Plan Review Details - Permit 20030695
Plan Review Stops For Permit 20030695
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-08 Cont ID  
Sent By lmarchan Date 2020-04-08 Time 10:15 Rev Time 0.00
Received By lmarchan Date 2020-04-06 Time 09:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-01 Cont ID  
Sent By lmarchan Date 2020-04-01 Time 08:04 Rev Time 0.00
Received By lmarchan Date 2020-03-31 Time 08:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-22 Cont ID  
Sent By shill Date 2020-03-22 Time 12:12 Rev Time 0.00
Received By shill Date 2020-03-16 Time 12:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-04-07 Cont ID  
Sent By medwards Date 2020-04-07 Time 07:27 Rev Time 0.00
Received By medwards Date 2020-04-07 Time 07:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-04-01 Cont ID  
Sent By medwards Date 2020-04-01 Time 07:45 Rev Time 0.00
Received By medwards Date 2020-04-01 Time 07:14 Sent To  
Notes
2020-04-01 07:46:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20030695
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY GAUGE FORM R405 IS MISSING FROM THE
 ENERGY COMPLIANCE SUBMITTAL- SECTION R405.2 FBC EC.
  
 2) PROVIDE THE MANUAL J WORKSHEETS WITH THE AC SYSTEM
 SIZING CALCULATIONS- SECTION R403.7.1 FBC EC.
  
 3) PLEASE SHOW A DETAIL OF HOW YOU ARE GOING TO ANCHOR
 THE A/C UNIT OUTSIDE. FBC RES M1307.2 ANCHORAGE OF
 APPLIANCES.
  
 4) THE CONTRACTOR MUST SIGN AND DATE THE DRAWINGS
 PROVIDED. FBC WPB- 107.3.4.2 CERTIFICATIONS BY
 CONTRACTORS
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-20 Cont ID  
Sent By medwards Date 2020-03-20 Time 09:46 Rev Time 0.00
Received By medwards Date 2020-03-20 Time 09:46 Sent To  
Notes
2020-03-20 10:07:021ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20030695
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 SHEET 7 OF 14: LEVEL 2- PLEASE SHOW THE LOCATION OF THE
 MAIN RETURN GRILL, INCLUDE SIZE AND CFM?S.
 SHEET 7 OF 14: LEVEL 2- RETURN AIR OPENINGS MUST MEET
 FBC RES M1602.2 (4) RETURN AIR SHALL NOT BE TAKEN FROM
 A CLOSET, BATHROOM, TOILET ROOM, KITCHEN, GARAGE,
 MECHANICAL ROOM, BOILER ROOM, FURNACE ROOM OR
 UNCONDITIONED ATTIC.
 SHEET 13 OF 14: LEVEL 1- PLEASE SHOW RETURN CFM IN THE
 CONDITIONED AREA. ALSO SHOW THE SUPPLY AND RETURN
 DUCTWORK WITH SIZES. SHEET 14 OF 14: PLEASE SHOW BOTH
 SUPPLY AND RETURN REGISTERS AND CFM?S FOR EACH.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-04-07 Cont ID  
Sent By medwards Date 2020-04-07 Time 07:28 Rev Time 0.00
Received By medwards Date 2020-04-07 Time 07:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-04-01 Cont ID  
Sent By medwards Date 2020-04-01 Time 07:46 Rev Time 0.00
Received By medwards Date 2020-04-01 Time 07:46 Sent To  
Notes
2020-04-01 07:47:27PLEASE SEE MECHANICAL COMMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-03-22 Cont ID  
Sent By shill Date 2020-03-22 Time 12:12 Rev Time 0.00
Received By shill Date 2020-03-22 Time 12:12 Sent To  
Notes
***NONE***