Plan Review Details - Permit 20031073
Plan Review Stops For Permit 20031073
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-24 Cont ID  
Sent By pvalenti Date 2020-03-24 Time 07:34 Rev Time 0.00
Received By pvalenti Date 2020-03-24 Time 07:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-21 Cont ID  
Sent By pvalenti Date 2020-03-21 Time 11:28 Rev Time 0.00
Received By pvalenti Date 2020-03-21 Time 11:05 Sent To  
Notes
2020-03-21 11:33:44PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
  
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-21 Cont ID  
Sent By pvalenti Date 2020-03-21 Time 11:33 Rev Time 0.00
Received By pvalenti Date 2020-03-20 Time 16:03 Sent To  
Notes
2020-03-20 16:03:07BLDG <5K


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved