2020-08-07 16:26:39 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S | | APPROVAL INCLUDING THE INFILL WORK. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2020-07-27 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-07-27 |
Time |
06:30 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-07-27 |
Time |
06:30 |
Sent To |
|
|
Notes |
2020-07-27 06:41:11 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561?805?6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | 3RD BUILDING REVIEW DENIED: | | | | FBC B 107.1, AS PER THE INFORMATION THAT HAS BEEN | | SUBMITTED, IT APPEARS THAT WE ARE STILL MISSING: | | | | 1) THE DETAILS FOR THE INFILL AREAS, INCLUDING COLUMNS | | AND BEAMS AS APPLICABLE. | | | | 2) THE PRODUCT APPROVAL FOR WINDOW MULLIONS. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-06-01 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-06-01 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-06-01 |
Time |
09:47 |
Sent To |
|
|
Notes |
2020-06-01 10:04:48 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | 2ND BUILDING REVIEW DENIED: | | | | FBC B 107, THE PLANS NEED TO BE RE-SUBMITTED, AS THE | | CHANGES WERE NOT ACCEPTABLE TO THE REQUIREMENTS OF THE | | HISTORIC DEPARTMENT. PLEASE SEE THE DENIED COMMENTS | | FROM THE HISTORIC DEPARTMENT. | | | | WHEN RESUBMITTING, IF THE WINDOW FRAME AND MULLION | | PRODUCT APPROVAL DETAILS DO NOT INCLUDE INFILLING | | STRUCTURAL AREAS, AN ENGINEER'S DETAIL MAY BE REQUIRED | | FOR REBUILDING ANY COLUMNS, BEAMS, AND/OR IN-FILL | | AREAS. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2020-03-19 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-03-19 |
Time |
08:00 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-03-19 |
Time |
08:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
4 |
Status |
P |
Date |
2020-08-07 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-08-07 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-08-07 |
Time |
11:45 |
Sent To |
B |
|
Notes |
2020-08-07 11:46:42 | THE PERMIT HAS BEEN APPROVED. | | | | PLEASE SCHEDULE A 507 ZONING FINAL AFTER THE PAIRED | | FRENCH DOOR AND ONE OF THE TRIPLE (RIBBON) WINDOWS HAVE | | BEEN INSTALLED WITH ALL TRIM AND SILL WORK COMPLETED. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
3 |
Status |
F |
Date |
2020-07-23 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-07-23 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-07-23 |
Time |
09:18 |
Sent To |
|
|
Notes |
2020-07-23 13:21:26 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | | | 1. THE SITE PLANS PROVIDED DOES NOT ACCURATELY REFLECT | | THE BUILDING. STAFF BELIEVES THE ORIENTATION MAY BE | | MIXED UP. | | 2. NO MULLION INFORMATION WAS PROVIDED FOR THE PAIRED | | OR TRIPLE WINDOWS. PROVIDE MULLION INFORMATION. | | 3. PROVIDE PHOTOS OF EACH ELEVATION WITH OPENING LABELS | | MATCHING THE WINDOW SCHEDULE AND SITE PLAN. IF NOT | | POSSIBLE FOR EACH ELEVATION, PROVIDE MORE THAN ONE | | PHOTO. | | 4. THE FIRST-FLOOR TRIPLE WINDOWS NEED TO HAVE MULLIONS | | SIZED TO WHAT WAS EXISTING BEFORE THE WINDOWS WERE | | REPLACED. | | 5. THE SECOND-FLOOR TRIPLE WINDOWS NEED TO HAVE A | | MULLIONS SIZED TO WHAT WAS EXISTING BEFORE THE WINDOWS | | WERE REPLACED. | | 6. THE WINDOW LOCATED ABOVE THE BALCONY WILL NEED TO BE | | REMOVED. A PAIRED FRENCH DOOR WITH 10-LITE EACH WILL | | NEED TO BE INSTALLED. | | 7. ALL WINDOWS WILL NEED TO HAVE WINDOW TRIM AND SILL | | RECONSTRUCTED IN WOOD. | | 8. ALL WINDOWS REQUIRING A MULLION SHALL HAVE A MULLION | | TO MATCH THE EXISTING/ORIGINAL MULLION WIDTH. THIS WAS | | LIKELY BETWEEN 4 AND 6 INCHES. | | 9. BASED ON PREVIOUS CONVERSATIONS, ALL WINDOWS WERE | | BEING REPLACED. ARE ANY WINDOWS NOT BEING REPLACED? | | | | PROPOSED CONDITIONS, SUBJECT TO CHANGE: | | 1. ALL WINDOWS NEED TO BE SIZED TO FIT THE ORIGINAL | | WINDOW FRAME OPENING. ALL WINDOWS SHALL MATCH THE | | INSET/LOCATION/DEPTH OF THE ORIGINAL WINDOWS WITHIN THE | | FRAME OPENING. | | 2. ALL MULLIONS NEED TO BE SIZED TO THE WIDTH OF THE | | ORIGINAL MULLION WITHIN THE WINDOW FRAME OPENING. ALL | | MULLIONS NEED TO MATCH THE LOCATION/PLACEMENT OF THE | | ORIGINAL MULLION WITHIN THE FRAME OPENING. | | 3. ALL NEW STREET-FACING WINDOWS NEED TO HAVE CLEAR | | GLASS ONLY. | | 4. THE SMALL 8-LITE WINDOWS ON EITHER SIDE OF THE FRONT | | DOOR SHALL REMAIN AND BE REPAIRED AS NEEDED. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
F |
Date |
2020-05-29 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-05-29 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-05-29 |
Time |
08:56 |
Sent To |
B |
|
Notes |
2020-05-29 08:56:52 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | 1. PROVIDE PHOTOS OF EACH ELEVATION WITH OPENING LABELS | | MATCHING THE WINDOW SCHEDULE AND SITE PLAN. IF NOT | | POSSIBLE FOR EACH ELEVATION, PROVIDE MORE THAN ONE | | PHOTO. | | 2. THE FRONT DOOR IS INAPPROPRIATE. REVISE THE DOOR TO | | BE A MISSION APPROPRIATE DOOR. PROVIDE GRAPHIC OF | | PROPOSED DOOR. | | 3. THE TWO WINDOWS (PAIRED) WITH A 12/12 LITE PATTERN | | NEED TO BE REMOVED. A TRIPLE PAIRED WINDOW WITH 6/1 | | LITE PATTERN WILL NEED TO BE INSTALLED. THE WINDOWS AND | | MULLION WILL NEED TO BE SIZED TO WHAT WAS EXISTING | | BEFORE THE WINDOWS WERE REPLACED. | | 4. THE TWO WINDOWS ON THE SECOND FLOOR UNDER THE PESKY | | CYPRESS BRACKETS WILL NEED TO BE REMOVED. A TRIPLE | | PAIRED WINDOW WITH 6/1 LITE PATTERN WILL NEED TO BE | | INSTALLED. THE WINDOWS AND MULLION WILL NEED TO BE | | SIZED TO WHAT WAS EXISTING BEFORE THE WINDOWS WERE | | REPLACED. | | 5. THE WINDOW LOCATED ABOVE THE BALCONY WILL NEED TO BE | | REMOVED. A PAIRED FRENCH DOOR WITH 10-LITE EACH WILL | | NEED TO BE INSTALLED. | | 6. ALL WINDOWS WILL NEED TO HAVE WINDOW TRIM AND SILL | | RECONSTRUCTED. | | 7. ALL WINDOWS REQUIRING A MULLION SHALL HAVE A MULLION | | TO MATCH THE EXISTING/ORIGINAL MULLION WIDTH. THIS WAS | | LIKELY BETWEEN 4 AND 6 INCHES. | | 8. PROVIDE THE MUNTIN DETAIL FOR EACH PRODUCT BEING | | USED. LAWSON HAS A DIFFERENT MUNTIN PROFILE AVAILABLE | | COMPARED TO JELD-WEN AND SILVER LINE. | | | | PROPOSED CONDITIONS, SUBJECT TO CHANGE: | | 1. ALL WINDOWS NEED TO BE SIZED TO FIT THE ORIGINAL | | WINDOW FRAME OPENING. ALL WINDOWS SHALL MATCH THE | | INSET/LOCATION/DEPTH OF THE ORIGINAL WINDOWS WITHIN THE | | FRAME OPENING. | | 2. ALL NEW STREET-FACING WINDOWS NEED TO HAVE CLEAR | | GLASS ONLY. | | 3. THE SMALL 8-LITE WINDOWS ON EITHER SIDE OF THE FRONT | | DOOR SHALL REMAIN AND BE REPAIRED AS NEEDED. | | | | | | THE FOLLOWING ITEMS TO ADDRESS MAY NOT BE COMPLETE | | GIVEN THE LACK OF INFORMATION PROVIDED TO STAFF. | | REUSING EXISTING WINDOWS IN OPENINGS THAT NEED TO BE | | REVERTED BACK TO THEIR ORIGINAL STATE MAY BE POSSIBLE. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | PLANNING DIVISION | | [email protected] | OFFICE: 561.822.1428 | TTY: | | 800.955.8771 | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | FL 33402 | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
F |
Date |
2020-03-27 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2020-03-27 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2020-03-23 |
Time |
10:56 |
Sent To |
PC |
|
Notes |
2020-03-27 09:57:14 | THE PERMIT HAS FAILED. ADDITIONAL INFORMATION IS | | REQUIRED. PLEASE SEE EMAIL SENT ON MONDAY, MARCH 23RD | | FOR WHAT ADDITIONAL INFORMATION IS REQUIRED. PLEASE | | FOLLOW THE WINDOW PERMIT APPLICATION EXAMPLE, THIS | | INFORMATION CAN BE ACCEPTED VIA EMAIL. | | | | AT PRESENT, AND SUBJECT TO CHANGE THE PERMIT MAY BE | | APPROVED WITH THE FOLLOWING CONDITION(S): | | | | 1. ALL WINDOWS SHALL BE SIZED TO FIT THE ORIGINAL | | WINDOW FRAME OPENING. ALL WINDOWS SHALL MATCH THE | | INSET/DEPTH/LOCATION OF THE ORIGINAL WINDOWS WITHIN THE | | WINDOW OPENING. | | 2. THE EXISTING MULLIONS FOR ALL WINDOWS SHALL REMAIN | | OR BE REPLACED WITH AN ALUMINUM MULLION OF THE SAME | | WIDTH. | | 3. ALL WINDOWS AND DOORS WITH A LITE PATTERN SHALL HAVE | | AN EXTERNAL OGEE DIMENSIONAL MUNTIN PROFILE. | | 4. ALL 6/1 WINDOWS LITE PATTERN. | | 5. ALL STREET FACING GLASS SHALL HAVE CLEAR GLASS ONLY. | | ALL NON-STREET FACING GLASS SHALL HAVE CLEAR GLASS. THE | | NON-STREET FACING GLASS MAY HAVE LOW-E COATING. | | | | FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER, | | HISTORIC PRESERVATION PLANNER AT [email protected]. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | | CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES | | T: 561-822-1428 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2020-08-07 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-08-07 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-08-07 |
Time |
16:27 |
Sent To |
|
|
Notes |
2020-08-07 09:07:48 | ROUTED TO ZONING BIN |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-07-27 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-07-27 |
Time |
06:41 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-07-27 |
Time |
06:29 |
Sent To |
|
|
Notes |
2020-07-21 16:45:04 | ROUTED TO ZONING IN BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-06-01 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-06-01 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-05-27 |
Time |
17:48 |
Sent To |
|
|
Notes |
2020-05-27 17:48:40 | ROUTED TO HISTORIC BIN |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-03-27 |
|
|
Cont ID |
|
Sent By |
ccarvaja |
Date |
2020-03-27 |
Time |
13:40 |
Rev Time |
|
Received By |
ccarvaja |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|