Plan Review Stops For Permit 20030947 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-04-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-04-22 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-04-22 |
Time |
14:05 |
Sent To |
|
|
Notes |
2020-04-22 14:07:04 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | FBC R G 2404.6, AT TIME OF INSPECTION, PLEASE PROVIDE | | ENGINEER SIGNED/SEALED ANCHORING DETAIL FOR SITE | | SPECIFIC WIND LOADS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2020-03-24 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-03-23 |
Time |
12:08 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-03-23 |
Time |
12:08 |
Sent To |
|
|
Notes |
2020-03-23 12:16:29 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | FBC R G 2404.6, AT TIME OF INSPECTION, PLEASE PROVIDE | | ENGINEER SIGNED/SEALED ANCHORING DETAIL FOR SITE | | SPECIFIC WIND LOADS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2020-04-22 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2020-04-22 |
Time |
14:06 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-04-22 |
Time |
12:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-03-24 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2020-03-24 |
Time |
09:05 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-03-24 |
Time |
09:05 |
Sent To |
I |
|
Notes |
2020-03-24 09:02:19 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF | | PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR | | THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC | | 107.1, 107.2.1, 107.3.5.1.2 | | | | FOR THE RESUBMITTAL: | | | | PLEASE PAY YOUR BALANCE DUE ONLINE SO YOUR PERMIT CAN | | BE EMAILED TO YOU. | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | PROFESSIONAL (ARCHITECT OR ENGINEER), OR IF THE DESIGN | | PROFESSIONAL HAS A DIGITAL SIGNATURE, AND THE PAGES ARE | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2020-05-12 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-05-12 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-05-12 |
Time |
08:27 |
Sent To |
|
|
Notes |
2020-05-12 08:28:17 | 05/12/20 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEW | | AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM | | EMAIL: [email protected] CELL: 561-701-6437 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2020-03-20 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-03-20 |
Time |
18:42 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-03-20 |
Time |
18:24 |
Sent To |
|
|
Notes |
2020-03-20 18:43:13 | 03/20/20 1ST GAS REVIEW **DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF | | EXISTING GAS. A FULL EVALUATION OF ALL GAS EQUIPMENT | | WILL BE DONE ON THIS REVIEW PROCESS, IF NOT TO CODE, IT | | MAY NEED TO BE BOUT UP TO CODE COMPLIANCE. | | | | 2. GAS RISER DIAGRAM HAS A 281 BTU'S AND THE | | SPECIFICATION SAYS 327 BTU'S PLEASE CHANGE PER THE WPB | | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL | | GAS. | | | | 3. PLEASE LABEL SHUTOFF VALVES, UNIONS AND REGULATORS | | (IF NEEDED) ON ISOMETRIC PER THE 2017 FBC FG SEC. | | 409.4. | | | | 4. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF | | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH | | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA | | STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1 | | GENERAL. | | | | 5. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | INSTALLATION PER THE 2017 FBC FG SEC. 410.1 OR 2017 FBC | | RES. SEC. G2421.1. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6720 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-05-13 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-05-13 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-04-13 |
Time |
08:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2020-03-24 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-03-18 |
Time |
08:40 |
Sent To |
|
|
Notes |
2020-03-20 13:14:30 | 3/20 ROUTED TO GENERATOR INBOX | 2020-03-19 08:40:28 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2020-04-22 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-04-22 |
Time |
14:08 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-04-22 |
Time |
14:08 |
Sent To |
|
|
Notes |
2020-04-22 14:27:41 | SIGNED AND SEALED GENERATOR PAD ENGINEERING IS TO BE | | PROVIDED TO FILED INSPECTOR. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2020-04-15 |
|
|
Cont ID |
|
Sent By |
rfalcone |
Date |
2020-04-15 |
Time |
13:15 |
Rev Time |
0.00 |
Received By |
rfalcone |
Date |
2020-04-15 |
Time |
13:15 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2020-03-20 |
|
|
Cont ID |
|
Sent By |
rfalcone |
Date |
2020-03-20 |
Time |
11:42 |
Rev Time |
0.00 |
Received By |
rfalcone |
Date |
2020-03-20 |
Time |
11:42 |
Sent To |
I |
|
Notes |
|
|