Plan Review Details - Permit 20031051
Plan Review Stops For Permit 20031051
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-06-11 Cont ID  
Sent By shill Date 2020-06-11 Time 07:06 Rev Time 0.00
Received By shill Date 2020-06-11 Time 07:06 Sent To  
Notes
2020-06-11 07:06:30PREVIOUSLY FAILED BY R.MCPHERSON FOR SIGNATURE; PAPER
 ORIGINALS RECEIVED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-04-16 Cont ID  
Sent By rmcphers Date 2020-04-16 Time 14:46 Rev Time 0.00
Received By rmcphers Date 2020-04-16 Time 14:46 Sent To  
Notes
2020-04-16 14:47:03SFR REMODEL MASTER PERMIT NUMBERS - 19080919 - 19110608
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS NEED TO BE ELECTRONICALLY SIGNED BY THE
 ARCHITECT OR ENGINEER TO BE USED IN ELECTRONIC PLAN
 REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-09 Cont ID  
Sent By rmcphers Date 2020-04-09 Time 11:18 Rev Time 0.00
Received By rmcphers Date 2020-04-09 Time 11:18 Sent To  
Notes
2020-04-09 11:21:19SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS NEED TO BE ELECTRONICALLY SIGNED BY THE
 ARCHITECT OR ENGINEER TO BE USED IN ELECTRONIC PLAN
 REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-03-25 Cont ID  
Sent By cthroop Date 2020-03-25 Time 12:12 Rev Time 0.00
Received By rmcphers Date 2020-03-25 Time 12:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-04-16 Cont ID  
Sent By jpearson Date 2020-04-16 Time 09:45 Rev Time 0.00
Received By jpearson Date 2020-04-16 Time 09:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-04-09 Cont ID  
Sent By jpearson Date 2020-04-09 Time 16:06 Rev Time 0.00
Received By jpearson Date 2020-04-09 Time 14:36 Sent To  
Notes
2020-04-09 14:48:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 PLEASE SEE ADDITIONAL COMMENTS IN PARENTHESES.
  
 1. THIS WAS SUBMITTED AS A REVISION TO PERMIT 19080919.
 THAT PERMIT SET INCLUDED SHEETS A-100 AND ME-1. THIS
 REVISION IS FOR SHEETS A-201 AND A-202. PROVIDE
 CLARIFICATION AND/OR CORRECTIONS AS NEEDED. PROVIDE
 NARRATIVE OF REVISION. WPB FBC 107.2.1 ( IT APPEARS
 THAT NOT ALL OF THE SHEETS WERE UPLOADED. WE RECEIVED
 A-100, ME-1, AND A 2 SHEET PLAN ENTITLED PERMIT PHASE I
 REVISION SHEETS WHICH JUST INCLUDED ANOTHER COPY OF
 A-100 AND ME-1. PROVIDE REVISED SHEETS.)
  
 NEW COMMENT:
  
 2. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-25 Cont ID  
Sent By jpearson Date 2020-03-25 Time 14:45 Rev Time 0.00
Received By jpearson Date 2020-03-25 Time 14:45 Sent To  
Notes
2020-03-25 14:45:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THIS WAS SUBMITTED AS A REVISION TO PERMIT 19080919.
 THAT PERMIT SET INCLUDED SHEETS A-100 AND ME-1. THIS
 REVISION IS FOR SHEETS A-201 AND A-202. PROVIDE
 CLARIFICATION AND/OR CORRECTIONS AS NEEDED. PROVIDE
 NARRATIVE OF REVISION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-16 Cont ID  
Sent By rmcphers Date 2020-04-16 Time 14:47 Rev Time 0.00
Received By rmcphers Date 2020-04-15 Time 14:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-04-13 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-08 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By lcrespo Date 2020-03-31 Time 07:08 Rev Time 0.00
Received By lcrespo Date 2020-03-20 Time 16:14 Sent To  
Notes
2020-03-20 16:14:53R10

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-03-24 Cont ID  
Sent By cthroop Date 2020-03-24 Time 14:31 Rev Time 0.00
Received By medwards Date 2020-03-24 Time 14:24 Sent To  
Notes
2020-03-24 14:32:52THIS IS A REVISION TO THE ORIGINAL PERMIT 19080919.
 THIS IS A ROOM LAYOUT CHANGE. NO MECHANICAL WORK SHOWN
 ON PLANS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-04-24 Cont ID  
Sent By jpearson Date 2020-04-24 Time 15:14 Rev Time 0.00
Received By jpearson Date 2020-04-24 Time 14:24 Sent To  
Notes
2020-04-24 14:24:53REVIEWED BY JERRY SMITH.

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-04-16 Cont ID  
Sent By jpearson Date 2020-04-16 Time 11:55 Rev Time 0.00
Received By jpearson Date 2020-04-16 Time 08:21 Sent To  
Notes
2020-04-16 08:21:19REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20031051 3510 N FLAGLER DR
 MASTER PERMIT 19080919, SEE ALSO PERMIT 19110608
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED
 1. NEW PLAN SHEETS A-201 AND A-202 SHOW A PROPOSED
 CABANA.
 2. PER WPB FBC 107.2.1, A SANITARY RISER DIAGRAM SHALL
 BE SUBMITTED FOR THE CABANA.
 3. PER WPB FBC 107.2.1, SHOW HOW HOT WATER WILL BE
 PROVIDED FOR THE CABANA. PROVIDE MANUFACTURER?S
 SPECIFICATION, SIZE/CAPACITY/GAS/ELECTRIC AND LOCATION
 OF NEW WATER HEATER IF THAT IS TO BE THE SOURCE. IF
 SOURCE IS TO BE FROM EXISTING PROPERTY THEN PLEASE NOTE
 THAT PER FBC RES P2601.1 AND FBC PL 607.2 THE DEVELOPED
 LENGTH OF HOT OR TEMPERED WATER PIPING, FROM THE SOURCE
 OF HOT WATER TO THE FIXTURES THAT REQUIRE HOT OR
 TEMPERED WATER, SHALL NOT EXCEED 50 FEET. RECIRCULATING
 SYSTEM PIPING AND HEAT-TRACED PIPING SHALL BE
 CONSIDERED TO BE SOURCES OF HOT OR TEMPERED WATER. PER
 WPB FBC A PLAN SHOWING CONNECTION TO EXISTING, ROUTING,
 HOT WATER RECIRCULATION RECIRC PUMP SPECIFICATION
 W/DETAIL AND INSULATION SPEC.
 4. PER WPB FBC 107.2.1, PROVIDE ON PLAN REQUIRED
 INFORMATION FOR ELECTRICAL SERVICE FOR ANY OF THE
 INSTANCES IN ITEM 3. IF GAS IS REQUIRED A SEPARATE
 PERMIT AND PLAN IS REQUIRED.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20031051 3510 N FLAGLER DR
 MASTER PERMIT 19080919, SEE ALSO PERMIT 19110608
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-04-13 Cont ID  
Sent By lcrespo Date 2020-04-13 Time 15:01 Rev Time 0.00
Received By jpearson Date 2020-04-13 Time 14:17 Sent To  
Notes
2020-04-13 14:57:24REVIEWED BY JERRY SMITH, RESULTS ENTERED BY JP.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20031051 3510 N FLAGLER
 MASTER PERMIT 19080919
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. THIS WAS SUBMITTED AS A REVISION TO PERMIT
 19080919.THAT PERMIT SET INCLUDED SHEETS A-100 AND
 ME-1. THIS REVISION IS FOR SHEETS A-201 AND A-202.
 PROVIDE CLARIFICATION AND/OR CORRECTIONS AS NEEDED.
 PROVIDE NARRATIVE OF REVISION. WPB FBC 107.2.1 (IT
 APPEARS THAT NOT ALL OF THE SHEETS WERE UPLOADED. WE
 RECEIVED A-100, ME-1, AND A 2 SHEET PLAN ENTITLED
 PERMIT PHASE I REVISION SHEETS WHICH JUST INCLUDED
 ANOTHER COPY OF A-100 AND ME-1. PROVIDE REVISED
 SHEETS.)
 2. WITHOUT BEING ABLE TO REVIEW THE NOTED NEW SHEETS
 A-201 AND A-202 WHICH PLAN SHEET ME-1 REFERS TO, THE
 PLUMBING REVIEW CANNOT BE COMPLETED. THE PLUMBING RISER
 DIAGRAM ON PLAN SHEET ME-1 APPEARS TO BE IN COMPLIANCE.
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT
 3. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20031051 3510 N FLAGLER
 MASTER PERMIT 19080919
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
  
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
  
 PROFESSIONAL,
  
 CONTRACTORS OR THEIR REPRESENTATIVES FROM THE
  
 RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
  
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
  
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
  
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
  
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
  
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
  
 AVOID VOIDING OF THE PERMIT.
2020-04-13 14:17:10REVIEWED BY JERRY SMITH.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-03-31 Cont ID  
Sent By lcrespo Date 2020-03-31 Time 17:14 Rev Time 0.00
Received By lcrespo Date 2020-03-30 Time 07:25 Sent To  
Notes
2020-03-31 07:09:3303/31/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL,
 CONTRACTORS OR THEIR REPRESENTATIVES FROM THE
 RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-11 Cont ID  
Sent By shill Date 2020-06-11 Time 07:07 Rev Time 0.00
Received By shill Date 2020-06-11 Time 07:07 Sent To  
Notes
2020-06-11 07:08:24PAPER ORIGINALS RECEIVED, ROUTED TO STORAGE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-04-16 Cont ID  
Sent By jpearson Date 2020-04-16 Time 09:52 Rev Time 0.00
Received By jpearson Date 2020-04-16 Time 09:52 Sent To  
Notes
2020-04-16 09:52:43PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR
 ENGINEERS. PROVIDE CORRECTION OR SUBMIT PAPER PLANS
 WITH SIGNATURE AND SEAL WHEN ALL TRADES HAVE APPROVED
 PLAN. WPB FBC 107.1; FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-09 Cont ID  
Sent By rmcphers Date 2020-04-09 Time 11:21 Rev Time 0.00
Received By rmcphers Date 2020-04-09 Time 11:21 Sent To  
Notes
2020-04-09 11:22:20DRAWINGS NEED TO BE ELECTRONICALLY SIGNED BY THE
 ARCHITECT OR ENGINEER TO BE USED IN ELECTRONIC PLAN
 REVIEW.