2020-03-10 07:34:07 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #20030401 |
| 3/10/20 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 201 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THIS PROJECT APPEARS TO BE A NEW INSTALLATION OF AIR |
| CONDITIONING IN A PREVIOUSLY UNCONDITIONED SPACE. |
| PLEASE PROVIDE A BASIC PLAN SHOWING THE LOCATIONS OF |
| THE NEW MINI SPLIT CONDENSER AND AIR HANDLER, AND |
| IDENTIFIY THE ROOM OR SPACE NOW BEING CONDITIONED. |
| |
| 2) REFER TO SECTION R503.2 FBC EC AND PROVIDE ENERGY |
| CALACULATIONS FOR THE NEW CONDITIONED SPACE- SEE |
| SECTION R101.5.1.1 AND PROVIDE A COMPLIANCE REPORT |
| USING EITHER THE PRESCRIPTIVE OR PERFORMANCE BASED |
| METHODS. |
| |
| 3) PROVIDE AC COOLING AND HEATING CALCULATIONS (HEAT |
| LOADS)- SECTION R403.7 FBC EC. |
| |
| 4) SUBMIT AN ELECTRICAL PLAN AND AN ELECTRICAL |
| SUB-PERMIT. PLEASE NOTE THE ELECTRICAL CONTRACT |
| SUBMITTED WITH THE APPLICATION ALSO INDICATES |
| INSTALLATION OF DISCONNECTS AND CIRCUITRY FOR A NW |
| TANKLESS WATER HEATER. PLEASE NOTE THAT SEPARATE |
| PLUMBING AND ELECTRICAL PERMITS ARE REQUIRED FOR THAT |
| INSTALLATION- SECTION 105.1 WPB. |
| |
| 5) PLEASE NOTE TWO COPIES OF PLANS AND DOCUMENTS ARE |
| REQUIRED- SECTION 107.2.1 WPB. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |