Plan Review Details - Permit 20030166
Plan Review Stops For Permit 20030166
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-05-05 Cont ID  
Sent By sathomas Date 2020-05-05 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-05-05 Time 00:00 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-11 Cont ID  
Sent By sathomas Date 2020-03-11 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-03-11 Time 00:00 Sent To M
Notes
2020-03-11 14:47:10PROVISO:
 WRONG BUSINESS NAME ON PLANS: THIS IS FOR AVANIT'S
 RESTURANT, NOT FIRED UP PIZZA.
  
 COOKING OPERATIONS PRODUCING SMOKE OR GREASE-LADEN
 VAPORS SHALL BE PROTECTED WITH A CLASS I MECHANICAL
 EXHAUST HOOD EQUIPPED WITH AN AUTOMATIC WET-CHEMICAL
 FIRE SUPPRESSION SYSTEM.
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
  
 FIRE SUPPRESSION SYSTEM TO BE SUBMITTED UNDER SEPARATE
 PERMIT.
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2020-05-18 Cont ID  
Sent By rsklarew Date 2020-05-18 Time 14:41 Rev Time 0.00
Received By rsklarew Date 2020-04-27 Time 14:14 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-27 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-04 Time 12:59 Sent To  
Notes
2020-03-05 13:00:04ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-04-30 Cont ID  
Sent By rsklarew Date 2020-05-18 Time 14:41 Rev Time 0.00
Received By pvalenti Date 2020-04-30 Time 09:33 Sent To  
Notes
2020-04-30 11:18:17PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 MECHANICAL HOOD REVIEW APPROVED.
  
 PROVISO: FBC M 506.3.2.5, A GREASE DUCT LEAKAGE TEST
 SHALL BE PERFORMED SUBJECT TO FIELD INSPECTOR'S
 APPROVAL.
  
 NOTE: THIS PERMIT DOES NOT INCLUDE GAS/STOVE EQUIPMENT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By ccole Date 2020-03-27 Time 16:59 Rev Time 0.00
Received By ccole Date 2020-03-27 Time 15:45 Sent To I
Notes
2020-03-27 17:31:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20030166
 3/27/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET H-1: THE NOTES INDICATE THE APPLICABLE
 COMPLIANCE CODE SECTIONS FROM THE FLORIDA MECHANCIAL
 CODE- 2014 FIFTH EDITION FOR NON-LISTED COMMERCIAL
 KITCHEN HOOD, HOWEVER THERE IS NO EVIDENCE ON THE PLAN
 THAT THE HOOD TO BE INSTALLED MEETS THOSE COMPLIANCES
 ORE THE 2017 APPLICABLE CODE SECTIONS. PLEASE UP DATE
 THE CODE SECTIONSIN THE NOTES AND PROVIDE A SCHEMATIC
 DRAWING OF THE HOOD AND A EQUIPMENT SCHEDULE THAT
 INDICATES COMPLIANCE WITH SECTIONS 507.1.5, 507.2.3,
 507.2.5, 507.2.8, & 507.4, & 507.5 FBC M.
  
 2) H-1: INDICATE COMPLIANCE WITH SECTION 508.1.1 FBC M
 WHICH REQUIRES THE TEMPERATURE DIFFERENTIAL BETWEEN THE
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE TO NOT
 EXCEED 10 DEGREES F.
  
 3) H-1: SHOW THE REQUIRED 18" CLEARANCE TO COMBUSTIBLES
 FOR THE GREASE EXHAUST DUCT INCLUDING THE PENETRATION
 THROUGH THE ROOF- SECTION 506.3.6 FBC M.
  
 4) H-1: SHOW THE REQUIRED 18" CLEARANCE TO COMBUSTIBLES
 FOR THE GREASE HOOD IN COMPLIANCE WITH SECTION 507.2.6
 FBC M. IF COMPLYING WITH THE EXCEPTION, PLEASE PROVIDE
 HOOD BACKING DIMENSIONS ON THE DRAWING TO SHOW PROPER
 EXTENSION COVERAGE.
  
 5) THE $12,900.00 VALUE ON THE APPLICATION APPEARS LOW
 FOR THE ENTIRE SCOPE OF WORK. PLEASE PROVIDE COPIES AOF
 SIGNED CONTRACTS AND/OR ESTIMATES, INVOICES ETC. TO
 VERIFY THE TOTAL COST. PLEASE NOTE THAT PERMIT VALUE IS
 BASED ON LABOR, MATERIALS AND EQUIPMENT- SECTION 109.3
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  