Plan Review Details - Permit 20031126
Plan Review Stops For Permit 20031126
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-03 Cont ID  
Sent By pvalenti Date 2020-04-03 Time 07:26 Rev Time 0.00
Received By pvalenti Date 2020-04-03 Time 07:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-24 Cont ID  
Sent By pvalenti Date 2020-03-24 Time 14:24 Rev Time 0.00
Received By pvalenti Date 2020-03-24 Time 14:13 Sent To  
Notes
2020-03-24 14:27:37PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107, PLEASE PROVIDE ENGINEER'S SIGNED AND SEALED
 FASTENER SPACING DETAIL WITH CALCULATIONS FOR
 PERIMETERS AND CORNERS AS PER PRODUCT APPROVAL
 LIMITATIONS #7.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-03 Cont ID  
Sent By pvalenti Date 2020-04-03 Time 07:26 Rev Time 0.00
Received By pvalenti Date 2020-04-02 Time 16:19 Sent To  
Notes
2020-04-02 16:19:47SENT TO P VALENTI

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-24 Cont ID  
Sent By pvalenti Date 2020-03-24 Time 14:27 Rev Time 0.00
Received By pvalenti Date 2020-03-24 Time 14:27 Sent To  
Notes
***NONE***