Plan Review Details - Permit 20030023
Plan Review Stops For Permit 20030023
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-29 Cont ID  
Sent By lcrespo Date 2020-05-29 Time 15:35 Rev Time 0.00
Received By lcrespo Date 2020-05-22 Time 10:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-09 Cont ID  
Sent By lcrespo Date 2020-03-09 Time 12:00 Rev Time 0.00
Received By lcrespo Date 2020-03-02 Time 13:33 Sent To  
Notes
2020-03-03 13:33:32ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-05-29 Cont ID  
Sent By lcrespo Date 2020-05-29 Time 15:35 Rev Time 0.00
Received By lcrespo Date 2020-05-29 Time 15:35 Sent To  
Notes
2020-05-29 15:36:2505/29/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL,
 CONTRACTORS OR THEIR REPRESENTATIVES FROM THE
 RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-09 Cont ID  
Sent By lcrespo Date 2020-03-09 Time 12:01 Rev Time 0.00
Received By lcrespo Date 2020-03-09 Time 12:00 Sent To  
Notes
2020-03-09 12:02:5403/09/20 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PLAN IS TOO SMALL TO READ NOTES, PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8" INCH SCALE PER THE WPB
 AMENDMENT TO FBC SEC. 107.2.1.3 QUALITY OF BUILDING
 PLANS.
  
 2. THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS IF APPLICABLE
 PER THE FBC WPB AMENDMENTS SEC. 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
  
 3. IF IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED UNLESS THE APPLICANT CAN SHOW DETAILED, QUANTITY
 ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING
 LAND VALUE) TO MEET THE APPROVAL OF THE BUILDING
 OFFICIAL. FOR PERMITTING PURPOSES, THE VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 4. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE)
 ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471. WPB AMENDMENTS TO
 THE FBC SEC. 107.1 GENERAL.
  
 5. PLEASE NOTE ON PLANS THAT BACKFLOW WILL BE UNDER A
 SEPARATE PERMIT PER THE 2017 FBC WPB A 105.1.
  
 6. A BUILDING AND ELECTRICAL PERMIT IS REQUIRED BY A
 LICENSED CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 7. PLEASE GIVE THE LEVEL OF ALTERATION PER 2017 FLORIDA
 EXISTING BUILDING CODE 301.1.
  
 8. PROVIDE MINIMUM SANITARY FACILITIES ACCORDING TO
 2017 FBC P TABLE 403.1.
  
 9. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE
 LINING FBC R 2709.2.
  
 10. PLEASE SHOW DETAIL SHOWER PAN MUST HAVE A SLOPED
 MORTAR BED THAT IS PRE-PITCHED BENEATH PRIOR TO LINER
 INSTALLATION OF 1/4" IN PER FOOT TOWARD THE DRAIN, MUST
 HAVE DAM CORNER, BACKING AROUND THE PERIMETER AND
 BEFORE FINAL MORTAR APPLICATION PLACE SOME PEA GRAVEL
 OVER WEEP HOLES SO THE MORTAR DOES NOT COVER THEM PER
 MANUFACTURES SPECIFICATIONS.
  
 11. WHEN CHANGING TUB TO THE SHOWER WILL THERE BE A
 VALVE REPLACEMENT AND IF SO, IT MUST COMPLY WITH 2017
 FBC P SECTION 424.3. PLEASE PROVIDE A SPECIFICATION FOR
 THE SHOWER VALVE TYPE THAT COMPLIES. WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-05-29 Cont ID  
Sent By lcrespo Date 2020-05-29 Time 15:35 Rev Time 0.00
Received By lcrespo Date 2020-05-29 Time 15:35 Sent To  
Notes
***NONE***