Plan Review Details - Permit 20030645
Plan Review Stops For Permit 20030645
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By ppetty Date 2020-03-23 Time 08:47 Rev Time 0.00
Received By ppetty Date 2020-03-23 Time 08:47 Sent To  
Notes
2020-03-23 08:48:12SEE F/D NOTE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-16 Cont ID  
Sent By pleduc Date 2020-03-16 Time   Rev Time 0.00
Received By pleduc Date 2020-03-16 Time 14:58 Sent To  
Notes
2020-03-16 14:59:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF THIS BE A LOCAL SYSTEM
 ONLY. THERE IS NO INDICATION OF WHAT TYPE OF FIRE ALARM
 SYSTEM IS EXISTING.
  
 PER NFPA 1 AND 101
  
 13.7.1.9.2.1* ELEVATOR LOBBY, HOISTWAY, AND ASSOCIATED
 MACHINE
 ROOM SMOKE DETECTORS USED SOLELY FOR ELEVATOR RECALL,
 AND HEAT
 DETECTORS USED SOLELY FOR ELEVATOR POWER SHUTDOWN,
 SHALL NOT BE
 REQUIRED TO ACTIVATE THE BUILDING EVACUATION ALARM IF
 THE POWER
 SUPPLY AND INSTALLATION WIRING TO SUCH DETECTORS ARE
 MONITORED BY
 THE BUILDING FIRE ALARM SYSTEM, AND IF THE ACTIVATION
 OF SUCH
 DETECTORS INITIATES A SUPERVISORY SIGNAL AT A
 CONSTANTLY ATTENDED
 LOCATION. [101: 9.6.3.2.1]
  
 PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-23 Cont ID  
Sent By ppetty Date 2020-03-23 Time 08:48 Rev Time 0.00
Received By ppetty Date 2020-03-12 Time 10:51 Sent To  
Notes
2020-03-13 10:51:20ROUTED TO FIRE INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved