Plan Review Details - Permit 20030156
Plan Review Stops For Permit 20030156
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-03-18 Cont ID  
Sent By tklarge Date 2020-03-18 Time 10:12 Rev Time 0.00
Received By tklarge Date 2020-03-18 Time 10:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-03-14 Cont ID  
Sent By tklarge Date 2020-03-14 Time 02:55 Rev Time 0.00
Received By tklarge Date 2020-03-14 Time 02:42 Sent To  
Notes
2020-03-14 02:55:21COMBUSTION AIR IS REQUIRED FOR THE COOKTOP AND THE
 DRYER. PROVIDE VERIFICATION & CALCULATIONS HOW THE
 REQUIREMENTS ARE BEING MET.PROVIDE THE CODE SECTIONS
 FROM THE GAS CODE THAT YOU ARE USING IN THE DESIGN OF
 THE COMBUSTION AIR REQUIREMENTS. WPB AMEND. TO FBC SEC.
 107.2.1, FBC-FUEL GAS SEC.304.1.2ND REQUEST.
 NOTE: A NOTE HAS BEEN PLACED ON THE PLANS THAT READS
 "REQUIRES LOUVER DOOR OR VENT IN WALL." PLEASE READ THE
 PLAN REVIEW COMMENT AND REFER TO THE NOTED CODE
 SECTIONS. THE CODE REQUIRES CALCULATIONS, NOT A VAGUE
 NOTE THAT DOES NOT PROVIDE THE REQUIRED INFORMATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By tklarge Date 2020-03-06 Time 05:55 Rev Time 0.00
Received By tklarge Date 2020-03-06 Time 05:13 Sent To  
Notes
2020-03-06 05:55:211) SUBMIT A GAS RISER DIAGRAM WITH LEGIBLE INFORMATION
 ON IT. I CANNOT READ SOME OF THE PIPE SIZES BECAUSE THE
 SIZES ARE WRITTEN SO SMALL AND THEY ARE ILLEGIBLE. GO
 OVER THE LINES ON THE RISER. A COUPLE OF THEM ARE VERY
 LIGHT.WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE CORRESPONDING EHD (EQUIVALENT HYDRAULIC
 DIAMETER) FOR THE STANDARD PIPE SIZES FOR THE
 CORRUGATED STAINLEASS STEEL TUBING. 2017 FBC-FUEL GAS
 SEC. 402.1.
 3) COMBUSTION AIR IS REQUIRED FOR THE COOKTOP AND THE
 DRYER. PROVIDE VERIFICATION & CALCULATIONS HOW THE
 REQUIREMENTS ARE BEING MET.PROVIDE THE CODE SECTIONS
 FROM THE GAS CODE THAT YOU ARE USING IN THE DESIGN OF
 THE COMBUSTION AIR REQUIREMENTS. WPB AMEND. TO FBC SEC.
 107.2.1, FBC-FUEL GAS SEC.304.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-18 Cont ID  
Sent By tklarge Date 2020-03-18 Time 10:12 Rev Time 0.00
Received By tklarge Date 2020-03-18 Time 10:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-14 Cont ID  
Sent By tklarge Date 2020-03-14 Time 02:55 Rev Time 0.00
Received By tklarge Date 2020-03-11 Time 13:15 Sent To  
Notes
2020-03-12 13:15:47RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-06 Cont ID  
Sent By tklarge Date 2020-03-06 Time 05:55 Rev Time 0.00
Received By tklarge Date 2020-03-04 Time 13:43 Sent To  
Notes
2020-03-05 13:43:56REVISION ROUTED TO TKLARGE