Plan Review Stops For Permit 20030355 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2020-05-18 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-05-18 |
Time |
11:34 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-05-18 |
Time |
09:49 |
Sent To |
|
|
Notes |
2020-05-18 11:45:58 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE | | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. | | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: | | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO | | BE USED. | | AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE | | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE | | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO | | VERIFY THE WELDERS QUALIFICATION AND CERTIFICATION AS | | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2020-05-08 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-05-08 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-05-08 |
Time |
15:14 |
Sent To |
|
|
Notes |
2020-05-08 15:54:29 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | 2ND BUILDING REVIEW DENIED: | | | | 1. FBC B 107.2.1, THE ARCHITECTUAL DRAWINGS DO NOT HAVE | | THE DESIGNER'S NAME AND SIGNATURE. | | THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A | | REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY | | CHAPTER 471, FLORIDA STATUTES & 61G15 FLORIDA | | ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES & | | 61G1 FLORIDA ADMINISTRATIVE CODE. | | | | 2. FBC B 107.2.1 INDICATE WHERE THE WINDOW WALL SYSTEM | | ( NOA NO.19-0326.07 ) WILL BE INSTALLED. | | | | 3. FBC B 107.2.1 PLEASE CLARIFY IF THE STEEL PLATE | | CONNECTION DETAIL 13/S2 REQUIRES FASTENER SPACING OF | | 12" OR 16" O.C. | | | | 4. FBC B 107.2.1 PLEASE CLARIFY THE WELD SIZES ON PAGES | | S-2 AND S-3.1 AS THE DETAILS CALL FOR ALL AROUND FILLET | | WELDS, 1" WELD SIZE/THICKNESS. THAT WELD SIZE IS | | THICKER THAN THE BASE MATERIALS. | | | | IN ADDITION TO CORRECTING THE WELD SIZE ON THE PLANS, | | AT TIME OF INSPECTION PLEASE PROVIDE THE FOLLOWING: | | AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE | | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. | | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: | | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO | | BE USED. | | AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE | | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE | | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO | | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS | | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-03-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-03-19 |
Time |
17:47 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-03-19 |
Time |
17:47 |
Sent To |
|
|
Notes |
2020-03-19 14:33:11 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. THE | | ARCHITECTURAL DRAWINGS DO NOT HAVE THE DESIGNER'S NAME | | AND SIGNATURE. | | | | 2) THE OCCUPANCY TYPE FOR THIS STRUCTURE IS SINGLE | | FAMILY RATHER THAN R-3. FBC RESIDENTIAL SECTION R101.2 | | | | 3) PROVIDE EXTERIOR ELEVATION DRAWINGS OF THE BUILDING. | | FBC 107.2.1.2 | | | | 4) PRODUCT APPROVALS WERE SUBMITTED FOR MULTIPLE WINDOW | | TYPE. IDENTIFY THE WINDOW TYPES AND THEIR LOCATIONS ON | | THE PLANS. FBC 107.2.1 | | | | 5) THE PRODUCT APPROVALS FOR THE WINDOWS, MULLIONS AND | | DOORS HAVE DIFFERENT DESIGN PRESSURES BASED ON SIZE, | | GLASS TYPE, STYLE REINFORCEMENT, ETC. CIRCLE THE | | SPECIFIC ITEMS THAT APPLY TO THE COMPONENTS THAT WILL | | BE USED FOR THIS PROJECT. FBC 107.2.1.2 AND R101.2 | | | | 6) INDICATE WHERE THE WINDOW WALL SYSTEM ( NOA | | NO.19-0326.07 ) WILL BE INSTALLED. FBC 107.2.1 | | | | 7) THE PRODUCT APPROVAL FOR THE SINGLE HUNG WINDOWS HAS | | A MAXIMUM DESIGN PRESSURE OF +60.0 PSF, -80 PSF. THE | | WINDOW/DOOR SCHEDULE ON A2.0 HAS THE OPPOSITE, +80 PSF, | | -60 PSF. PLEASE CORRECT. | | | | 8) THE WINDOW/DOOR SCHEDULE ON A2.0 IS BLANK FOR DOOR | | NUMBER 4 AND NO DESIGN PRESSURES ARE PROVIDED FOR THE | | SLIDING GLASS DOORS. WINDOWS #3 AND #5 ARE DRAWN AS | | TWIN WINDOWS WITH A MULL AND THE SCHEDULE HAS N FOR NO | | MULLION. THERE APPEARS TO BE MULTIPLE ERRORS IN THIS | | SCHEDULE. PLEASE CORRECT IT. FBC 107.2.1 | | | | 9) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2020-05-18 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2020-05-18 |
Time |
08:30 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2020-05-18 |
Time |
08:30 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2020-05-08 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2020-05-08 |
Time |
09:46 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2020-05-08 |
Time |
09:41 |
Sent To |
|
|
Notes |
2020-05-08 09:46:43 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | 2) | | | | 3) | | | | 4) | | | | 5) SEVERAL OF THE REMODELED AREAS AND THE NEWLY | | ENCLOSED AREAS DO NOT COMPLY WITH THE WALL SPACING | | REQUIREMENTS FOR RECEPTACLE OUTLETS. RECEPTACLES SHALL | | BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY | | ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 | | FEET FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC | | 210.52; FBC RE E3901.2.1 PROPOSED GREAT ROOM AND BAR | | ARE | | | | | | | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | SINCERELY, | | | | PHIL PETTY | | PLANS EXAMINER | | 561-805-6742 | | [email protected] | | | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-03-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-03-23 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-03-23 |
Time |
16:36 |
Sent To |
I |
|
Notes |
2020-03-23 13:03:34 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | 2) PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, | | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF | | SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE | | E3602.2 | | | | 3) PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 | | | | 4) PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, | | E3609.3; WPB FBC 107.2.1 | | | | 5) SEVERAL OF THE REMODELED AREAS AND THE NEWLY | | ENCLOSED AREAS DO NOT COMPLY WITH THE WALL SPACING | | REQUIREMENTS FOR RECEPTACLE OUTLETS. RECEPTACLES SHALL | | BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY | | ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 | | FEET FROM A RECEPTACLE OUTLET. PROVIDE CORRECTION. NEC | | 210.52; FBC RE E3901.2.1 | | | | 6) PLAN DOES NOT SHOW THE 20 AMP RECEPTACLE IN THE | | LAUNDRY REQUIRED PER CODE. PROVIDE CORRECTION. NEC | | 210.52(F); FBC RE E3901.8 | | | | 7) BATHROOMS. A GFCI PROTECTED RECEPTACLE OUTLET ON A | | 20 AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. | | THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR | | PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN | | COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON | | THE SIDE OR FACE OF THE BASIN CABINET. PROVIDE | | CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE E3901.6 | | | | 8) PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE | | OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING | | UNIT. NEC 210.52(E)(3); FBC RE E3901.7 | | | | 9) ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS | | SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC | | 210.8(A)(9); FBC RE E3902.9 | | | | 10) PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | 210.8(D); FBC RE E3902.10 | | | | 11) PROVIDE SMOKE ALARM ON EACH STORY OF THE DWELLING. | | (NEAR THE BOTTOM OF THE STAIRS.) FBC RE R314.3 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | SINCERELY, | | | | ROBERT MCDOUGAL | | COMBINATION PLANS EXAMINER | | 561-805-6714 | | [email protected] | | | | | | | | | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2020-05-18 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-05-18 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-05-18 |
Time |
14:50 |
Sent To |
|
|
Notes |
2020-05-18 14:51:59 | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A | | CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE | | COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS | | WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1. | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | FBC-R, SEC. G2404.3. | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | GAS SEC. 301.3. | | | | A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2020-05-08 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-05-08 |
Time |
06:32 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-05-08 |
Time |
06:32 |
Sent To |
|
|
Notes |
2020-05-08 06:59:55 | 1) SHOW THE LOCATION OF THE GAS WATER HEATERS ON THE | | PLAN. IF THE WATER HEATERS ARE TANKLESS, THEY SHALL BE | | INSTALLED PER THE MANUFACTURER'S INSTALLATION | | INSTRUCTIONS WHICH USUALLY REQUIRE 4 FEET FROM ANY | | OPERABLE DORRS, WINDOWS OR BUILDING OPENINGS. | | 2) SHOW THE LOCATION OF THE FIREPLACE ON THE FLOOR | | PLAN. WPB AMEND. TO FBC SEC. 107.2.1. | | 3) REVISE THE BTU LOAD TO READ 633,000 BTU'S. | | 4) THE 1 INCH CSST TO THE FIREPLACE APPEARS TO BE | | UNDERSIZED PER THE REFERENCED SIZING TABLE. INDICATE | | THE EHD OF THE CSST OFR THIS LINE. | | 5) SUBMIT THE CORRESPONDING EHD NUMBER OF THE | | CORRUGATED STAINLESS STEEL TUBING SHOWN ON THE GAS | | RISER. | | 6) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE | | FIREPLACE, DRYER, AND RANGE.PER THE 2017 FBC-FUEL GAS | | CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR 2017 FBC-RES. | | SEC. G 2407.1 AND G2439.4 (CLOTHES DRYERS). | | 7) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | 8) THE EXTERIOR GRILL SHALL BE INSTALLED IN ACCORDANCE | | WITH THE MANUFACTURER'S INSTALLATION REQUIREMENTS. A | | HOOD MAY BE REQUIRED ABOVE THE GRILL. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-05-18 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-05-18 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-05-15 |
Time |
12:26 |
Sent To |
|
|
Notes |
2020-05-15 12:27:49 | ROUTED TO R37 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-05-08 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2020-05-08 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2020-05-07 |
Time |
15:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-03-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-03-23 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-03-06 |
Time |
13:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2020-05-18 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-05-18 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-05-08 |
Time |
15:34 |
Sent To |
|
|
Notes |
2020-05-18 11:34:21 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | IMPACT FEE REVIEW APPROVED | | | | COMPLETED BY COUNTY: | | | | PLAN STAMPED BY COUNTY AND RECEIPT PROVIDED, | | MU-2020-016053-0000. | 2020-05-08 15:34:37 | CHECKED OUT A SET TO DEAN TO TAKE TO PBC IMPACT FEE | | OFFICE. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2020-03-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-03-19 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-03-19 |
Time |
10:37 |
Sent To |
|
|
Notes |
2020-03-19 10:42:02 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | RETURN STAMPEDED PLANS AND A COPY OF THE PAID RECEIPT | | AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2020-05-18 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2020-05-18 |
Time |
11:34 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2020-05-18 |
Time |
09:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2020-05-08 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2020-05-08 |
Time |
13:32 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2020-05-08 |
Time |
13:20 |
Sent To |
|
|
Notes |
2020-05-08 14:01:52 | PLAN DENIED | | 1) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION | | DOCUMENTS. | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS ANS | | ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE | | FOR THE DESIGN. 2017 CITY AMENDMENTS. | | 2) BEDROOM #3 PROVIDE RETURN DUCT SIZE. | | 3) PROVIDE DUCT SIZE ON A/C # 1 TRUNK LINE | | 4) MECHANICAL PLAN AND PROPOSED FLOOR PLAN DO NOT | | MATCH. | | PER SECTION 107.2.1.3 CITY AMENDMENTS. | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-03-17 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-03-17 |
Time |
14:06 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-03-13 |
Time |
13:39 |
Sent To |
|
|
Notes |
2020-03-17 14:07:19 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT- 20030355 | | | | CODES IN EFFECT: | | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) IDENTIFY AHU?S ON DRAWINGS. | | | | 2) PLEASE PROVIDE A DETAIL DRAWING OF THE RETURN DUCT | | IN HALL THAT BEDROOM 2 AND 3 ARE DUCTED TO, THE A | | SHEETS SHOW THIS AREA IS A CLOSET. RETURN AIR CANNOT | | COME FROM A CLOSET OR THE MASTER BATH UPSTAIRS. | | (. SEE FBCEC 103.2 INFORMATION ON CONSTRUCTION | | DOCUMENTS.)(SEE FBC RES M1602.2 (4) RETURN AIR SHALL | | NOT BE TAKEN FROM A CLOSET, BATHROOM, TOILET ROOM, | | KITCHEN, GARAGE, MECHANICAL ROOM, BOILER ROOM, FURNACE | | ROOM OR UNCONDITIONED ATTIC. | | | | 3) AHU?S IN ATTIC MUST MEET SECTION FBC RES M1305.1.3 | | APPLIANCES IN ATTIC. SEE ALSO FBC EC R403.3.6 | | | | 4) DUCTWORK IN THE GARAGE MUST MEET FBC RES R302.5.2 | | | | 5) PROVIDE SPEC SHEETS FOR THE HOOD AND THE RANGE, ALSO | | PROVIDE FUEL SOURCE FOR THE NEW RANGE. | | (. SEE FBCEC 103.2 INFORMATION ON CONSTRUCTION | | DOCUMENTS.) | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2020-05-08 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-05-08 |
Time |
06:32 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-05-08 |
Time |
06:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-03-19 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-03-19 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-03-19 |
Time |
13:25 |
Sent To |
|
|
Notes |
2020-03-19 14:01:44 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY PLUMBING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT PLUMBING RISER PLANS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2020-05-07 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2020-05-07 |
Time |
|
Rev Time |
0.00 |
Received By |
llouie |
Date |
2020-05-07 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-03-17 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2020-03-17 |
Time |
|
Rev Time |
|
Received By |
llouie |
Date |
2020-03-17 |
Time |
|
Sent To |
|
|
Notes |
2020-03-17 15:40:15 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) UPDATED, SIGNED AND SEALED SURVEY OF THE PROPERTY | | IS REQUIRED. | | | | 2.) CHANGES DETECTED TO THE EXISTING BUILDING | | FOOTPRINT. A SITE PLAN, SHOWING THE PROPOSED | | IMPROVEMENT AND DISTANCE FROM THE PROPERTY LINE(S) IS | | REQUIRED. INCLUDE LOCATION AND SETBACKS FOR NEW A/C | | UNIT. | | | | 3.) ONLY ONE KITCHEN IS PERMITTED IN THE RESIDENCE. | | THERE ARE TWO (2) KITCHENS IN THE PROPOSED FIRST FLOOR | | PLAN. | | | | 4.) PROPOSED BUILDING ELEVATIONS MISSING. | | | | 5.) ALL ARCHITECTURAL PLANS MUST BE SIGNED AND SEALED | | BY A FLORIDA REGISTERED ARCHITECT. | | | | | | | | NOTES: | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | QUESTIONS. | | | | * DOES NOT TRIGGER THE 50% THRESHOLD FOR LANDSCAPE | | IMPROVEMENTS (VALUE OF SCOPE OF WORK: $108,000; VALUE | | OF IMPROVEMENT (PER 2019 PAPA): $267,186) | | | | * ZONE: SF7 | | |
|
|