2020-03-25 13:55:49 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS |
| OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. THE RISER |
| PROVIDED SHOWS TWO METERS FEEDING ONE PANEL, WHICH IS |
| NOT PERMITTED. ARE THERE SEPARATE PANELS FOR EACH UNIT? |
| IS THIS SERVICE EXISTING OR PROPOSED? PROVIDE |
| CLARIFICATIONS AND CORRECTIONS AS NEEDED. NEC 215.5, |
| 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| E3609.3; WPB FBC 107.2.1 |
| 2. PLAN IS NOT CLEAR WHAT IS PROPOSED AND WHAT IS |
| EXISTING. PROVIDE CLEAR INDICATION OF PROPOSED WORK. |
| WPB FBC 107.2.1 |
| 3. PROVIDE ACCURATE PANEL SCHEDULE INDICATING ANY NEW |
| OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| APPLICABLE TO COMPLY WITH CODE. THE CIRCUITS FOR EACH |
| UNIT MUST BE ACCESSIBLE FOR TO THE OCCUPANT OF THAT |
| UNIT. THE PANEL SCHEDULE PROVIDED SHOWS CIRCUITS FOR |
| UNIT A AND B IN THE SAME PANEL. PROVIDE CLARIFICATION |
| AND/OR CORRECTION. NEC 210.8, 210.12, 210.19, 210.20, |
| 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE |
| E3602.2 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |