Plan Review Details - Permit 20030440
Plan Review Stops For Permit 20030440
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-04-09 Cont ID  
Sent By rmcphers Date 2020-04-09 Time 13:19 Rev Time 0.00
Received By rmcphers Date 2020-04-09 Time 13:19 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-03-18 Cont ID  
Sent By rmcphers Date 2020-03-18 Time 11:39 Rev Time 0.00
Received By rmcphers Date 2020-03-18 Time 11:39 Sent To  
Notes
2020-03-18 11:40:24ASBESTOS ? PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM
 THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-04-29 Cont ID  
Sent By rmcphers Date 2020-04-29 Time 11:03 Rev Time 0.00
Received By rmcphers Date 2020-04-29 Time 11:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-09 Cont ID  
Sent By rmcphers Date 2020-04-09 Time 13:18 Rev Time 0.00
Received By rmcphers Date 2020-04-09 Time 13:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-18 Cont ID  
Sent By rmcphers Date 2020-03-18 Time 11:40 Rev Time 0.00
Received By rmcphers Date 2020-03-18 Time 11:21 Sent To  
Notes
2020-03-18 11:39:13REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE CHECK-OUT COUNTER HEIGHT TO COMPLY
 WITH FBC ACCESSIBILITY 904
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-26 Cont ID  
Sent By jleahy Date 2020-03-26 Time 13:01 Rev Time 0.00
Received By jleahy Date 2020-03-26 Time 10:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-04-23 Cont ID  
Sent By sathomas Date 2020-04-23 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-04-23 Time 00:00 Sent To M
Notes
2020-04-23 15:07:56PROVISO:
  
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM, HOOD SUPPRESSION, AND/OR FIRE ALARM SYSTEM.
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-08 Cont ID  
Sent By sathomas Date 2020-04-08 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-04-08 Time 00:00 Sent To M
Notes
2020-04-08 13:29:43PROVISO:
  
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM, HOOD SUPPRESSION, AND/OR FIRE ALARM SYSTEM.
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-19 Cont ID  
Sent By sathomas Date 2020-03-19 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-03-19 Time 00:00 Sent To M
Notes
2020-03-19 14:42:36PROVISO:
  
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM, HOOD SUPPRESSION, AND/OR FIRE ALARM SYSTEM.
  
 S. THOMAS
 561-804-4728

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2020-04-30 Cont ID  
Sent By jpearson Date 2020-04-30 Time 09:17 Rev Time 0.00
Received By jpearson Date 2020-04-30 Time 09:17 Sent To  
Notes
2020-04-30 09:17:42REVIEWED BY JERRY SMITH.
  
 GAS COMMENTS: APPROVED; SEE BELOW
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PLEASE NOTE; PLAN SHEET P2 IS THE SAME AS P1 MAKING P2
 REDUNDANT. SEE NOTES ON PLANS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 20030440 2380 PALM BEACH LAKES BLVD
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-04-30 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-20 Time 15:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-04-09 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-07 Time 09:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By shill Date 2020-03-31 Time 15:30 Rev Time 0.00
Received By shill Date 2020-03-17 Time 16:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-04-09 Cont ID  
Sent By medwards Date 2020-04-09 Time 07:22 Rev Time 0.00
Received By medwards Date 2020-04-09 Time 07:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-26 Cont ID  
Sent By medwards Date 2020-03-26 Time 14:32 Rev Time 0.00
Received By medwards Date 2020-03-26 Time 12:18 Sent To  
Notes
2020-03-26 14:33:541ST REVIEW FBC-2017 MECHANICAL
 PERMIT - 20030440
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 PLEASE PROVIDE M SHEETS SHOWING THE MECHANICAL WORK
 BEING DONE. PLEASE SHOW MECHANICAL CALCULATIONS FOR THE
 MECHANICAL SYSTEM AND THE NEW EQUIPMENT BEING
 INSTALLED. THE NEW DISHWASHER SHOULD BE IN THESE
 CALCULATIONS. FBC FS 107.2; FBC M 507.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-04-30 Cont ID  
Sent By jpearson Date 2020-04-30 Time 09:16 Rev Time 0.00
Received By jpearson Date 2020-04-30 Time 08:39 Sent To  
Notes
2020-04-30 08:39:51REVIEWED BY JERRY SMITH.
  
 PLUMBING COMMENTS: APPROVED; SEE BELOW
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PLEASE NOTE; PLAN SHEET P2 IS THE SAME AS P1 MAKING P2
 REDUNDANT. SEE NOTES ON PLANS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 20030440 2380 PALM BEACH LAKES BLVD
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-04-09 Cont ID  
Sent By jpearson Date 2020-04-09 Time 16:51 Rev Time 0.00
Received By jpearson Date 2020-04-09 Time 14:05 Sent To  
Notes
2020-04-09 14:06:03REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20030440 2380 PALM BEACH LAKES BLVD
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 1. REGARDING RESPONSES FOR REVIEW COMMENTS 1 AND 2, NEW
 PLAN SHEETS P2 AND P3 HAVE NOT BEEN UPLOADED.
 2. REGARDING COMMENT 3, THE TRENCH DETAIL SHOWS CRUSHED
 ROCK AROUND THE PIPE. PER FBC PL 306.3 LOOSE EARTH FREE
 FROM ROCKS, BROKEN CONCRETE AND FROZEN CHUNKS SHALL BE
 PLACED IN THE TRENCH IN 6-INCH (152 MM) LAYERS AND
 TAMPED IN PLACE UNTIL THE CROWN OF THE PIPE IS COVERED
 BY 12 INCHES OF TAMPED EARTH. PLEASE CORRECT.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 20030440 2380 PALM BEACH LAKES BLVD
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-25 Cont ID  
Sent By shill Date 2020-03-25 Time 18:25 Rev Time 0.00
Received By shill Date 2020-03-25 Time 15:37 Sent To  
Notes
2020-03-25 18:25:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20030440 2380 PALM BEACH LAKES BLVD
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. RE: PLAN SHEET P2; THE PLUMBING PLAN VIEW IS VERY
 BUSY AND DIFFICULT TO FOLLOW. PER WPB FBC 107.2.1,
 PROVIDE A SANITARY AND WATER RISER DIAGRAM CLEARLY
 INDICATING EXISTING PIPING AND NEW PIPING AND EQUIPMENT
 BEING SERVICED.
 2. THERE IS A GAS PIPING MATERIAL SPEC ON P1.1 AND
 REMOVAL AND RE INSTALLATION OF AN EXISTING RICE COOKER.
 IS THERE GAS PIPING TO THE RICE COOKER? PER WPB FBC
 107.2.1, PROVIDE CLARIFICATION. IF A GAS CONNECTION IS
 INVOLVED PROVIDE GUIDANCE FOR DISCONNECT AND RE
 CONNECTION IN SCOPE. IF THERE IS NO GAS CONNECTION IN
 THE SCOPE THEN REMOVE REFERENCE TO GAS PIPING FROM THE
 PLANS.
 3. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 20030440 2380 PALM BEACH LAKES BLVD
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-04-29 Cont ID  
Sent By rmcphers Date 2020-04-29 Time 11:06 Rev Time 0.00
Received By rmcphers Date 2020-04-29 Time 11:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-09 Cont ID  
Sent By medwards Date 2020-04-09 Time 07:21 Rev Time 0.00
Received By medwards Date 2020-04-09 Time 07:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-03-18 Cont ID  
Sent By rmcphers Date 2020-03-18 Time 11:41 Rev Time 0.00
Received By rmcphers Date 2020-03-18 Time 11:41 Sent To  
Notes
***NONE***