Plan Review Details - Permit 20030355
Plan Review Stops For Permit 20030355
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-18 Cont ID  
Sent By pvalenti Date 2020-05-18 Time 11:34 Rev Time 0.00
Received By pvalenti Date 2020-05-18 Time 09:49 Sent To  
Notes
2020-05-18 11:45:58PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S.
 SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING:
 BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO
 BE USED.
 AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE
 W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO
 VERIFY THE WELDERS QUALIFICATION AND CERTIFICATION AS
 IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-08 Cont ID  
Sent By pvalenti Date 2020-05-08 Time 15:14 Rev Time 0.00
Received By pvalenti Date 2020-05-08 Time 15:14 Sent To  
Notes
2020-05-08 15:54:29PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 1. FBC B 107.2.1, THE ARCHITECTUAL DRAWINGS DO NOT HAVE
 THE DESIGNER'S NAME AND SIGNATURE.
 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES & 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES &
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 2. FBC B 107.2.1 INDICATE WHERE THE WINDOW WALL SYSTEM
 ( NOA NO.19-0326.07 ) WILL BE INSTALLED.
  
 3. FBC B 107.2.1 PLEASE CLARIFY IF THE STEEL PLATE
 CONNECTION DETAIL 13/S2 REQUIRES FASTENER SPACING OF
 12" OR 16" O.C.
  
 4. FBC B 107.2.1 PLEASE CLARIFY THE WELD SIZES ON PAGES
 S-2 AND S-3.1 AS THE DETAILS CALL FOR ALL AROUND FILLET
 WELDS, 1" WELD SIZE/THICKNESS. THAT WELD SIZE IS
 THICKER THAN THE BASE MATERIALS.
  
 IN ADDITION TO CORRECTING THE WELD SIZE ON THE PLANS,
 AT TIME OF INSPECTION PLEASE PROVIDE THE FOLLOWING:
 AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S.
 SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING:
 BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO
 BE USED.
 AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE
 W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO
 VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS
 IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-19 Cont ID  
Sent By rmcdouga Date 2020-03-19 Time 17:47 Rev Time 0.00
Received By rmcdouga Date 2020-03-19 Time 17:47 Sent To  
Notes
2020-03-19 14:33:11PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE
 ARCHITECTURAL DRAWINGS DO NOT HAVE THE DESIGNER'S NAME
 AND SIGNATURE.
  
 2) THE OCCUPANCY TYPE FOR THIS STRUCTURE IS SINGLE
 FAMILY RATHER THAN R-3. FBC RESIDENTIAL SECTION R101.2
  
 3) PROVIDE EXTERIOR ELEVATION DRAWINGS OF THE BUILDING.
 FBC 107.2.1.2
  
 4) PRODUCT APPROVALS WERE SUBMITTED FOR MULTIPLE WINDOW
 TYPE. IDENTIFY THE WINDOW TYPES AND THEIR LOCATIONS ON
 THE PLANS. FBC 107.2.1
  
 5) THE PRODUCT APPROVALS FOR THE WINDOWS, MULLIONS AND
 DOORS HAVE DIFFERENT DESIGN PRESSURES BASED ON SIZE,
 GLASS TYPE, STYLE REINFORCEMENT, ETC. CIRCLE THE
 SPECIFIC ITEMS THAT APPLY TO THE COMPONENTS THAT WILL
 BE USED FOR THIS PROJECT. FBC 107.2.1.2 AND R101.2
  
 6) INDICATE WHERE THE WINDOW WALL SYSTEM ( NOA
 NO.19-0326.07 ) WILL BE INSTALLED. FBC 107.2.1
  
 7) THE PRODUCT APPROVAL FOR THE SINGLE HUNG WINDOWS HAS
 A MAXIMUM DESIGN PRESSURE OF +60.0 PSF, -80 PSF. THE
 WINDOW/DOOR SCHEDULE ON A2.0 HAS THE OPPOSITE, +80 PSF,
 -60 PSF. PLEASE CORRECT.
  
 8) THE WINDOW/DOOR SCHEDULE ON A2.0 IS BLANK FOR DOOR
 NUMBER 4 AND NO DESIGN PRESSURES ARE PROVIDED FOR THE
 SLIDING GLASS DOORS. WINDOWS #3 AND #5 ARE DRAWN AS
 TWIN WINDOWS WITH A MULL AND THE SCHEDULE HAS N FOR NO
 MULLION. THERE APPEARS TO BE MULTIPLE ERRORS IN THIS
 SCHEDULE. PLEASE CORRECT IT. FBC 107.2.1
  
 9) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-05-18 Cont ID  
Sent By ppetty Date 2020-05-18 Time 08:30 Rev Time 0.00
Received By ppetty Date 2020-05-18 Time 08:30 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-08 Cont ID  
Sent By ppetty Date 2020-05-08 Time 09:46 Rev Time 0.00
Received By ppetty Date 2020-05-08 Time 09:41 Sent To  
Notes
2020-05-08 09:46:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2)
  
 3)
  
 4)
  
 5) SEVERAL OF THE REMODELED AREAS AND THE NEWLY
 ENCLOSED AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR RECEPTACLE OUTLETS. RECEPTACLES SHALL
 BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE E3901.2.1 PROPOSED GREAT ROOM AND BAR
 ARE
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 PLANS EXAMINER
 561-805-6742
 [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By rmcdouga Date 2020-03-23 Time 16:36 Rev Time 0.00
Received By rmcdouga Date 2020-03-23 Time 16:36 Sent To I
Notes
2020-03-23 13:03:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
  
 3) PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 4) PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
  
 5) SEVERAL OF THE REMODELED AREAS AND THE NEWLY
 ENCLOSED AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR RECEPTACLE OUTLETS. RECEPTACLES SHALL
 BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC
 210.52; FBC RE E3901.2.1
  
 6) PLAN DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE
 LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC
 210.52(F); FBC RE E3901.8
  
 7) BATHROOMS. A GFCI PROTECTED RECEPTACLE OUTLET ON A
 20 AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR
 PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON
 THE SIDE OR FACE OF THE BASIN CABINET. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE E3901.6
  
 8) PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE
 OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING
 UNIT. NEC 210.52(E)(3); FBC RE E3901.7
  
 9) ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS
 SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
  
 10) PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
  
 11) PROVIDE SMOKE ALARM ON EACH STORY OF THE DWELLING.
 (NEAR THE BOTTOM OF THE STAIRS.) FBC RE R314.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 ROBERT MCDOUGAL
 COMBINATION PLANS EXAMINER
 561-805-6714
 [email protected]
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2020-05-18 Cont ID  
Sent By tklarge Date 2020-05-18 Time 14:50 Rev Time 0.00
Received By tklarge Date 2020-05-18 Time 14:50 Sent To  
Notes
2020-05-18 14:51:59A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-05-08 Cont ID  
Sent By tklarge Date 2020-05-08 Time 06:32 Rev Time 0.00
Received By tklarge Date 2020-05-08 Time 06:32 Sent To  
Notes
2020-05-08 06:59:551) SHOW THE LOCATION OF THE GAS WATER HEATERS ON THE
 PLAN. IF THE WATER HEATERS ARE TANKLESS, THEY SHALL BE
 INSTALLED PER THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS WHICH USUALLY REQUIRE 4 FEET FROM ANY
 OPERABLE DORRS, WINDOWS OR BUILDING OPENINGS.
 2) SHOW THE LOCATION OF THE FIREPLACE ON THE FLOOR
 PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
 3) REVISE THE BTU LOAD TO READ 633,000 BTU'S.
 4) THE 1 INCH CSST TO THE FIREPLACE APPEARS TO BE
 UNDERSIZED PER THE REFERENCED SIZING TABLE. INDICATE
 THE EHD OF THE CSST OFR THIS LINE.
 5) SUBMIT THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING SHOWN ON THE GAS
 RISER.
 6) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 FIREPLACE, DRYER, AND RANGE.PER THE 2017 FBC-FUEL GAS
 CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR 2017 FBC-RES.
 SEC. G 2407.1 AND G2439.4 (CLOTHES DRYERS).
 7) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 8) THE EXTERIOR GRILL SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTALLATION REQUIREMENTS. A
 HOOD MAY BE REQUIRED ABOVE THE GRILL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-18 Cont ID  
Sent By tklarge Date 2020-05-18 Time 14:52 Rev Time 0.00
Received By tklarge Date 2020-05-15 Time 12:26 Sent To  
Notes
2020-05-15 12:27:49ROUTED TO R37

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-08 Cont ID  
Sent By skennedy Date 2020-05-08 Time 16:00 Rev Time 0.00
Received By skennedy Date 2020-05-07 Time 15:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-23 Cont ID  
Sent By rmcdouga Date 2020-03-23 Time 16:36 Rev Time 0.00
Received By rmcdouga Date 2020-03-06 Time 13:29 Sent To  
Notes
2020-03-09 13:29:09R37

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-05-18 Cont ID  
Sent By pvalenti Date 2020-05-18 Time 10:49 Rev Time 0.00
Received By pvalenti Date 2020-05-08 Time 15:34 Sent To  
Notes
2020-05-18 11:34:21PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 IMPACT FEE REVIEW APPROVED
  
 COMPLETED BY COUNTY:
  
 PLAN STAMPED BY COUNTY AND RECEIPT PROVIDED,
 MU-2020-016053-0000.
2020-05-08 15:34:37CHECKED OUT A SET TO DEAN TO TAKE TO PBC IMPACT FEE
 OFFICE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-03-19 Cont ID  
Sent By rmcdouga Date 2020-03-19 Time 10:37 Rev Time 0.00
Received By rmcdouga Date 2020-03-19 Time 10:37 Sent To  
Notes
2020-03-19 10:42:02PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPEDED PLANS AND A COPY OF THE PAID RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-05-18 Cont ID  
Sent By pvalenti Date 2020-05-18 Time 11:34 Rev Time 0.00
Received By pvalenti Date 2020-05-18 Time 09:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-05-08 Cont ID  
Sent By hmoser Date 2020-05-08 Time 13:32 Rev Time 0.00
Received By hmoser Date 2020-05-08 Time 13:20 Sent To  
Notes
2020-05-08 14:01:52PLAN DENIED
 1) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS ANS
 ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE
 FOR THE DESIGN. 2017 CITY AMENDMENTS.
 2) BEDROOM #3 PROVIDE RETURN DUCT SIZE.
 3) PROVIDE DUCT SIZE ON A/C # 1 TRUNK LINE
 4) MECHANICAL PLAN AND PROPOSED FLOOR PLAN DO NOT
 MATCH.
 PER SECTION 107.2.1.3 CITY AMENDMENTS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By medwards Date 2020-03-17 Time 14:06 Rev Time 0.00
Received By medwards Date 2020-03-13 Time 13:39 Sent To  
Notes
2020-03-17 14:07:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20030355
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IDENTIFY AHU?S ON DRAWINGS.
  
 2) PLEASE PROVIDE A DETAIL DRAWING OF THE RETURN DUCT
 IN HALL THAT BEDROOM 2 AND 3 ARE DUCTED TO, THE A
 SHEETS SHOW THIS AREA IS A CLOSET. RETURN AIR CANNOT
 COME FROM A CLOSET OR THE MASTER BATH UPSTAIRS.
 (. SEE FBCEC 103.2 INFORMATION ON CONSTRUCTION
 DOCUMENTS.)(SEE FBC RES M1602.2 (4) RETURN AIR SHALL
 NOT BE TAKEN FROM A CLOSET, BATHROOM, TOILET ROOM,
 KITCHEN, GARAGE, MECHANICAL ROOM, BOILER ROOM, FURNACE
 ROOM OR UNCONDITIONED ATTIC.
  
 3) AHU?S IN ATTIC MUST MEET SECTION FBC RES M1305.1.3
 APPLIANCES IN ATTIC. SEE ALSO FBC EC R403.3.6
  
 4) DUCTWORK IN THE GARAGE MUST MEET FBC RES R302.5.2
  
 5) PROVIDE SPEC SHEETS FOR THE HOOD AND THE RANGE, ALSO
 PROVIDE FUEL SOURCE FOR THE NEW RANGE.
 (. SEE FBCEC 103.2 INFORMATION ON CONSTRUCTION
 DOCUMENTS.)
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-05-08 Cont ID  
Sent By tklarge Date 2020-05-08 Time 06:32 Rev Time 0.00
Received By tklarge Date 2020-05-08 Time 06:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-19 Cont ID  
Sent By rmcdouga Date 2020-03-19 Time 13:25 Rev Time 0.00
Received By rmcdouga Date 2020-03-19 Time 13:25 Sent To  
Notes
2020-03-19 14:01:44PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY PLUMBING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT PLUMBING RISER PLANS.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-05-07 Cont ID  
Sent By llouie Date 2020-05-07 Time   Rev Time 0.00
Received By llouie Date 2020-05-07 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By llouie Date 2020-03-17 Time   Rev Time  
Received By llouie Date 2020-03-17 Time   Sent To  
Notes
2020-03-17 15:40:15** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED, SIGNED AND SEALED SURVEY OF THE PROPERTY
 IS REQUIRED.
  
 2.) CHANGES DETECTED TO THE EXISTING BUILDING
 FOOTPRINT. A SITE PLAN, SHOWING THE PROPOSED
 IMPROVEMENT AND DISTANCE FROM THE PROPERTY LINE(S) IS
 REQUIRED. INCLUDE LOCATION AND SETBACKS FOR NEW A/C
 UNIT.
  
 3.) ONLY ONE KITCHEN IS PERMITTED IN THE RESIDENCE.
 THERE ARE TWO (2) KITCHENS IN THE PROPOSED FIRST FLOOR
 PLAN.
  
 4.) PROPOSED BUILDING ELEVATIONS MISSING.
  
 5.) ALL ARCHITECTURAL PLANS MUST BE SIGNED AND SEALED
 BY A FLORIDA REGISTERED ARCHITECT.
  
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * DOES NOT TRIGGER THE 50% THRESHOLD FOR LANDSCAPE
 IMPROVEMENTS (VALUE OF SCOPE OF WORK: $108,000; VALUE
 OF IMPROVEMENT (PER 2019 PAPA): $267,186)
  
 * ZONE: SF7
  