Plan Review Details - Permit 20030202
Plan Review Stops For Permit 20030202
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-13 Cont ID  
Sent By ppetty Date 2020-03-13 Time 11:20 Rev Time 0.00
Received By ppetty Date 2020-03-13 Time 11:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-11 Cont ID  
Sent By pleduc Date 2020-03-11 Time   Rev Time 0.00
Received By pleduc Date 2020-03-11 Time 10:36 Sent To E
Notes
2020-03-11 10:38:35THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS
 APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS
  
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR
 ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH ELECTRICAL LOCK HARDWARE THAT PREVENTS
 EGRESS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE
 MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO UNLOCK THE DOOR LEAF IN THE DIRECTION OF
 EGRESS UPON DETECTION OF AN APPROACHING OCCUPANT.
 (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE
 DIRECTION OF EGRESS UPON LOSS OF POWER TO THE SENSOR OR
 TO THE PART OF THE ACCESS CONTROL SYSTEM THAT LOCKS THE
 DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 COMPLYING WITH ALL OF THE FOLLOWING CRITERIA:
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM )
 VERTICALLY ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM)
 OF THE SECURED DOOR OPENINGS.
 (B) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 AS FOLLOWS: PUSH TO EXIT.
 (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK
 INDEPENDENT OF THE LOCKING SYSTEM ELECTRONICS .AND THE
 LOCK SHALL REMAIN UNLOCKED FOR NOT LESS THAN 30
 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE
 FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY
 RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM
 SPECIFIED IN 7.2.1.6.2 (4) SHALL NOT BE REQUIRED TO
 UNLOCK THE DOOR LEAVES.
 (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE
 FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY
 RESET.
 (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS,
 OTHER THAN EXISTING ACCESS-CONTROLLED EGRESS DOORS,
 SHALL BE PROVIDED WITH EMERGENCY LIGHTING IN ACCORDANCE
 WITH SECTION 7.9.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-13 Cont ID  
Sent By ppetty Date 2020-03-13 Time 11:20 Rev Time 0.00
Received By ppetty Date 2020-03-04 Time 12:57 Sent To  
Notes
2020-03-05 12:57:25ROUTED TO FIRE INBOX