Plan Review Details - Permit 20030922
Plan Review Stops For Permit 20030922
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-20 Cont ID  
Sent By jleahy Date 2020-05-20 Time 11:53 Rev Time 0.00
Received By rmcphers Date 2020-05-20 Time 11:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-29 Cont ID  
Sent By rmcphers Date 2020-04-29 Time 16:30 Rev Time 0.00
Received By rmcphers Date 2020-04-29 Time 16:30 Sent To  
Notes
2020-04-29 16:40:48SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS AND ENGINEERING CALCULATIONS DO NOT SHOW IN
 "ADOBE" AS DIGITALLY SIGNED BY THE ENGINEER. DRAWINGS
 AND ENGINEERING PROVIDED NEED TO HAVE A DIGITAL
 SIGNATURE PROVIDED BY THE ARCHITECT OR ENGINEER TO BE
 USED IN ELECTRONIC PLAN REVIEW. PLEASE CONTACT THE
 ENGINEER OR ARCHITECT AND ASK FOR THE ENGINEERING TO BE
 DIGITALLY SIGNED. A CERTIFICATE-BASED DIGITAL SIGNATURE
 (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A SPECIFIC
 TYPE OF E-SIGNATURE. WHEN PROVIDED IT CANNOT BE PRINTED
 OUT - IT WILL LOSE THE DIGITAL SIGNATURE ? IT MUST
 TRAVEL IN THE COMPUTER.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By rmcphers Date 2020-03-23 Time 14:09 Rev Time 0.00
Received By rmcphers Date 2020-03-23 Time 14:07 Sent To  
Notes
2020-03-23 14:09:27SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS AND ENGINEERING NEEDS TO BE ELECTRONICALLY
 SIGNED BY THE ENGINEER FOR USE IN ELECTRONICAL PLAN
 REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-05-08 Cont ID  
Sent By jleahy Date 2020-05-08 Time 14:02 Rev Time 0.00
Received By jleahy Date 2020-05-08 Time 10:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-05-06 Cont ID  
Sent By jleahy Date 2020-05-06 Time 12:06 Rev Time 0.00
Received By jleahy Date 2020-05-06 Time 11:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-26 Cont ID  
Sent By jleahy Date 2020-03-26 Time 18:07 Rev Time 0.00
Received By jleahy Date 2020-03-26 Time 18:07 Sent To  
Notes
2020-03-26 18:10:30ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR THIS SIZE SIGN TO LOW.
  
 PLEASE SUBMIT A SIGNED CONTRACXT WITH THE OWNER.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-20 Cont ID  
Sent By rmcphers Date 2020-05-20 Time 11:54 Rev Time 0.00
Received By rmcphers Date 2020-05-07 Time 13:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-06 Cont ID  
Sent By jleahy Date 2020-05-06 Time 12:06 Rev Time 0.00
Received By jleahy Date 2020-04-22 Time 16:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-27 Cont ID  
Sent By lmarchan Date 2020-03-27 Time 14:37 Rev Time 0.00
Received By lmarchan Date 2020-03-19 Time 12:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-05-20 Cont ID  
Sent By rmcphers Date 2020-05-20 Time 11:53 Rev Time 0.00
Received By rmcphers Date 2020-05-20 Time 11:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-04-29 Cont ID  
Sent By rmcphers Date 2020-04-29 Time 16:41 Rev Time 0.00
Received By rmcphers Date 2020-04-29 Time 16:41 Sent To  
Notes
2020-04-29 16:41:36SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By rmcphers Date 2020-03-23 Time 14:09 Rev Time 0.00
Received By rmcphers Date 2020-03-23 Time 14:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-05-15 Cont ID  
Sent By llouie Date 2020-05-15 Time   Rev Time 0.00
Received By llouie Date 2020-05-15 Time   Sent To  
Notes
2020-05-15 11:36:05* APPROVAL OF SIGNAGE DOES NOT CONSTITUTE APPROVAL OF
 USE/ZONING COMPLIANCE FOR BUSINESS.
  
 * MAXIMUM SIGN AREA PERMITTED: 227.035 SQ. FT.
  
 * SIGN AREA PROPOSED: 185.51 SQ. FT.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-04-24 Cont ID  
Sent By llouie Date 2020-04-24 Time   Rev Time 0.00
Received By llouie Date 2020-04-24 Time   Sent To  
Notes
2020-04-24 07:10:42* APPROVAL OF SIGNAGE DOES NOT CONSTITUTE APPROVAL OF
 USE/ZONING COMPLIANCE FOR BUSINESS.
  
 * MAXIMUM SIGN AREA PERMITTED: 227.035 SQ. FT.
  
 * SIGN AREA PROPOSED: 185.44 SQ. FT.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-03-27 Cont ID  
Sent By llouie Date 2020-03-27 Time   Rev Time  
Received By llouie Date 2020-03-27 Time   Sent To  
Notes
2020-03-27 14:31:09* APPROVAL OF SIGNAGE DOES NOT CONSTITUTE APPROVAL OF
 USE/ZONING COMPLIANCE FOR BUSINESS.
  
 * MAXIMUM SIGN AREA PERMITTED: 227.035 SQ. FT.
  
 * SIGN AREA PROPOSED: 185.44 SQ. FT.