Plan Review Details - Permit 20031034
Plan Review Stops For Permit 20031034
Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2020-04-09 Cont ID  
Sent By lcrespo Date 2020-04-09 Time 07:20 Rev Time 0.00
Received By lcrespo Date 2020-04-09 Time 07:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-20 Cont ID  
Sent By lcrespo Date 2020-03-20 Time 18:05 Rev Time 0.00
Received By lcrespo Date 2020-03-20 Time 14:44 Sent To  
Notes
2020-03-20 14:44:29PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-04-09 Cont ID  
Sent By lcrespo Date 2020-04-09 Time 07:20 Rev Time 0.00
Received By lcrespo Date 2020-04-09 Time 07:18 Sent To  
Notes
2020-04-09 07:19:5604/09/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-20 Cont ID  
Sent By lcrespo Date 2020-03-20 Time 18:05 Rev Time 0.00
Received By lcrespo Date 2020-03-20 Time 18:05 Sent To  
Notes
2020-03-20 18:19:1303/20/2020 PLUMBING 1ST REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3
 BUILDING PERMIT VALUATIONS.
  
 2. A SEPARTE PLUMBING PERMIT IS REQUIRED FOR A BACKFLOW
 BY A LICENSED CONTRACTOR AND CERTIFIED BY THE CITY OF
 WEST PALM BEACH UTILITITES DERPARTMENT FOR THAT SCOPE
 OF WORK PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 THE PERMIT APPLICATION SHALL CONTAIN THE FOLLOWING
 INFORMATION AND DOCUMENTATION:
 A) A SITE PLAN DEPICTING THE GENERAL LOCATION OF THE
 PROPOSED BACKFLOW PREVENTION DEVICE (UTILITIES REQUIRES
 THE DEVIVE TO BE WITH 5' OF METER).
 B) TWO COPIES OF THE MANUFACTURER'S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF
 THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
 C) DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE.
 D) DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS
 ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT DEPARTMENT
 OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT
 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE
 PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY
 REQUIREMENTS.
  
 ALL BACKFLOW PREVENTION ASSEMBLIES SHALL BE INSTALLED
 ON PRIVATE PROPERTY, ON THE CONSUMER'S PLUMBING LINE
 LOCATED IMMEDIATELY BEYOND THE WATER METER BUT BEFORE
 ANY BRANCHING OF PLUMBING LINES FROM THE COMMON LINE.
 ALL DEVICES MUST BE TESTED AND CERTIFIED BY THE CITY OF
 WEST PALM BEACH UTILITIES DEPARTMENT PRIOR TO THE FINAL
 INSPECTIONS BY THE BUILDING DEPARTMENT. PLEASE CONTACT
 THE CITY OF WEST PALM BEACH PUBLIC UTILITIES CENTRAL
 OPERATIONS AT 561-822-2210 TO ARRANGE FOR THE UTILITIES
 DEPARTMENT TO CERTIFY THE DEVICE.
  
 NOTE: THE CITY OF WEST PALM BEACH UTILITIES REQUIRES
 THE WATER SUPPLY PIPING BETWEEN THE METER AND THE
 BACKFLOW PREVENTION DEVICE TO BE A MINIMUM OF TYPE L
 COPPER. PVC PIPING IS NOT PERMITTED. EXISTING WATER
 SUPPLIES NOT MEETING THESE CRITERIA MUST BE UPGRADED.
 PLEASE CALL 561- 822-2240 FOR FURTHER INFORMATION.
  
 THE ESTIMATED REVIEW TIME FOR THESE PERMITS IS
 APPROXIMATELY 72 HOURS.
  
 THE PERMIT CARD AND MANUFACTURER?S SPECIFICATIONS MUST
 BE ON THE JOB SITE FOR INSPECTION.
  
 3. PLEASE PROVIDE THE LENGTH OF PIPE BEING REPLACED AND
 IF YOU ARE CONNECTING TO A CITY LATERAL AND PLEASE SHOW
 IT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. PLEASE BE ADVISED THAT YOU WILL REQUIRE A CLEANOUT
 AT CITY LATERAL IF THERE IS NOT ONE PRESENT PER CITY OF
 WEST PALM UTILITIES DEPARTMENT AS A CITY ORDINANCE .
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-805-6720
  