Plan Review Details - Permit 20031119
Plan Review Stops For Permit 20031119
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-06-08 Cont ID  
Sent By shill Date 2020-06-08 Time 11:47 Rev Time 0.00
Received By shill Date 2020-06-08 Time 11:47 Sent To  
Notes
2020-06-08 11:51:17PROVISO: FUTURE ASBESTOS LETTERS TO HAVE LANGUAGE
 CONSISTENT WITH PREVIOUS PLAN REVIEW

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-04-29 Cont ID  
Sent By rmcphers Date 2020-04-29 Time 15:01 Rev Time 0.00
Received By rmcphers Date 2020-04-29 Time 15:01 Sent To  
Notes
2020-04-29 15:02:03ASBESTOS ? PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM
 THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By rmcphers Date 2020-03-31 Time 09:50 Rev Time 0.00
Received By rmcphers Date 2020-03-31 Time 09:50 Sent To  
Notes
2020-03-31 09:51:14ASBESTOS ? PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM
 THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-16 Cont ID  
Sent By shill Date 2020-05-16 Time 15:13 Rev Time 0.00
Received By shill Date 2020-05-16 Time 15:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-29 Cont ID  
Sent By rmcphers Date 2020-04-29 Time 14:54 Rev Time 0.00
Received By rmcphers Date 2020-04-29 Time 14:54 Sent To  
Notes
2020-04-29 14:55:092ND FLOOR ALT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ARCHITECTURAL DRAWINGS NEED TO HAVE A DIGITAL
 SIGNATURE PROVIDED BY THE ARCHITECT OR ENGINEER TO BE
 USED IN ELECTRONIC PLAN REVIEW. A CERTIFICATE-BASED
 DIGITAL SIGNATURE (OFTEN JUST CALLED A DIGITAL
 SIGNATURE) IS A SPECIFIC TYPE OF E-SIGNATURE. WHEN
 PROVIDED IT CANNOT BE PRINTED OUT IT WILL LOSE THE
 DIGITAL SIGNATURE - IT MUST TRAVEL IN THE COMPUTER.
 SEE FAC 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING
 AND SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 (1) INFORMATION STORED IN ELECTRONIC FILES REPRESENTING
 PLANS, SPECIFICATIONS, PLATS, REPORTS, OR OTHER
 DOCUMENTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 481, F.S., SHALL BE SIGNED, DATED AND SEALED BY
 THE ARCHITECT OR INTERIOR DESIGNER IN RESPONSIBLE
 CHARGE.
 (A) A SCANNED IMAGE OF AN ORIGINAL SIGNATURE SHALL NOT
 BE USED IN LIEU OF A DIGITAL OR ELECTRONIC SIGNATURE.
 (B) THE DATE THAT THE ELECTRONIC SIGNATURE FILE WAS
 CREATED OR THE DIGITAL SIGNATURE WAS PLACED INTO THE
 DOCUMENT MUST APPEAR ON THE DOCUMENT IN THE SAME MANNER
 AS DATE IS REQUIRED TO BE APPLIED WHEN A LICENSEE USES
 THE MANUAL SEALING PROCEDURE SET OUT IN RULE
 61G1-16.003, F.A.C.
 (2) AN ARCHITECT OR INTERIOR DESIGNER UTILIZING A
 DIGITAL SIGNATURE TO SEAL CONSTRUCTION DOCUMENTS SHALL
 ASSURE THAT THE DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
 (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN
 AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST
 DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD
 PUBLICATION 180-4 "SECURE HASH STANDARD," MARCH 2012,
 WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE
 BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE
 S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE
 INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP
 S/FIPS180-4/FIPS-180-4.PDF.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By rmcphers Date 2020-03-31 Time 09:50 Rev Time 0.00
Received By rmcphers Date 2020-03-31 Time 08:48 Sent To  
Notes
2020-03-31 09:50:012ND FLOOR ALT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE GLASS WALL DETAILS.
 2) PLEASE SHOW GLASS WALLS TO COMPLY WITH FBC 2406
 SAFETY GLAZING.
 3) EXISTING WALLS REMOVED AT LOBBY - PLEASE SHOW
 EXISTING ELEVATOR LOBBY TO COMPLY WITH FBC 3006.3
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-17 Cont ID  
Sent By jleahy Date 2020-04-17 Time 10:19 Rev Time 0.00
Received By jleahy Date 2020-04-17 Time 10:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By jleahy Date 2020-03-31 Time 15:00 Rev Time 0.00
Received By jleahy Date 2020-03-31 Time 08:02 Sent To  
Notes
2020-03-31 15:04:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) LOAD CALCULATION FOR THE ADDES LOADS PROVIDE
 ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. NEC 220
  
 2) PANEL SCHEDULE REQUIRED. PROVIDE PANEL SCHEDULE
 INDICATING ANY NEW OR ALTERED CIRCUITS 215.5
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-27 Cont ID  
Sent By pleduc Date 2020-03-27 Time   Rev Time 0.00
Received By pleduc Date 2020-03-27 Time 11:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-07 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-22 Time 15:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By shill Date 2020-03-31 Time 16:04 Rev Time 0.00
Received By shill Date 2020-03-25 Time 11:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-03-30 Cont ID  
Sent By ccole Date 2020-03-30 Time 14:50 Rev Time 0.00
Received By ccole Date 2020-03-30 Time 12:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-05-07 Cont ID  
Sent By jpearson Date 2020-05-07 Time 15:43 Rev Time 0.00
Received By jpearson Date 2020-05-07 Time 13:15 Sent To  
Notes
2020-05-07 13:15:54REVIEWED BY JERRY SMITH.
  
 PLUMBING COMMENTS: APPROVED WITH PROVISO
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PLUMBING PROVISO
 I. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, A REVISED PLAN SHEET A7 WHICH
 SHALL PROVIDE THE INFORMATION NOTED BELOW.
 1. A7 INTERIOR ELEVATIONS; DETAILS 5 AND 6:
 A. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 B. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3
  
 2. A7 INTERIOR ELEVATIONS; DETAILS 5, 6 AND 7:
 A. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE PER FBC ACC 609.4
 B. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
  
 3. A7 INTERIOR ELEVATIONS; DETAIL 7:
 A. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 B. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
  
 DOCUMENT SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR
 TO FIRST INSPECTION. PROCEED AT YOUR OWN RISK.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20031119 525 S FLAGLER DR FL 2
  
  
  
  
  
 PHONE 561-805-6715
 PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 PLUMBING COMMENTS: APPROVED WITH PROVISO
  
  
 PLUMBING COMMENTS: DENIED
  
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
  
 FBC EB = FBC EXISTING BUILDING
  
 FBC A = FBC ACCESSIBILITY
  
 FBC EC = FBC ENERGY CONSERVATION
  
 FBC R = FBC RESIDENTIAL
  
 FBC M = FBC MECHANICAL
  
 FBC P = FBC PLUMBING
  
  
  
 1. 2017 FBC 107.2.1 PROVIDE SUBMITTAL SHEET FOR
  
 TANKLESS WATER HEATER CONFIRMING HEATER MEETS ENERGY
  
 CODE.
  
 2. 2017 FBC ACCESSIBILITY. PROVIDE DIMENSIONED ENLARGED
  
 TOILET ROOM ELEVATIONS. THESE ELEVATIONS ONLY SAY ADA
  
 COMPLIANT BUT PROVIDE NO DIMENSIONAL INFORMATION FOR
  
 ANY FIXTURES, GRAB BARS, MIRRORS, ETC.
  
 3. 2017 FPC PIPING SIZING. PLUMBING KEY NOTE 1 LEAVES
  
 IT TO THE CONTRACTOR TO DECIDE IF EXISTING WATER PIPE
  
 IS LARGE ENOUGH TO SUPPLY NEW LAYOUT ADEQUATELY. THIS
  
 IS A REQUIREMENT THAT NEEDS TO BE PROVIDED ON THE
  
 PLUMBING DOCUMENTS AND THE CORRECT SIZE NEEDS TO BE
  
 SHOWN ON THE NEXT SUBMITTAL.
  
  
  
 PLEASE PROVIDE A COMMENT/RESPONSE LETTER WITH YOUR
  
 RESUBMITTAL.
  
  
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By shill Date 2020-03-27 Time 13:24 Rev Time 0.00
Received By shill Date 2020-03-27 Time 13:24 Sent To  
Notes
2020-03-27 13:24:52FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC P = FBC PLUMBING
  
 1. 2017 FBC 107.2.1 PROVIDE SUBMITTAL SHEET FOR
 TANKLESS WATER HEATER CONFIRMING HEATER MEETS ENERGY
 CODE.
 2. 2017 FBC ACCESSIBILITY. PROVIDE DIMENSIONED ENLARGED
 TOILET ROOM ELEVATIONS. THESE ELEVATIONS ONLY SAY ADA
 COMPLIANT BUT PROVIDE NO DIMENSIONAL INFORMATION FOR
 ANY FIXTURES, GRAB BARS, MIRRORS, ETC.
 3. 2017 FPC PIPING SIZING. PLUMBING KEY NOTE 1 LEAVES
 IT TO THE CONTRACTOR TO DECIDE IF EXISTING WATER PIPE
 IS LARGE ENOUGH TO SUPPLY NEW LAYOUT ADEQUATELY. THIS
 IS A REQUIREMENT THAT NEEDS TO BE PROVIDED ON THE
 PLUMBING DOCUMENTS AND THE CORRECT SIZE NEEDS TO BE
 SHOWN ON THE NEXT SUBMITTAL.
  
 PLEASE PROVIDE A COMMENT/RESPONSE LETTER WITH YOUR
 RESUBMITTAL.
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-05-16 Cont ID  
Sent By shill Date 2020-05-16 Time 15:13 Rev Time 0.00
Received By shill Date 2020-05-16 Time 15:13 Sent To  
Notes
2020-05-16 15:13:50DIGITALLY SIGNED COVER PAGE RECEIVED.
 PROVISO: PROVIDE ALL ARCHITECTURAL PAGES DIGITALLY S&S
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-04-29 Cont ID  
Sent By rmcphers Date 2020-04-29 Time 15:04 Rev Time 0.00
Received By rmcphers Date 2020-04-29 Time 15:04 Sent To  
Notes
2020-04-29 15:04:51SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By rmcphers Date 2020-03-31 Time 09:53 Rev Time 0.00
Received By rmcphers Date 2020-03-31 Time 09:53 Sent To  
Notes
2020-03-31 09:57:09DRAWINGS NEED TO BE ELECTRONICALLY SIGNED AND SEALED TO
 BE USED IN ELECTRONIC PLAN REVIEW RMCPHERSON 3/31/20
2020-03-30 14:50:27MECAHNCIAL, PLUMBING, AND FIRE SPRINKLER PLANS ARE
 GOOD.
 CCOLE- 3/30/20


Account Summary | Usage Policy | Privacy Policy