Plan Review Details - Permit 20030947
Plan Review Stops For Permit 20030947
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-22 Cont ID  
Sent By rmcdouga Date 2020-04-22 Time 14:05 Rev Time 0.00
Received By rmcdouga Date 2020-04-22 Time 14:05 Sent To  
Notes
2020-04-22 14:07:04BUILDING REVIEW APPROVED WITH PROVISO:
  
 FBC R G 2404.6, AT TIME OF INSPECTION, PLEASE PROVIDE
 ENGINEER SIGNED/SEALED ANCHORING DETAIL FOR SITE
 SPECIFIC WIND LOADS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-03-24 Cont ID  
Sent By pvalenti Date 2020-03-23 Time 12:08 Rev Time 0.00
Received By pvalenti Date 2020-03-23 Time 12:08 Sent To  
Notes
2020-03-23 12:16:29PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 FBC R G 2404.6, AT TIME OF INSPECTION, PLEASE PROVIDE
 ENGINEER SIGNED/SEALED ANCHORING DETAIL FOR SITE
 SPECIFIC WIND LOADS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-22 Cont ID  
Sent By jpearson Date 2020-04-22 Time 14:06 Rev Time 0.00
Received By jpearson Date 2020-04-22 Time 12:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-24 Cont ID  
Sent By jpearson Date 2020-03-24 Time 09:05 Rev Time 0.00
Received By jpearson Date 2020-03-24 Time 09:05 Sent To I
Notes
2020-03-24 09:02:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
  
 FOR THE RESUBMITTAL:
  
 PLEASE PAY YOUR BALANCE DUE ONLINE SO YOUR PERMIT CAN
 BE EMAILED TO YOU.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), OR IF THE DESIGN
 PROFESSIONAL HAS A DIGITAL SIGNATURE, AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-05-12 Cont ID  
Sent By lcrespo Date 2020-05-12 Time 08:27 Rev Time 0.00
Received By lcrespo Date 2020-05-12 Time 08:27 Sent To  
Notes
2020-05-12 08:28:1705/12/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-03-20 Cont ID  
Sent By lcrespo Date 2020-03-20 Time 18:42 Rev Time 0.00
Received By lcrespo Date 2020-03-20 Time 18:24 Sent To  
Notes
2020-03-20 18:43:1303/20/20 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING GAS. A FULL EVALUATION OF ALL GAS EQUIPMENT
 WILL BE DONE ON THIS REVIEW PROCESS, IF NOT TO CODE, IT
 MAY NEED TO BE BOUT UP TO CODE COMPLIANCE.
  
 2. GAS RISER DIAGRAM HAS A 281 BTU'S AND THE
 SPECIFICATION SAYS 327 BTU'S PLEASE CHANGE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 GAS.
  
 3. PLEASE LABEL SHUTOFF VALVES, UNIONS AND REGULATORS
 (IF NEEDED) ON ISOMETRIC PER THE 2017 FBC FG SEC.
 409.4.
  
 4. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1
 GENERAL.
  
 5. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC FG SEC. 410.1 OR 2017 FBC
 RES. SEC. G2421.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-13 Cont ID  
Sent By lmarchan Date 2020-05-13 Time 08:48 Rev Time 0.00
Received By lmarchan Date 2020-04-13 Time 08:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-24 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-18 Time 08:40 Sent To  
Notes
2020-03-20 13:14:303/20 ROUTED TO GENERATOR INBOX
2020-03-19 08:40:28ROUTED TO ZONING INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-22 Cont ID  
Sent By rmcdouga Date 2020-04-22 Time 14:08 Rev Time 0.00
Received By rmcdouga Date 2020-04-22 Time 14:08 Sent To  
Notes
2020-04-22 14:27:41SIGNED AND SEALED GENERATOR PAD ENGINEERING IS TO BE
 PROVIDED TO FILED INSPECTOR.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-04-15 Cont ID  
Sent By rfalcone Date 2020-04-15 Time 13:15 Rev Time 0.00
Received By rfalcone Date 2020-04-15 Time 13:15 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-03-20 Cont ID  
Sent By rfalcone Date 2020-03-20 Time 11:42 Rev Time 0.00
Received By rfalcone Date 2020-03-20 Time 11:42 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved