Plan Review Details - Permit 20030927
Plan Review Stops For Permit 20030927
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-29 Cont ID  
Sent By pvalenti Date 2020-04-29 Time 11:07 Rev Time 0.00
Received By pvalenti Date 2020-04-29 Time 11:07 Sent To  
Notes
2020-04-29 11:22:02PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 PROVIDE PRODUCT APPROVAL FOR NEW WINDOWS (INCLUDE
 SHUTTERS IF WINDOWS ARE NON-IMPACT) AT TIME OF
 INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-20 Cont ID  
Sent By pvalenti Date 2020-03-20 Time 14:10 Rev Time 0.00
Received By pvalenti Date 2020-03-20 Time 13:48 Sent To  
Notes
2020-03-20 14:27:56PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 107, PROVIDE INDICATION ON PLANS OF THE
 LOCATIONS OF ALL DRYWALL/INSULATION/FRAMING REPAIRS
 INCLUDING EXTERIOR WALLS.
  
 2) FBC B 107, PROVIDE AN EXTERIOR WALL REPAIR DETAIL ON
 PLANS, INCLUDING FRAMING MEMBER, INSULATION, AND
 DRYWALL SPECIFICATIONS.
  
 3) FBC B 107, PROVIDE INDICATION OF LOCATIONS AND
 DETAILS INCLUDING UL LISTING FOR FIRE RATED TENANT
 SEPARATION WALLS AND CEILING/FLOOR ASSEMBLIES.
  
 4) FBC B 107, PROVIDE INDICATION OF LOCATION ON PLANS
 OF WINDOW/DOOR REPLACEMENT.
  
  
 NOTE: ANY WINDOWS OR DOORS THAT ARE NOT IMPACT
 RESISTANT WILL NEED TO HAVE STORM PROTECTION, SUCH AS
 SHUTTERS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-30 Cont ID  
Sent By skennedy Date 2020-04-30 Time 15:30 Rev Time 0.00
Received By skennedy Date 2020-04-30 Time 15:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-25 Cont ID  
Sent By jpearson Date 2020-03-25 Time 13:55 Rev Time 0.00
Received By jpearson Date 2020-03-25 Time 13:55 Sent To  
Notes
2020-03-25 13:55:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL DETAILS
 OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. THE RISER
 PROVIDED SHOWS TWO METERS FEEDING ONE PANEL, WHICH IS
 NOT PERMITTED. ARE THERE SEPARATE PANELS FOR EACH UNIT?
 IS THIS SERVICE EXISTING OR PROPOSED? PROVIDE
 CLARIFICATIONS AND CORRECTIONS AS NEEDED. NEC 215.5,
 230, 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 2. PLAN IS NOT CLEAR WHAT IS PROPOSED AND WHAT IS
 EXISTING. PROVIDE CLEAR INDICATION OF PROPOSED WORK.
 WPB FBC 107.2.1
 3. PROVIDE ACCURATE PANEL SCHEDULE INDICATING ANY NEW
 OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. THE CIRCUITS FOR EACH
 UNIT MUST BE ACCESSIBLE FOR TO THE OCCUPANT OF THAT
 UNIT. THE PANEL SCHEDULE PROVIDED SHOWS CIRCUITS FOR
 UNIT A AND B IN THE SAME PANEL. PROVIDE CLARIFICATION
 AND/OR CORRECTION. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2020-04-30 Cont ID  
Sent By skennedy Date 2020-04-30 Time 15:30 Rev Time 0.00
Received By skennedy Date 2020-04-29 Time 11:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-27 Cont ID  
Sent By lcrespo Date 2020-03-27 Time 17:38 Rev Time 0.00
Received By lcrespo Date 2020-03-18 Time 09:42 Sent To  
Notes
2020-03-19 09:42:26R41

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-04-29 Cont ID  
Sent By pvalenti Date 2020-04-29 Time 11:07 Rev Time 0.00
Received By pvalenti Date 2020-04-29 Time 11:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-20 Cont ID  
Sent By pvalenti Date 2020-03-20 Time 13:48 Rev Time 0.00
Received By pvalenti Date 2020-03-20 Time 13:48 Sent To  
Notes
2020-03-20 14:09:56PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 MECHANICAL REVIEW DENIED:
  
 1) FBC M 301.15/304.1, PROVIDE (ENGINEER APPROVED) TIE
 DOWN DETAIL FOR THE EXTERIOR CONDENSING UNIT. PLEASE
 INCLUDE LOCATIONS AND QUANTIES OF FASTENERS AND
 CONNECTORS IF REQUIRED.
 2) FBC M 307.2.4.1, PROVIDE INDICATION OF MINI-SPLIT
 CHECK VALVE TRAP IN CONDENSATE LINE.
 3) FBC M 603.1, PROVIDE INDICATION OF HOW AIR WILL BE
 CONDITIONED AT OTHER HALF OF HOUSE; WILL THIS BE
 ACCOMPLISHED THROUGH A SECOND MINI-SPLIT AIR HANDLER?
  
 NOTE: A MECHANICAL SUB-PERMIT IS REQUIRED PRIOR TO
 MECHANICAL WORK.

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-03-27 Cont ID  
Sent By lcrespo Date 2020-03-27 Time 17:37 Rev Time 0.00
Received By lcrespo Date 2020-03-26 Time 07:28 Sent To  
Notes
2020-03-27 17:37:5403/27/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  