Plan Review Details - Permit 20030904
Plan Review Stops For Permit 20030904
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-18 Cont ID  
Sent By pvalenti Date 2020-09-18 Time 08:35 Rev Time 0.00
Received By pvalenti Date 2020-09-18 Time 08:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-09-11 Cont ID  
Sent By pvalenti Date 2020-09-11 Time 15:45 Rev Time 0.00
Received By pvalenti Date 2020-09-11 Time 15:45 Sent To  
Notes
2020-09-11 15:54:38PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, THE INFORMATION PROVIDED ON THE
 SUBMITTED SKETCHES AND SCHEDULES ARE NOT CLEAR AS TO
 THE CHANGES FROM HORIZONTAL ROLLER TO CASEMENT TYPE
 WINDOWS. PLEASE RESUBMIT THE DOCUMENTS, CLEARLY
 INDICATING THE CHANGES ON WINDOW OPENINGS THAT REQUIRE
 CASEMENT WINDOWS SUCH AS WINDOW OPENINGS # 9, 10 & 11.
  
 NOTE: MAKE SURE THAT THE CHANGES INDICATED ON SUBMITTED
 PLANS ARE ACCURATE AND THAT THE REQUIREMENTS OF THE
 HISTORIC REVIEW HAVE BEEN MET.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-19 Cont ID  
Sent By pvalenti Date 2020-03-19 Time 15:26 Rev Time 0.00
Received By pvalenti Date 2020-03-19 Time 15:26 Sent To  
Notes
2020-03-19 15:33:19PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC R 310.2.1, THE MASTER BEDROOM WINDOWS (HORIZONTAL
 ROLLERS) # 9, 10, AND 11 DO NOT MEET THE CLEAR OPENING
 SIZE REQUIREMENTS.
  
 NOTE: ONLY ONE OF THE MASTER BEDROOM WINDOWS NEEDS TO
 MEET THE CLEAR OPENING REQUIREMENT OF 24" HIGH AND 20"
 WIDE.
 PLEASE RESUBMIT WITH A WINDOW THAT WILL MEET THE
 REQUIRED CLEAR OPENING SIZE.

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2020-09-22 Cont ID  
Sent By aborngra Date 2020-09-22 Time 10:30 Rev Time 0.00
Received By aborngra Date 2020-09-22 Time 10:30 Sent To  
Notes
2020-09-22 10:29:59THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
 1. ALL WINDOWS SHALL BE SIZED TO FIT THE ORIGINAL FRAME
 OPENING AND MATCH THE INSET/LOCATION/PLACEMENT/DEPTH OF
 THE ORIGINAL WINDOWS WITHIN THE WINDOW FRAME OPENING.

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2020-09-11 Cont ID  
Sent By aborngra Date 2020-09-11 Time 14:57 Rev Time 0.00
Received By aborngra Date 2020-09-04 Time 13:00 Sent To  
Notes
2020-09-11 14:57:19THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. THE OG(EE) MUNTIN PROFILE FOR THE ES WINDOW IS NOT
 AN APPROPRIATE MUNTIN FOR THIS PROPERTY. REVISE PER
 HISTORIC PRESERVATION BOARD CONDITION TO A PYRAMID
 PROFILE. IF ES WINDOWS DOES NOT OFFER A PYRAMID
 PROFILE, ANOTHER WINDOW MANUFACTURER MAY BE REQUIRED.
 2. REVISE WINDOW SCHEDULE/FLOOR PLAN TO COMPLY WITH
 HISTORIC PRESERVATION BOARD APPROVAL.
  
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By aborngra Date 2020-03-23 Time 11:23 Rev Time 0.00
Received By aborngra Date 2020-03-23 Time 11:23 Sent To PC
Notes
2020-03-23 11:23:47HISTORIC REVIEW FAILED.
 CERTIRFICATE OF APPROPRIATNESS APPLICATION REQUIRED TO
 BE SUBMITTED AND CASE HEARD BY THE HISTORIC
 PRESERVATION BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2020-09-17 Time 17:24 Sent To  
Notes
2020-09-17 17:24:36TO PV DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-11 Cont ID  
Sent By pvalenti Date 2020-09-11 Time 15:55 Rev Time 0.00
Received By pvalenti Date 2020-09-02 Time 15:55 Sent To  
Notes
2020-09-02 17:01:41ROUTED TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-23 Cont ID  
Sent By ccarvaja Date 2020-03-23 Time 16:30 Rev Time 0.00
Received By ccarvaja Date 2020-03-18 Time 12:25 Sent To  
Notes
***NONE***