Plan Review Details - Permit 20030383
Plan Review Stops For Permit 20030383
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-30 Cont ID  
Sent By jpearson Date 2020-03-30 Time 13:24 Rev Time 0.00
Received By jpearson Date 2020-03-30 Time 13:24 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-30 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-09 Time 15:54 Sent To  
Notes
2020-03-09 15:54:28ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-03-30 Cont ID  
Sent By hmoser Date 2020-03-30 Time 09:11 Rev Time 0.00
Received By hmoser Date 2020-03-27 Time 12:24 Sent To E
Notes
2020-03-30 09:11:16PASS PROVISO
 1) PROVIDE ENGINEERING TO MEET SECTION 301.15 WIND
 RESISTANCE
 ON CHILLER AT FIRST INSPECTION. 2017 FBC (M)
 2) PROVIDE SIZE OF THREADED ROD ON DETAIL # 3 PAGE M401
 OF PLAN AT FIRST INSPECTION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  