Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-01 Cont ID  
Sent By rmcphers Date 2020-04-01 Time 16:03 Rev Time 0.00
Received By rmcphers Date 2020-04-01 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-18 Cont ID  
Sent By rmcphers Date 2020-03-18 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2020-03-18 Time 11:56 Sent To  
Notes
2020-03-18 12:48:31FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) TEST REPORT PROVIDED FOR THE "IIC" (47) WITHOUT THE
 CEILING ASSEMBLY DOES NOT MEET THE REQUIRED "IIC"
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50 PER
 FBC 1207.3
 2) ALSO NEED THE FLAME SPREAD TEST REPORT - SEE
 REQUIREMENTS BELOW. (C)
  
 1) FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS. IT IS RECOMMENDED THAT THIS BE RESOLVED
 VIA EMAIL PRIOR TO RESUBMITTAL. EMAIL THE NAME OF THE
 UNDERLAYMENT PROPOSED TO [email protected]. IF THE
 MANUFACTURER HAS ALREADY PROVIDED THE REQUIRED TEST
 REPORTS DIRECTLY TO US, TEST REPORTS DO NOT NEED TO BE
 SUBMITTED WHEN RESUBMITTING.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. PROVIDE A COPY OF THE TEST REPORT.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-01 Cont ID  
Sent By rmcphers Date 2020-04-01 Time 16:04 Rev Time 0.00
Received By rmcphers Date 2020-03-27 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-18 Cont ID  
Sent By rmcphers Date 2020-03-18 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2020-03-17 Time 11:18 Sent To  
Notes
2020-03-18 12:50:27E MAIL SENT TO PERMIT LIBRARY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-03-18 Cont ID  
Sent By rmcphers Date 2020-03-18 Time 12:49 Rev Time 0.00
Received By rmcphers Date 2020-03-18 Time 12:49 Sent To  
Notes
***NONE***