCT APPROVAL/NOA FOR PROPOSED WINDOW
 LINTELS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE LINTEL SUBMITTALS.
  
 8. PROVIDE A STRUCTURAL DESIGN OF NEW WINDOW OPENINGS.
 INCLUDE ROUGH OPENING DEMENSIONS AND DESIGN PRESSURES
 FOR EACH OPENING.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 9. PLEASE REFERENCE PLAN PAGE SP1.0 SITE PLAN. CANNOT
 READ GENERAL NOTES AND SQUARE FOOTAGE CALCULATIONS.
 PLEASE UPLOAD NEW PLAN PAGE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-30 Cont ID  
Sent By cthroop Date 2021-04-30 Time 13:02 Rev Time 0.00
Received By cthroop Date 2021-04-30 Time 09:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-28 Cont ID  
Sent By cthroop Date 2020-04-28 Time 16:21 Rev Time 0.00
Received By cthroop Date 2020-04-28 Time 11:17 Sent To  
Notes
2020-04-28 16:25:26PLAN REVIEW - ELECTRICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A CODE COMPLIANT ELECTRICAL PLAN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE A NEW LOAD CALCULATION. INCLUDE ALL EXISTING
 AND PROPOSED LOADS.
 PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL LOADS
 FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS FOR
 THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2.
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-04-24 Cont ID  
Sent By fmittner Date 2020-04-24 Time 16:50 Rev Time 0.00
Received By fmittner Date 2020-04-24 Time 16:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-30 Cont ID  
Sent By cthroop Date 2021-04-30 Time 13:02 Rev Time 0.00
Received By cthroop Date 2021-04-19 Time 13:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-29 Cont ID  
Sent By lmarchan Date 2020-04-29 Time 10:55 Rev Time 0.00
Received By lmarchan Date 2020-04-13 Time 11:33 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2020-05-18 Cont ID  
Sent By lmarchan Date 2020-05-18 Time 14:18 Rev Time 0.00
Received By lmarchan Date 2020-04-29 Time 10:55 Sent To  
Notes
2020-05-18 14:18:26NO FEES DUE, SEE UPLOADED EMAIL. LEM
2020-04-29 10:55:354/29 NOTIFIED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-04-22 Cont ID  
Sent By medwards Date 2021-04-22 Time 16:18 Rev Time 0.00
Received By medwards Date 2021-04-22 Time 15:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-15 Cont ID  
Sent By medwards Date 2020-04-15 Time 16:50 Rev Time 0.00
Received By medwards Date 2020-04-15 Time 16:50 Sent To  
Notes
2020-04-15 16:54:18THERE IS AMECHANICAL SUB-PERMIT BUT THERE IS NO
 DOCUMENTATION FOR THIS PERMIT.
 1). PLEASE PROVIDE DRAWNGS SHOWING THIS MECHANICAL
 SYSTEM AND WORK. FBC FS 107.2.1
 2) PLEASE PROVIDE THE ENERGY SUMMARY AND THE MANUAL J
 CALCULATIONS FOR THIS PROJECT.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2020-04-29 Cont ID  
Sent By cthroop Date 2020-04-29 Time 09:10 Rev Time 0.00
Received By cthroop Date 2020-04-28 Time 16:13 Sent To  
Notes
2020-04-29 09:16:41PLAN REVIEW - NFIP
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: NOT APPLICABLE
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. AREA OF PROPOSED WORK IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA IDENTIFIED AS FLOOD ZONE AE WITH A BASE
 FLOOD ELVATION OF 7.0 FEET NAVD.
  
 2. BASED ON THE IMPROVEMENT VALUE OF $2,455,357.00 AND
 A FIVE YEAR CUMULATIVE VALUE OF IMPROVEMENTS OF APPRX.
 $180,000.00 THIS PROJECT IS NOT CLASSIFIED AS A
 SUBSTANTIAL IMPROVEMENT PER FEMA P-758, SECTION 4.
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-04-15 Cont ID  
Sent By lcrespo Date 2020-04-15 Time 17:24 Rev Time 0.00
Received By lcrespo Date 2020-04-15 Time 16:30 Sent To  
Notes
2020-04-15 17:25:13NO PLUMBING WORK DONE ON THE SCOPE OF WORK.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-04-30 Cont ID  
Sent By cthroop Date 2021-04-30 Time 13:02 Rev Time 0.00
Received By cthroop Date 2021-04-30 Time 09:24 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-04-29 Cont ID  
Sent By cthroop Date 2020-04-28 Time 16:21 Rev Time 0.00
Received By cthroop Date 2020-04-28 Time 11:18 Sent To  
Notes
2020-04-29 10:05:49PLAN REVIEW - ROOFING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVAL/NOA FOR ROOF TILE ADHESIVE.
 PLAN PAGE LABLED NOAICPCO ADHESIVES IS A SECOND COPY OF
 THE PERMIT APPLICATION.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-30 Cont ID  
Sent By cthroop Date 2021-04-30 Time 13:02 Rev Time 0.00
Received By cthroop Date 2021-04-30 Time 09:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-29 Cont ID  
Sent By cthroop Date 2020-04-29 Time 10:37 Rev Time 0.00
Received By cthroop Date 2020-04-28 Time 11:17 Sent To  
Notes
2020-04-29 10:42:23PLAN REVIEW - DIGITAL SIGNATURE AND SEAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DIGITAL SIGNATURES AND SEALS
  
 DESIGN PROFESSIONALS
  
 DIGITAL SIGNATURE IS NOT ISSUED IN A MANNER WHICH IS
 ACCEPTABLE TO EITHER FBPA OR FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS. THIS TYPE OF SELF-CERTIFICATION
 IS NOT INTENDED TO BE USED FOR PROFESSIONAL PURPOSES.
 THIRD PARTY CERTIFICATION IS REQUIRED.
  
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
 4. MULTIPLE PLAN PAGES ARE MISLABLED. USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT.
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-04-24 Cont ID  
Sent By fmittner Date 2020-04-24 Time 16:46 Rev Time 0.00
Received By fmittner Date 2020-04-24 Time 16:46 Sent To  
Notes
***NONE***