Plan Review Details - Permit 20030302
Plan Review Stops For Permit 20030302
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-06-16 Cont ID  
Sent By rmcphers Date 2020-06-16 Time 08:39 Rev Time 0.00
Received By rmcphers Date 2020-06-16 Time 08:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-05-28 Cont ID  
Sent By rmcphers Date 2020-05-28 Time 13:47 Rev Time 0.00
Received By rmcphers Date 2020-05-28 Time 13:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-13 Cont ID  
Sent By rmcphers Date 2020-03-13 Time 16:25 Rev Time 0.00
Received By rmcphers Date 2020-03-13 Time 14:53 Sent To  
Notes
2020-03-13 16:25:34REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE WOOD BEAM SPAN DIMENSION.
 2) PLEASE SHOW THE MANUFACTURE AND TYPE OF LAMINATED
 WOOD BEAM AND COLUMNS TO COMPLY WITH FBC R602.1.3
 3) PLEASE SHOW ALL ATTACHMENT HARDWARE TYPE - (NUMBER
 AND SIZE OF BOLTS, NUMBER AND SIZE OF NAILS ETC) FOR
 THE STRAPPING AND BUCKETS.
 4) PLEASE SHOW THE HEIGHT FROM FINISHED FLOOR TO THE
 BOTTOM OF THE BEAM.
 5) PLEASE SHOW THE NAILING SIZE AND ON CENTER NAILING
 SPACING FOR THE 2 PLY LVL BEAM.
 6) PLEASE PROVIDE SIGNED AND SEALED DETAILS FOR THE
 HELICAL PILING TO COMPLY WITH FBC 1810.3.1.5
 7) PLEASE PROVIDE WRITTEN INFORMATION ON WHO WILL BE
 INSPECTING THE HELICAL PILING INSTALLATION PER FBC
 110.3.9

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-06-04 Cont ID  
Sent By cthroop Date 2020-06-04 Time 08:22 Rev Time 0.00
Received By cthroop Date 2020-06-04 Time 07:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-26 Cont ID  
Sent By rmcdouga Date 2020-03-26 Time 10:12 Rev Time 0.00
Received By rmcdouga Date 2020-03-26 Time 09:17 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-06-22 Cont ID  
Sent By medwards Date 2020-06-22 Time 11:29 Rev Time 0.00
Received By medwards Date 2020-06-22 Time 11:29 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-05-26 Cont ID  
Sent By medwards Date 2020-05-26 Time 14:07 Rev Time 0.00
Received By medwards Date 2020-05-26 Time 13:52 Sent To  
Notes
2020-05-26 14:08:181ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20030302
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THE LOCATION OF THE GAS METER ON THE
 FLOOR PLAN. FBC FS 107.2.1
  
 2) PLEASE SPECIFY WHERE THE REGULATOR IS LOCATED,
 INSIDE OR OUTSIDE OF HOUSE? IF THE REGULATOR IS NOT
 OUTSIDE PLEASE SHOW WHERE IT WILL BE VENTED TO AND THE
 ACCESS FOR THE MP REGULATOR. FBC FS 107.2.1
  
 3) PLEASE PROVIDE THE PRESSURE DROP AND TABLES USED TO
 SIZE GAS LINES. FBC FS 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-06-22 Cont ID  
Sent By lmarchan Date 2020-06-22 Time 12:01 Rev Time 0.00
Received By lmarchan Date 2020-06-22 Time 11:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-16 Cont ID  
Sent By rmcphers Date 2020-06-16 Time 08:47 Rev Time 0.00
Received By rmcphers Date 2020-06-10 Time 15:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-04 Cont ID  
Sent By cthroop Date 2020-06-04 Time 08:22 Rev Time 0.00
Received By cthroop Date 2020-05-20 Time 13:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-26 Cont ID  
Sent By rmcdouga Date 2020-03-26 Time 10:12 Rev Time 0.00
Received By rmcdouga Date 2020-03-06 Time 13:31 Sent To  
Notes
2020-03-09 13:31:24R06

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-06-15 Cont ID  
Sent By medwards Date 2020-06-15 Time 14:16 Rev Time 0.00
Received By medwards Date 2020-06-15 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-05-26 Cont ID  
Sent By medwards Date 2020-05-26 Time 13:50 Rev Time 0.00
Received By medwards Date 2020-05-26 Time 12:14 Sent To  
Notes
2020-05-26 13:51:09REVIEW FBC-2017 MECHANICAL
 PERMIT-20030302
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW HOW THIS COMMERCIAL RANGE MODEL #
 PRD486WDGU MEETS FBC M 917.2 FOR RESIDENTIAL USE.
  
 2) PLEASE PROVIDE THE INSTALLATION INSTRUCTIONS AND
 SPECS FOR BOTH THE RANGE AND THE HOOD THAT IS
 RECOMMENDED BY THE MANUFACTURER OF THE RANGE. FBC FS
 107.2.1
  
 3) THE RANGE SHOWN ON THIS PROJECT ( PRD486WDGU )
 REQUIRES 103,000BTU OF GAS. PLEASE SHOW THE
 MANUFACTURER RECOMMENDED HOOD ALONG WITH THE MAKEUP AIR
 FOR THE CFM?S REQUIRED FOR THIS HOOD. FBC FS 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-13 Cont ID  
Sent By medwards Date 2020-03-13 Time 10:48 Rev Time 0.00
Received By medwards Date 2020-03-12 Time 16:57 Sent To  
Notes
2020-03-13 10:51:031ST REVIEW FBC-2017 MECHANICAL
 PERMIT 20030302
  
 CODES IN EFFECT:
  
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 PLEASE PROVIDE THE SPEC SHEETS FOR THE NEW HOOD AND
 RANGE INCLUDING THE FUEL SOURCE. ARE YOU MOVING THE
 DUCT WORK THAT IS CONDITIONING THESE AREAS? PLEASE SHOW
 THE DUCT WORK FOR THE DRYER AND BATH EXHAUST, INCLUDING
 THE TERMINATION LOCATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-06-04 Cont ID  
Sent By cthroop Date 2020-06-04 Time 08:22 Rev Time 0.00
Received By cthroop Date 2020-06-04 Time 07:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-03-25 Cont ID  
Sent By lcrespo Date 2020-03-25 Time 14:03 Rev Time 0.00
Received By lcrespo Date 2020-03-25 Time 14:03 Sent To  
Notes
2020-03-25 14:04:3103/25/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-09-01 Cont ID  
Sent By pvalenti Date 2020-09-01 Time 10:22 Rev Time 0.00
Received By pvalenti Date 2020-09-01 Time 10:01 Sent To  
Notes
2020-09-01 10:23:40PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW APPROVED BY PAPER ORIGINAL SUBMITTALS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-06-29 Cont ID  
Sent By shill Date 2020-06-29 Time 07:54 Rev Time 0.00
Received By shill Date 2020-06-29 Time 07:54 Sent To  
Notes
2020-06-29 07:55:00PAPER ORIGINAL SUBMITTED, ONLY ONE PAGE, PLAN IS FIVE
 PAGES
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-22 Cont ID  
Sent By shill Date 2020-06-22 Time 11:07 Rev Time 0.00
Received By shill Date 2020-06-22 Time 11:07 Sent To  
Notes
2020-06-22 11:08:21PROVISO: SUBMIT PAPER ORIGINALS FOR NEW SHEETS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-06-16 Cont ID  
Sent By rmcphers Date 2020-06-16 Time 08:39 Rev Time 0.00
Received By rmcphers Date 2020-06-16 Time 08:39 Sent To  
Notes
2020-06-16 08:47:36DRAWING LABELED - 003_A102.PDF V2 - IN PROJECTDOX NEEDS
 TO BE ELECTRONICALLY SIGNED BY THE ARCHITECT OR
 ENGINEER OR AN ORIGINAL SIGNED AND SEALED DRAWING NEEDS
 TO BE DELIVERED TO THE FRONT DESK OF THE BUILDING DEPT
 ALONG WITH A "PLAN REVIEW REQUEST FORM". STATING THE
 DRAWING IS BEING DELIVERED BECAUSE YOUR DESIGNER DOES
 NOT HAVE AN ELECTRONIC SIGNATURE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-22 Cont ID  
Sent By shill Date 2020-05-22 Time 09:18 Rev Time 0.00
Received By shill Date 2020-05-22 Time 09:18 Sent To  
Notes
2020-05-22 09:19:20SIGNATURE DOCUMENTS RECEIVED (ONE SET PAPER S&S),
 ROUTED TO LIBRARY/ SH