Plan Review Details - Permit 20031297
Plan Review Stops For Permit 20031297
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-07 Cont ID  
Sent By cthroop Date 2020-08-07 Time 11:52 Rev Time 0.00
Received By cthroop Date 2020-08-07 Time 10:24 Sent To  
Notes
2020-08-07 11:53:17DEFERRAL: PRODUCT APPROVALS FOR WINDOWS AND DOORS SHALL
 BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-04 Cont ID  
Sent By cthroop Date 2020-05-04 Time 14:51 Rev Time 0.00
Received By cthroop Date 2020-04-30 Time 10:40 Sent To  
Notes
2020-05-04 14:52:33PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE HAS BEEN ADJUSTED FROM $100,000 TO $136,362
 PER THE ICC BUILDING VALUATION TABLES.
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS.
  
 2. PROVIDE A SOILS REPORT.
 FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE
 CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 3. REFERENCE PLAN PAGE A2. DOOR WIDTH ON DOOR SCHEDULE
 IS STATED IN INCHES.
 PLEASE CLAIFY.
  
 4. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-07 Cont ID  
Sent By cthroop Date 2020-08-07 Time 12:05 Rev Time 0.00
Received By cthroop Date 2020-08-07 Time 10:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-05-04 Cont ID  
Sent By cthroop Date 2020-05-04 Time 14:59 Rev Time 0.00
Received By cthroop Date 2020-04-30 Time 10:40 Sent To  
Notes
2020-05-04 15:46:54PLAN REVIEW - ELECTRICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REMOVED - CT
  
 2. LUMINAIRES INSTALLED IN SHOWER AREAS REQUIRED TO BE
 VAPOR PROOF.
  
 VAPOR PROOF LIGHTING
 E4003.9 WET OR DAMP LOCATIONS.
 LUMINAIRES INSTALLED IN WET OR DAMP LOCATIONS SHALL BE
 INSTALLED SO THAT WATER CANNOT ENTER OR ACCUMULATE IN
 WIRING COMPARTMENTS, LAMP HOLDERS OR OTHER ELECTRICAL
 PARTS. ALL LUMINAIRES INSTALLED IN WET LOCATIONS SHALL
 BE MARKED SUITABLE FOR WET LOCATIONS. ALL LUMINAIRES
 INSTALLED IN DAMP LOCATIONS SHALL BE MARKED SUITABLE
 FOR WET LOCATIONS OR SUITABLE FOR DAMP LOCATIONS.
 (410.10)
  
 INCLUDE VP NEXT TO THE SYMBOL AT THE VAPOR PROOF
 FIXTURE IN THE SHOWER AREA.
  
 3. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR THE SUB-PANELS AT THE
 PROPOSED ADDITION. NEC 225.31, 225.32
  
 4. REMOVED - CT
  
 5. REMOVED - CT
  
 6. A NOTICE SHALL BE POSTED ON THE ELECTRIC SERVICE
 PANEL INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER
 IS LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16-POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD PER R403.3.6.
  
 7. THE OUTLET SHOWN BETWEEN THE TWO MASTER BATH BASIN
 SHALL BE GFCI PROTECTED.
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2020-12-02 Cont ID  
Sent By cthroop Date 2020-12-02 Time 07:52 Rev Time 0.00
Received By cthroop Date 2020-12-02 Time 07:52 Sent To  
Notes
2020-12-02 07:53:15PROVISO: A SEPERATE GAS PERMIT IS REQUIRED. CT

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-08-07 Cont ID  
Sent By abelisle Date 2020-08-05 Time 18:58 Rev Time 0.00
Received By abelisle Date 2020-08-05 Time 18:09 Sent To  
Notes
2020-08-07 16:40:188/5/2020 1ST GAS REVIEW **DENIED** WITH COMMENTS NOTE -
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 1- I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND
 THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF
 ANY GAS AT THIS ADDRESS.SINCE THERE IS NO RECORD OF A
 PERMIT FOR THE GAS, THE EXISTING GAS LINES SHALL
 CONSIDERED AS NEW. WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 2 -SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
  
 3- TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4- SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR
 2017 FBC FUEL GAS RES. SEC. G2408.1.
  
 5- A GAS GRILL IS LABELED FOR OUTSIDE USE AND IT SEEMS
 TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE
 MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD,
 2017 FBC FG SEC.G2408.1.
  
 6- THERE ARE SECTIONS OF PRINTING ON THE GAS RISER
 DRAWING THAT ARE ILLEGIBLE. SUBMIT A CLEAR AND LEGIBLE
 SHEET THAT REFLECTS THE SCOPE OF WORK BEING DONE. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 7- REGULATORS SHALL HAVE A UNION INSTALLED WITHIN 1
 FOOT OF EITHER SIDE OF THE REGULATOR FBC FG 410.2
  
 8-FUTURE POOL HEATER AND FIRE BOWL SHALL HAVE A GAS
 SHUT OFF VALVE, GAS REGULATOR, HARD CAP, AND A UNION
 INSTALLED WITHIN ONE FOOT OF THE REGULATOR. FBC FG
 410.2
  
 9-SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS DRYER. THE GAS DRYER SHALL BE LISTED AND LABELED
 PER THE 2017 FBC FUEL GAS SEC.301.3 OR 2017 FBC FUEL
 GAS RES. SEC. G2404.3. THE MANUFACTURER'S
 SPECIFICATIONS SHALL NOTE THE CFM'S THAT ARE BEING
 EXHAUSTED BY THE DRYER.
  
 10- PLEASE INDICATE THE EDH OF THE CSST ON THE GAS
 ISOMETRIC
  
 11-SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FGC
 SEC.304.9.3 OR 2017 FBC R G2407.9.3. COMBINED
 COMBUSTION AIR AND VENTILATION AIR SYSTEM
  
 12-SUBMIT A COPY OF A HOUSE PLAN SHOWING THE LOCATION
 OF THE TANKLESS WATER HEATER AND THE LOCATION AND
 DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION
 TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER
 SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND DRAWN. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 13- WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-04-30 Cont ID  
Sent By cthroop Date 2020-04-30 Time 16:32 Rev Time 0.00
Received By cthroop Date 2020-04-30 Time 11:39 Sent To  
Notes
2020-04-30 16:33:58GAS PERMIT REQUIRED. PROVIDE CODE COMPLIANT GAS PLAN,
 RISER DIAGRAHM AND EQUIPMENT SPECIFICATIONS. CT

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-04-24 Cont ID  
Sent By fmittner Date 2020-04-24 Time 16:46 Rev Time 0.00
Received By fmittner Date 2020-04-24 Time 16:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-02 Cont ID  
Sent By cthroop Date 2020-12-02 Time 07:54 Rev Time 0.00
Received By cthroop Date 2020-11-13 Time 11:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-07 Cont ID  
Sent By ccarvaja Date 2020-08-07 Time 18:43 Rev Time 0.00
Received By ccarvaja Date 2020-07-22 Time 09:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-04 Cont ID  
Sent By cthroop Date 2020-05-04 Time 15:46 Rev Time 0.00
Received By cthroop Date 2020-04-17 Time 16:48 Sent To  
Notes
2020-04-20 16:48:47SAMANTHA RECEIVED E-MAIL WITH PDF'S.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-10-06 Cont ID  
Sent By lmarchan Date 2020-10-06 Time 07:37 Rev Time 0.00
Received By lmarchan Date 2020-10-06 Time 07:37 Sent To  
Notes
2020-10-06 07:37:19RECEIPT MU-2020-37321 - $1043.60 - PAID

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-04-30 Cont ID  
Sent By cthroop Date 2020-04-30 Time 16:28 Rev Time 0.00
Received By cthroop Date 2020-04-30 Time 10:39 Sent To  
Notes
2020-04-30 16:28:52IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-07-31 Cont ID  
Sent By hmoser Date 2020-07-31 Time 14:35 Rev Time 0.00
Received By hmoser Date 2020-07-31 Time 14:12 Sent To  
Notes
2020-07-31 14:44:00PASS PROVISO
 HAVE MANUFACTURE SPECIFICATIONS FOR GAS GRILL HOOD ON
 SITE AT INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-22 Cont ID  
Sent By medwards Date 2020-04-22 Time 15:02 Rev Time 0.00
Received By medwards Date 2020-04-22 Time 14:04 Sent To  
Notes
2020-04-22 15:02:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20031297
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 SHEET A5 HAS A DETAIL OF A HOOD OVER THE GRILL IN THE
 PORCH AREA. PLEASE PROVIDE SPECS ON THE GRILL AND THE
 HOOD ON THE MECHANICAL SHEETS. PLEASE SHOW THE
 TERMINATION POINT FOR THE HOOD. FBC FS 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-12-02 Cont ID  
Sent By cthroop Date 2020-12-02 Time 07:52 Rev Time 0.00
Received By cthroop Date 2020-12-02 Time 06:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-08-07 Cont ID  
Sent By cthroop Date 2020-08-07 Time 12:01 Rev Time 0.00
Received By cthroop Date 2020-08-05 Time 18:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-04-30 Cont ID  
Sent By cthroop Date 2020-04-30 Time 16:34 Rev Time 0.00
Received By cthroop Date 2020-04-30 Time 10:39 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2020-08-07 Cont ID  
Sent By cthroop Date 2020-08-07 Time 11:59 Rev Time 0.00
Received By cthroop Date 2020-08-07 Time 10:24 Sent To  
Notes
2020-08-07 12:00:26ROOFING SUB-PERMIT REQUIRED. SUBMIT PRODUCT APPROVALS
 FOR REVIEW PRIOR TO INSTALLATION. CT

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-04-30 Cont ID  
Sent By cthroop Date 2020-04-30 Time 16:28 Rev Time 0.00
Received By cthroop Date 2020-04-30 Time 10:40 Sent To  
Notes
2020-04-30 16:32:45PLAN REVIEW - ROOFING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
  
 PERMITS
 105.1 REQUIRED.
  
  
 2. PROVIDE PRODUCT APPROVALS FOR THE PROPOSED ROOFING
 SYSTEM COMPONENTS. DESIGNER SHALL REVIEW AND APPROVE IN
 WRITING - NO SEAL REQUIRED.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-07 Cont ID  
Sent By cthroop Date 2020-08-07 Time 12:00 Rev Time 0.00
Received By cthroop Date 2020-08-07 Time 10:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-21 Cont ID  
Sent By jgomez Date 2020-04-20 Time 17:00 Rev Time 0.00
Received By shill Date 2020-04-20 Time 16:51 Sent To  
Notes
2020-07-07 07:38:22ORIGINAL SOILS REPORT RECEIVED, SCANNED AND UPLOADED,
 ROUTED TO STORAGE
  
2020-04-21 15:46:48DIGITALLY SIGNED PDFS PROVIDED; SEE SIGNATURE FOLDER
  
  
2020-04-20 17:00:50SAMANTHA RECEIVED E-MAIL WITH PDF'S. THESE DRAWINGS
 WERE UPLOADED TO PROJECTDOX. DRAWINGS DON'T HAVE ANY
 SIGNATURE. JG.
 NEED DIGITAL SIGNATURE OF HARD COPY OF ORIGINALS.
 COORDINATE WITH SAMANTHA. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-04-24 Cont ID  
Sent By fmittner Date 2020-04-24 Time 16:45 Rev Time 0.00
Received By fmittner Date 2020-04-24 Time 16:45 Sent To  
Notes
***NONE***