Plan Review Details - Permit 20031229
Plan Review Stops For Permit 20031229
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-06-22 Cont ID  
Sent By rmcphers Date 2020-06-22 Time 09:45 Rev Time 0.00
Received By rmcphers Date 2020-06-22 Time 09:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-05-29 Cont ID  
Sent By rmcphers Date 2020-05-29 Time 16:29 Rev Time 0.00
Received By rmcphers Date 2020-05-29 Time 16:29 Sent To  
Notes
2020-05-29 16:35:10GENERATOR FOUNDATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING BY DONALD J. NUELLE P.E. NEEDS TO BE
 DIGITALLY SIGNED AND SEALED - NEEDS TO SHOW THE WIND
 DESIGN CRITERIA FBC 1603.1.4 AND SHOW THE SLAB WIDTH
 AND LENGTH DIMENSIONS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-01 Cont ID  
Sent By rmcphers Date 2020-05-01 Time 16:31 Rev Time 0.00
Received By rmcphers Date 2020-05-01 Time 16:31 Sent To  
Notes
2020-05-01 16:33:29GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE SIGNED AND SEALED TIEDOWN DETAILS
 FROM AN ARCHITECT OR ENGINEER TO COMPLY WITH WIND LOADS
 PER FBC R301.2.1
 2) PLEASE SHOW THE WIND DESIGN CRITERIA USED PER FBC
 R301.2.1.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By rmcphers Date 2020-03-31 Time 16:46 Rev Time 0.00
Received By rmcphers Date 2020-03-31 Time 16:27 Sent To  
Notes
2020-03-31 16:46:08GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE SIGNED AND SEALED TIEDOWN DETAILS
 FROM AN ARCHITECT OR ENGINEER TO COMPLY WITH WIND LOADS
 PER FBC R301.2.1
 2) PLEASE SHOW THE WIND DESIGN CRITERIA USED PER FBC
 R301.2.1.1
 3) PLEASE PROVIDE FOUNDATION DETAILS.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-07-15 Cont ID  
Sent By jleahy Date 2020-07-15 Time 08:51 Rev Time 0.00
Received By jleahy Date 2020-07-15 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-06-01 Cont ID  
Sent By jleahy Date 2020-06-01 Time 11:30 Rev Time 0.00
Received By jleahy Date 2020-06-01 Time 11:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-13 Cont ID  
Sent By jleahy Date 2020-05-13 Time 09:53 Rev Time 0.00
Received By jleahy Date 2020-05-13 Time 09:46 Sent To  
Notes
2020-05-13 09:58:23PLAN NEEDS TO BE SIGNED
  
 PLAN IS REQUIRED TO BE SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; FBC
 107.2.1
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-02 Cont ID  
Sent By jleahy Date 2020-04-02 Time 10:38 Rev Time 0.00
Received By jleahy Date 2020-03-31 Time 17:07 Sent To  
Notes
2020-04-01 16:05:08ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO ELECTRICAL PLANS SUBMITTED.
  
 2) RISER DIAGRAM REQUIRED FOR SERVICE PROVIDE RISER
 DIAGRAM OF EXISTING SERVICE. NEC 215.5; FBC 107.2.1
  
 3) PROVIDE LOAD CALCULATION. PROVIDE ACCURATE LOAD
 CALCULATION INCLUDING ALL LOADS. NEC 220; FBC RE3602.3
  
 4) HAVE NO IDEA WHAT SIZE GENERATOR IS BEING INSTALLED,
 TRANSFER SWITCH (SE RATED OR NOT).
  
 5) DEPENDING ON THE SIZE OF THE GENERATOR AND TRANSFER
 SWITCH VALUE MAY BE A QUESTION (YOU CAN INCLUDE
 CONTRACT ON RESUBMITAL IF YOU LIKE.)
  
 6) SUMITTED PLANS SHALL BE SIGNED BY THE ELECTRICAL
 QUALIFIER. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR
 QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
  
  

Review Stop G GAS REVIEW
Rev No 7 Status P Date 2020-08-04 Cont ID  
Sent By lcrespo Date 2020-08-04 Time 13:05 Rev Time 0.00
Received By lcrespo Date 2020-08-04 Time 13:05 Sent To  
Notes
2020-08-04 13:06:1108/04/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 6 Status F Date 2020-07-20 Cont ID  
Sent By ccole Date 2020-07-20 Time 10:44 Rev Time 0.00
Received By ccole Date 2020-07-20 Time 07:36 Sent To  
Notes
2020-07-20 10:47:325TH REVIEW FBC-2017 RES. FUEL GAS
 PERMIT #20031229
 7/20/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE PREVIOUS REVIEWS LISTED BELOW HAVE
 NOT BEEN ADDRESSED ON THE PLANS AND NO NARRATIVE
 RESPONSE WAS PROVIDED.
 ON THE DATE OF THIS REVIEW- 7/20/17- I CONTACTED THE
 COMPANY BY TELEPHONE, AND THE COMPANY HAS AGREED TO
 PROVIDE THE CORRECTIONS ON THE NEXT SUBMITTAL.
  
 1) THE SUBMITTED GAS RISER DRAWING BY C & C DIVERSIFIED
 SERVICES WAS ORIGINALLY SUBMITTED UNDER PERMIT 19040921
 WHICH IS STILL AN OPEN PERMIT. TO DATE NO GAS
 INSPECTIONS HAVE BEEN PERFORMED UNDER THAT PERMIT. IF C
 & C DIVERSIFIED SERVICES TO BE THE SUB-CONTRACTOR UNDER
 THIS GENERATOR PERMIT, THEN A NEW SUB-PERMIT IS
 REQUIRED. IF MITCHELL MECHANICAL & ELECTRICAL REMAINS
 THE SUB THEN A NEW GAS RISER PLAN SHALL BE SUBMITTED
 AND SIGNED BY MITCHELL MECHANICAL AND ELECTRICAL-
 SECTIONS 105.3 AND 107.2.1 WPB.
  
 2) AS NOTED IN THE PREVIOUS REVIEW, THE SUBMITTED
 GENERATOR SPECS INDICATE THE GENERATOR HAS A GAS LOAD
 OF 1,202,000 BTUH AT 100% CAPACITY. PLEASE CORRECT THE
 LOAD ON THE NEW RISER DRAWING- SECTION 107.2.1 WPB.
  
 3) AS NOTED IN THE PREVIOUS REVIEW, THE SUBMITTED RISER
 DRAWING SHOWS A NEW REGULATOR FOR THE INTERIOR
 GAS-FIRED APPLIANCES WITH A GAS LOAD ESTIMATED AT
 150,000 BTUH. THE NEW RISER SHALL SHOW THE LENGTH OF
 THE SYSTEM FROM THE REGULATOR TO THE MOST REMOTE
 APPLIANCE- SECTION G2413.4.1 FBC RES; SHOW THE DIAMETER
 OF THE NEW 3' PIPE FROM THE METER TO THE REGULATOR, AND
 INDICATE THE SIZING TABLE USED FOR THE SYSTEM- SECTION
 2413.3 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2020-07-01 Cont ID  
Sent By ccole Date 2020-07-01 Time 16:00 Rev Time 0.00
Received By ccole Date 2020-07-01 Time 10:13 Sent To  
Notes
2020-07-01 16:01:294TH REVIEW FBC-2017 RES. FUEL GAS
 PERMIT #20031229
 6/16/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE PREVIOUS REVIEWS LISTED BELOW HAVE
 NOT BEEN ADDRESSED ON THE PLANS AND NO NARRATIVE
 RESPONSE WAS PROVIDED.
  
 1) THE SUBMITTED GAS RISER DRAWING BY C & C DIVERSIFIED
 SERVICES WAS ORIGINALLY SUBMITTED UNDER PERMIT 19040921
 WHICH IS STILL AN OPEN PERMIT. TO DATE NO GAS
 INSPECTIONS HAVE BEEN PERFORMED UNDER THAT PERMIT. IF C
 & C DIVERSIFIED SERVICES TO BE THE SUB-CONTRACTOR UNDER
 THIS GENERATOR PERMIT, THEN A NEW SUB-PERMIT IS
 REQUIRED. IF MITCHELL MECHANICAL & ELECTRICAL REMAINS
 THE SUB THEN A NEW GAS RISER PLAN SHALL BE SUBMITTED
 AND SIGNED BY MITCHELL MECHANICAL AND ELECTRICAL-
 SECTIONS 105.3 AND 107.2.1 WPB.
  
 2) AS NOTED IN THE PREVIOUS REVIEW, THE SUBMITTED
 GENERATOR SPECS INDICATE THE GENERATOR HAS A GAS LOAD
 OF 1,202,000 BTUH AT 100% CAPACITY. PLEASE CORRECT THE
 LOAD ON THE NEW RISER DRAWING- SECTION 107.2.1 WPB.
  
 3) AS NOTED IN THE PREVIOUS REVIEW, THE SUBMITTED RISER
 DRAWING SHOWS A NEW REGULATOR FOR THE INTERIOR
 GAS-FIRED APPLIANCES WITH A GAS LOAD ESTIMATED AT
 150,000 BTUH. THE NEW RISER SHALL SHOW THE LENGTH OF
 THE SYSTEM FROM THE REGULATOR TO THE MOST REMOTE
 APPLIANCE- SECTION G2413.4.1 FBC RES; SHOW THE DIAMETER
 OF THE NEW 3' PIPE FROM THE METER TO THE REGULATOR, AND
 INDICATE THE SIZING TABLE USED FOR THE SYSTEM- SECTION
 2413.3 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2020-06-16 Cont ID  
Sent By ccole Date 2020-06-16 Time 14:39 Rev Time 0.00
Received By ccole Date 2020-06-16 Time 12:43 Sent To  
Notes
2020-06-16 14:40:453RD REVIEW FBC-2017 RES. FUEL GAS
 PERMIT #20031229
 6/16/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED GAS RISER DRAWING BY C & C DIVERSIFIED
 SERVICES WAS ORIGINALLY SUBMITTED UNDER PERMIT 19040921
 WHICH IS STILL AN OPEN PERMIT. TO DATE NO GAS
 INSPECTIONS HAVE BEEN PERFORMED UNDER THAT PERMIT. IF C
 & C DIVERSIFIED SERVICES TO BE THE SUB-CONTRACTOR UNDER
 THIS GENERATOR PERMIT, THEN A NEW SUB-PERMIT IS
 REQUIRED. IF MITCHELL MECHANICAL & ELECTRICAL REMAINS
 THE SUB THEN A NEW GAS RISER PLAN SHALL BE SUBMITTED
 AND SIGNED BY MITCHELL MECHANICAL AND ELECTRICAL-
 SECTIONS 105.3 AND 107.2.1 WPB.
  
 2) AS NOTED IN THE PREVIOUS REVIEW, THE SUBMITTED
 GENERATOR SPECS INDICATE THE GENERATOR HAS A GAS LOAD
 OF 1,202,000 BTUH AT 100% CAPACITY. PLEASE CORRECT THE
 LOAD ON THE NEW RISER DRAWING- SECTION 107.2.1 WPB.
  
 3) AS NOTED IN THE PREVIOUS REVIEW, THE SUBMITTED RISER
 DRAWING SHOWS A NEW REGULATOR FOR THE INTERIOR
 GAS-FIRED APPLIANCES WITH A GAS LOAD ESTIMATED AT
 150,000 BTUH. THE NEW RISER SHALL SHOW THE LENGTH OF
 THE SYSTEM FROM THE REGULATOR TO THE MOST REMOTE
 APPLIANCE- SECTION G2413.4.1 FBC RES; SHOW THE DIAMETER
 OF THE NEW 3' PIPE FROM THE METER TO THE REGULATOR, AND
 INDICATE THE SIZING TABLE USED FOR THE SYSTEM- SECTION
 2413.3 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2020-06-04 Cont ID  
Sent By ccole Date 2020-06-04 Time 12:24 Rev Time 0.00
Received By ccole Date 2020-06-04 Time 12:20 Sent To  
Notes
2020-06-04 12:25:552ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT #20031229
 6/4/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOPT
 ADDRESSED AND STILL EXIST- PLEASE COMPLY.
  
 1) GAS RISER DRAWING:
 A) INDICATE THE TOTAL BTUH LOAD OF THE ENTIRE SYSTEM
 INCLUDING THE EXISTING, NEW, AND FUTURE GAS APPLIANCES
 AND EQUIPMENT- SECTIONS 2412.4, 2412.8, 2413.2, &
 2413.3 FBC RES. PLEASE NOTE THAT THE GENERATOR SPECS
 INDICATE THE GENERATOR HAS A GAS LOAD OF 1,202,000 BTUH
 AT 100% CAPACITY.
 B) INDICATE THE TOTAL DEVELOPED LENGTH OF THE GAS
 PIPING SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET.
 THIS INCLUDES THE EXISTING AND THE NEW PIPING-
 SECTIONS- G2413.4.1 & G2413.4.2 FBC RES. A THOROUGH
 REVIEW OF THE PIPE SIZING CANNOT BE ACCOMPLISHED
 WITHOUT THE TOTAL DEVELOPED LENGTH OF THE SYSTEM-
 SECTION 107.2.1 WPB.
 C) THE SUBMITTED SPECS FOR THE B31 REGULATORS DO NOT
 PROVIDE PERFORMANCE DATA IN LBS. PLEASE INDICATE THE
 STEP-DOWN PRESSURES IN PSI OR INCHES W.C. INDICATE THE
 MODEL NUMBERS OF THE REGULATORS AND ORIFICE SIZES ON
 THE RISER, AND ALSO MARK OR HIGHLIGHT IN THE SPECS THE
 MODEL NUMBER AND ORIFICE SIZES AS SHOWN IN THE
 PERFORMANCE DATA TABLES- SECTION G2421.1 FBC RES.
 D) SHOW THE SHUT OFF VALVE LOCATIONS AT THE METER, AND
 AT THE STEP-DOWN REGULATORS- SECTION 2420.1 FBC RES.
 E) NOTE: WHERE CONNECTED TO RIGID PIPING, A UNION SHALL
 BE INSTALLED WITH 1 FT OF EITHER SIDE OF AN MP
 REGULATOR- SECTION G2421.2 FBC RES.
  
 2) GAS WATER HEATERS:
 A) PROVIDE A BASIC FLOOR PLAN DRAWING SHOWING THE
 INSTALLATION LOCATIONS OF THE NEW TANKLESS WATER
 HEATERS- SECTION 107.2.1 WPB.
 B) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS- SECTION G2408.1 FBC RES.
 C) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO THE
 WATER HEATERS AND PROVIDE CALCULATIONS- SECTION G2407.1
 FBC RES.
 D) PROVIDE GAS VENTING DIAGRAMS SHOWING THE TYPES AND
 SIZES OF VENTS, VENT RUNS THROUGH AND OUT OF THE
 BUILDING, TERMINATION LOCATIONS, HEIGHTS ABOVE THE
 ROOF, AND ANCHORING DETAILS. SUBMIT SPECIFICATIONS FOR
 ALL THE VENT FLUES, CONNECTORS, AND TERMINATION CAPS-
 SECTIONS 2426.1 THROUGH 2426.7 FBC RES.
  
 3) SURVEY: THE GENERATOR SHALL BE LOCATED AT A MINIMUM
 OF 5' FROM THE ADJACENT EXTERIOR WALL, OR VERIFY THE
 WALL HAS A 1-HR. FIRE RESISTANCE RATING- SECTION 4.1.4
 (1) NFPA 54. A) INDICATE A MINIMUM 10' CLEARANCE FROM
 THE GENERATOR TO AIR INTAKES AND OPERABLE OPENINGS INTO
 THE BUILDING WILL BE MAINTAINED PER SECTION R303.5.1
 FBC RES. C) TWO GENERATORS ARE SHOWN ON THE GAS RISER.
 SHOW THE LOCATION OF THE FUTURE GENERATOR- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-05-20 Cont ID  
Sent By ccole Date 2020-05-20 Time 15:22 Rev Time 0.00
Received By ccole Date 2020-05-20 Time 11:52 Sent To  
Notes
2020-05-20 15:24:04 
 1ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT #20031229
 5/20/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING:
 A) INDICATE THE TOTAL BTUH LOAD OF THE ENTIRE SYSTEM
 INCLUDING THE EXISTING, NEW, AND FUTURE GAS APPLIANCES
 AND EQUIPMENT- SECTIONS 2412.4, 2412.8, 2413.2, &
 2413.3 FBC RES. PLEASE NOTE THAT THE GENERATOR SPECS
 INDICATE THE GENERATOR HAS A GAS LOAD OF 1,202,000 BTUH
 AT 100% CAPACITY.
 B) INDICATE THE TOTAL DEVELOPED LENGTH OF THE GAS
 PIPING SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET.
 THIS INCLUDES THE EXISTING AND THE NEW PIPING-
 SECTIONS- G2413.4.1 & G2413.4.2 FBC RES. A THOROUGH
 REVIEW OF THE PIPE SIZING CANNOT BE ACCOMPLISHED
 WITHOUT THE TOTAL DEVELOPED LENGTH OF THE SYSTEM-
 SECTION 107.2.1 WPB.
 C) THE SUBMITTED SPECS FOR THE B31 REGULATORS DO NOT
 PROVIDE PERFORMANCE DATA IN LBS. PLEASE INDICATE THE
 STEP-DOWN PRESSURES IN PSI OR INCHES W.C. INDICATE THE
 MODEL NUMBERS OF THE REGULATORS AND ORIFICE SIZES ON
 THE RISER, AND ALSO MARK OR HIGHLIGHT IN THE SPECS THE
 MODEL NUMBER AND ORIFICE SIZES AS SHOWN IN THE
 PERFORMANCE DATA TABLES- SECTION G2421.1 FBC RES.
 D) SHOW THE SHUT OFF VALVE LOCATIONS AT THE METER, AND
 AT THE STEP-DOWN REGULATORS- SECTION 2420.1 FBC RES.
 E) NOTE: WHERE CONNECTED TO RIGID PIPING, A UNION SHALL
 BE INSTALLED WITH 1 FT OF EITHER SIDE OF AN MP
 REGULATOR- SECTION G2421.2 FBC RES.
  
 2) GAS WATER HEATERS:
 A) PROVIDE A BASIC FLOOR PLAN DRAWING SHOWING THE
 INSTALLATION LOCATIONS OF THE NEW TANKLESS WATER
 HEATERS- SECTION 107.2.1 WPB.
 B) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS- SECTION G2408.1 FBC RES.
 C) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO THE
 WATER HEATERS AND PROVIDE CALCULATIONS- SECTION G2407.1
 FBC RES.
 D) PROVIDE GAS VENTING DIAGRAMS SHOWING THE TYPES AND
 SIZES OF VENTS, VENT RUNS THROUGH AND OUT OF THE
 BUILDING, TERMINATION LOCATIONS, HEIGHTS ABOVE THE
 ROOF, AND ANCHORING DETAILS. SUBMIT SPECIFICATIONS FOR
 ALL THE VENT FLUES, CONNECTORS, AND TERMINATION CAPS-
 SECTIONS 2426.1 THROUGH 2426.7 FBC RES.
  
 3) SURVEY: THE GENERATOR SHALL BE LOCATED AT A MINIMUM
 OF 5' FROM THE ADJACENT EXTERIOR WALL, OR VERIFY THE
 WALL HAS A 1-HR. FIRE RESISTANCE RATING- SECTION 4.1.4
 (1) NFPA 54. A) INDICATE A MINIMUM 10' CLEARANCE FROM
 THE GENERATOR TO AIR INTAKES AND OPERABLE OPENINGS INTO
 THE BUILDING WILL BE MAINTAINED PER SECTION R303.5.1
 FBC RES. C) TWO GENERATORS ARE SHOWN ON THE GAS RISER.
 SHOW THE LOCATION OF THE FUTURE GENERATOR- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-04-01 Cont ID  
Sent By cthroop Date 2020-04-01 Time 13:28 Rev Time 0.00
Received By cthroop Date 2020-04-01 Time 06:13 Sent To  
Notes
2020-04-01 13:56:52PLAN REVIEW - GAS
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 SOW - REPLACE EXISTING 36KW GENERATOR AND PRE FAB BASE
 WITH NEW 80KW GENERATOR
  
 1. A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 2. THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS.
 THE BTU LOAD OF THE PROPOSED GAS EQUIPTMENT MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR ANY NEW PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION.
 IDENTIFY ON THE SPECIFICATION SHEETS WHICH MODEL
 REGULATOR IS BEING INSTALLED AND THE ORIFICE SIZE TO
 ENSURE THE REGULATOR CAN ACCOMMODATE THE BTU LOAD
 THROUGH THE REGULATOR.2017 FGC SEC.410.1, 2017 FBC-RES.
 SEC. G2421.1.
  
 4. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS RES SECS. G2413.4.1, G2413.4.2.
  
 5. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, &
 G2413.3.
  
 6. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. SITE PLAN SUBMITTED FOR REVIEW SHOWS GENERATOR
 LOCATED THREE FEET FROM STRUCTURE.
 NFPA 37 ? 4.1.4
 EXHAUST GASES SHALL NOT BE LOCATED WITHIN 5 FEET OF ANY
 BUILDING OPENING OR COMBUSTIBLE CONSTRUCTION.
  
 8. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL
 GAS SEC. 411.1.3.2.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2020-08-04 Cont ID  
Sent By lcrespo Date 2020-08-04 Time 13:06 Rev Time 0.00
Received By lcrespo Date 2020-08-03 Time 14:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2020-08-03 Cont ID  
Sent By shill Date 2020-08-03 Time 12:19 Rev Time 0.00
Received By shill Date 2020-07-16 Time 14:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-07-15 Cont ID  
Sent By jleahy Date 2020-07-15 Time 08:57 Rev Time 0.00
Received By jleahy Date 2020-06-25 Time 14:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-06-22 Cont ID  
Sent By rmcphers Date 2020-06-22 Time 09:49 Rev Time 0.00
Received By rmcphers Date 2020-06-10 Time 14:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-06-04 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-21 Time 14:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-20 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-29 Time 11:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-03 Cont ID  
Sent By shill Date 2020-04-03 Time 17:24 Rev Time 0.00
Received By shill Date 2020-03-26 Time 12:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2020-08-04 Cont ID  
Sent By lcrespo Date 2020-08-04 Time 13:06 Rev Time 0.00
Received By lcrespo Date 2020-08-04 Time 13:06 Sent To  
Notes
2020-08-04 13:07:0908/04/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop P PLUMBING
Rev No 5 Status N Date 2020-07-20 Cont ID  
Sent By ccole Date 2020-07-20 Time 10:43 Rev Time 0.00
Received By ccole Date 2020-07-20 Time 07:36 Sent To  
Notes
2020-07-20 10:43:51SEPARATE PLUMBING PERMIT REQUIRED FOR INSTALLATION OF
 THE WATER HEATERS- SECTION 105.3 WPB. PLEASE NOTE THAT
 MAIN PERMIT- 18050348, AND PLUMBING SUB-PERMIT 18110608
 ARE OPEN PERMITS.

Review Stop P PLUMBING
Rev No 4 Status N Date 2020-07-01 Cont ID  
Sent By ccole Date 2020-07-01 Time 15:59 Rev Time 0.00
Received By ccole Date 2020-07-01 Time 10:13 Sent To  
Notes
2020-07-01 15:59:56SEPARATE PLUMBING PERMIT REQUIRED FOR INSTALLATION OF
 THE WATER HEATERS- SECTION 105.3 WPB. PLEASE NOTE THAT
 MAIN PERMIT- 18050348, AND PLUMBING SUB-PERMIT 18110608
 ARE OPEN PERMITS.

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-06-16 Cont ID  
Sent By ccole Date 2020-06-16 Time 14:46 Rev Time 0.00
Received By ccole Date 2020-06-16 Time 12:43 Sent To  
Notes
2020-06-16 14:51:55SEPARATE PLUMBING PERMIT REQUIRED FOR INSTALLATION OF
 THE WATER HEATERS- SECTION 105.3 WPB. PLEASE NOTE THAT
 MAIN PERMIT- 18050348, AND PLUMBING SUB-PERMIT 18110608
 ARE OPEN PERMITS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-06-04 Cont ID  
Sent By ccole Date 2020-06-04 Time 12:22 Rev Time 0.00
Received By ccole Date 2020-06-04 Time 12:20 Sent To  
Notes
2020-06-04 12:24:052ND REVIEW FBC-2017 PLUMBING
 PERMIT #20031229
 6/4/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #1 FROMTHE 1ST REVIEW PRINTED BELOW WAS NOT
 ADDRESSED- PLEASE COMPLY.
  
 1) THE NEW GAS ISOMETRIC DRAWING SHOWS TWO INTERIOR
 TANKLESS WATER HEATERS THAT ARE NOT LABELED AS EXISTING
 ON THE DRAWING. IT APPEARS THESE WILL BE NEW
 INSTALLATIONS. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION GUIDELINES FOR THE
 UNITS- SEE SECTIONS P2801.3 AND G2408.1 FBC RES. PLEASE
 NOTE THAT A PLUMBING SUB-PERMIT MUST BE SUBMITTED-
 SECTION 105.3 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-05-20 Cont ID  
Sent By ccole Date 2020-05-20 Time 12:26 Rev Time 0.00
Received By ccole Date 2020-05-20 Time 11:52 Sent To  
Notes
2020-05-20 12:47:061ST REVIEW FBC-2017 PLUMBING
 PERMIT #20031229
 5/20/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW GAS ISOMETRIC DRAWING SHOWS TWO INTERIOR
 TANKLESS WATER HEATERS THAT ARE NOT LABELED AS EXISTING
 ON THE DRAWING. IT APPEARS THESE WILL BE NEW
 INSTALLATIONS. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION GUIDELINES FOR THE
 UNITS- SEE SECTIONS P2801.3 AND G2408.1 FBC RES. PLEASE
 NOTE THAT A PLUMBING SUB-PERMIT MUST BE SUBMITTED-
 SECTION 105.3 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status N Date 2020-08-04 Cont ID  
Sent By lcrespo Date 2020-08-04 Time 13:07 Rev Time 0.00
Received By lcrespo Date 2020-08-04 Time 13:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2020-07-20 Cont ID  
Sent By ccole Date 2020-07-20 Time 10:47 Rev Time 0.00
Received By ccole Date 2020-07-20 Time 10:47 Sent To  
Notes
2020-07-20 10:49:00FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ENERGY PAGE (RISER DIAGRAM) NOT SIGNED.
  
 1) PLAN IS NOT SIGNED BY THE DESIGNER OF RECORD
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2020-07-15 Cont ID  
Sent By jleahy Date 2020-07-15 Time 08:55 Rev Time 0.00
Received By jleahy Date 2020-07-15 Time 08:55 Sent To  
Notes
2020-07-15 08:56:47FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ENERGY PAGE (RISER DIAGRAM) NOT SIGNED.
  
 1) PLAN IS NOT SIGNED BY THE DESIGNER OF RECORD
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-06-22 Cont ID  
Sent By rmcphers Date 2020-06-22 Time 09:45 Rev Time 0.00
Received By rmcphers Date 2020-06-22 Time 09:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-05-29 Cont ID  
Sent By rmcphers Date 2020-05-29 Time 16:35 Rev Time 0.00
Received By rmcphers Date 2020-05-29 Time 16:35 Sent To  
Notes
2020-05-29 16:35:50SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-01 Cont ID  
Sent By rmcphers Date 2020-05-01 Time 16:33 Rev Time 0.00
Received By rmcphers Date 2020-05-01 Time 16:33 Sent To  
Notes
2020-05-01 16:36:39SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By rmcphers Date 2020-03-31 Time 16:46 Rev Time 0.00
Received By rmcphers Date 2020-03-31 Time 16:46 Sent To  
Notes
2020-04-01 09:15:05PLAN REVIEW - DIGITAL SIGNATURE AND SEAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NON-DESIGN PROFESSIONAL DOCS
  
 1. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON PLAN SHEETS UNDER THEIR
 AUTHORITY
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
 IF THE DESIGNER IS A FLORIDA LICENSED ARCHITECT OR
 ENGINEER, HE/SHE SHALL ALSO PROVIDE AN ORIGINAL SEAL
 AND WET SIGNATURE PER F.S. 61G15-16.003 AND FAC 23.002.
  
 2. UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL WITH
 SIGNATURE OF DESIGNER AS APPLICABLE; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT.
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-08-03 Cont ID  
Sent By rthermid Date 2020-08-03 Time 09:00 Rev Time 0.00
Received By ajones Date 2020-08-03 Time 09:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-05-01 Cont ID  
Sent By rfalcone Date 2020-05-01 Time 09:57 Rev Time 0.00
Received By rfalcone Date 2020-05-01 Time 09:57 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-04-03 Cont ID  
Sent By rfalcone Date 2020-04-03 Time 16:35 Rev Time 0.00
Received By rfalcone Date 2020-04-03 Time 16:35 Sent To I
Notes
***NONE***