Plan Review Details - Permit 20021294
Plan Review Stops For Permit 20021294
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-27 Cont ID  
Sent By rmcdouga Date 2020-05-27 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2020-05-27 Time 09:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-24 Cont ID  
Sent By pvalenti Date 2020-04-24 Time 11:48 Rev Time 0.00
Received By pvalenti Date 2020-04-24 Time 08:41 Sent To  
Notes
2020-04-24 12:27:05PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 AS NOTED ON 1ST REVIEW, PLEASE PROVIDE:
 A SIGNED CITY OF WEST PALM BEACH THRESHOLD INSPECTION
 AGREEMENT AND ON THE PLANS PROVIDE A THRESHOLD
 INSPECTION PLAN.
 A RECEIPT FROM PALM BEACH COUNTY DEPARTMENT OF HEALTH,
 FOR THE SWIMMING POOL.
 A RESPONSE LETTER ADDRESSING ALL OF THE ITEMS LISTED
 BELOW WILL BE VERY HELPFUL IN THE REVIEW PROCESS.
  
 1) SUBMIT A RECEIPT FROM THE PALM BEACH COUNTY HEALTH
 TO SHOW THAT AN APPLICATION AND THE REQUIRED
 INFORMATION HAS BEEN SUBMITTED TO THEM. FLORIDA
 STATUTES 514.03, APPROVAL NECESSARY TO CONSTRUCT,
 DEVELOP, OR MODIFY PUBLIC SWIMMING POOLS OR PUBLIC
 BATHING PLACES.
 (1) A PERSON OR PUBLIC BODY DESIRING TO CONSTRUCT,
 DEVELOP, OR MODIFY A PUBLIC SWIMMING POOL MUST SUBMIT
 AN APPLICATION, CONTAINING THE INFORMATION REQUIRED
 UNDER S. 514.031(1)(A)1.-6. TO THE DEPARTMENT FOR AN
 OPERATING PERMIT BEFORE FILING AN APPLICATION FOR A
 BUILDING PERMIT UNDER S. 553.79. A COPY OF THE FINAL
 INSPECTION REQUIRED UNDER S. 514.031(1)(A)5. SHALL BE
 SUBMITTED TO THE DEPARTMENT UPON RECEIPT BY THE
 APPLICANT. THE APPLICATION SHALL BE DEEMED INCOMPLETE
 PURSUANT TO S. 120.60 UNTIL SUCH COPY IS SUBMITTED TO
 THE DEPARTMENT.
 (2) LOCAL GOVERNMENTS OR LOCAL ENFORCEMENT DISTRICTS
 MAY DETERMINE COMPLIANCE WITH THE GENERAL CONSTRUCTION
 STANDARDS OF THE FLORIDA BUILDING CODE, PURSUANT TO S.
 553.80. LOCAL GOVERNMENTS OR LOCAL ENFORCEMENT
 DISTRICTS MAY CONDUCT PLAN REVIEWS AND INSPECTIONS OF
 PUBLIC SWIMMING POOLS AND PUBLIC BATHING PLACES FOR
 THIS PURPOSE.
 2) THIS PUBLIC POOL IS ASSOCIATED WITH AN R-2 OCCUPANCY
 AND IS SUBJECT TO THE FBC ACCESSIBILTY FOR ACCESSIBILE
 MEANS OF ENTRY PER SECTION 242 UNLESS IT IS EXEMPT.
 COMMUNITY POOLS THAT ARE ASSOCIATED WITH A PRIVATE
 RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL
 FINANCIAL ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO
 THE EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT
 COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS,
 INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES.
 IF A SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY
 IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS
 REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON
 THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER
 STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013?011.
 3) DUE TO THE STRUCTURAL NATURE OF THIS PROJECT AND THE
 REQUIREMENTS FOR SHORING, A THRESHOLD INSPECTOR WILL BE
 REQUIRED. THRESHOLD BUILDING / FL S. S. 553.71(7)
 "THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE?SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E?MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E?MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
 H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805?6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER
 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
 4) ADDITIONAL PERMITS WILL BE REQUIRED FOR ELECTRICAL,
 PLUMBING AND GAS. FBC 105.1
 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-05 Cont ID  
Sent By rmcdouga Date 2020-03-05 Time 19:06 Rev Time 0.00
Received By rmcdouga Date 2020-03-05 Time 17:05 Sent To  
Notes
2020-03-05 18:18:35PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A RECEIPT FROM THE PALM BEACH COUNTY HEALTH
 TO SHOW THAT AN APPLICATION AND THE REQUIRED
 INFORMATION HAS BEEN SUBMITTED TO THEM. FLORIDA
 STATUTES 514.03, APPROVAL NECESSARY TO CONSTRUCT,
 DEVELOP, OR MODIFY PUBLIC SWIMMING POOLS OR PUBLIC
 BATHING PLACES.
 (1) A PERSON OR PUBLIC BODY DESIRING TO CONSTRUCT,
 DEVELOP, OR MODIFY A PUBLIC SWIMMING POOL MUST SUBMIT
 AN APPLICATION, CONTAINING THE INFORMATION REQUIRED
 UNDER S. 514.031(1)(A)1.-6. TO THE DEPARTMENT FOR AN
 OPERATING PERMIT BEFORE FILING AN APPLICATION FOR A
 BUILDING PERMIT UNDER S. 553.79. A COPY OF THE FINAL
 INSPECTION REQUIRED UNDER S. 514.031(1)(A)5. SHALL BE
 SUBMITTED TO THE DEPARTMENT UPON RECEIPT BY THE
 APPLICANT. THE APPLICATION SHALL BE DEEMED INCOMPLETE
 PURSUANT TO S. 120.60 UNTIL SUCH COPY IS SUBMITTED TO
 THE DEPARTMENT.
 (2) LOCAL GOVERNMENTS OR LOCAL ENFORCEMENT DISTRICTS
 MAY DETERMINE COMPLIANCE WITH THE GENERAL CONSTRUCTION
 STANDARDS OF THE FLORIDA BUILDING CODE, PURSUANT TO S.
 553.80. LOCAL GOVERNMENTS OR LOCAL ENFORCEMENT
 DISTRICTS MAY CONDUCT PLAN REVIEWS AND INSPECTIONS OF
 PUBLIC SWIMMING POOLS AND PUBLIC BATHING PLACES FOR
 THIS PURPOSE.
  
 2) THIS PUBLIC POOL IS ASSOCIATED WITH AN R-2 OCCUPANCY
 AND IS SUBJECT TO THE FBC ACCESSIBILTY FOR ACCESSIBILE
 MEANS OF ENTRY PER SECTION 242 UNLESS IT IS EXEMPT.
 COMMUNITY POOLS THAT ARE ASSOCIATED WITH A PRIVATE
 RESIDENTIAL COMMUNITY THAT DO NOT RECEIVE GOVERNMENTAL
 FINANCIAL ASSISTANCE OR SPONSORSHIP AND ARE LIMITED TO
 THE EXCLUSIVE OF RESIDENTS AND THEIR GUESTS ARE NOT
 COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS,
 INCLUDING PROVISIONS FOR POOL LIFTS OR SLOPED ENTRIES.
 IF A SWIMMING POOL LOCATED IN A RESIDENTIAL COMMUNITY
 IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL OR USE IT IS
 REQUIRED TO COMPLY WITH TITLE II OF THE ADA. SPECIFY ON
 THE PLANS THE FORMER OR SHOW COMPLIANCE WITH THE LATTER
 STATEMENTS. SEE DECLARATORY STATEMENT, DS 2013-011.
  
 3) DUE TO THE STRUCTURAL NATURE OF THIS PROJECT AND THE
 REQUIREMENTS FOR SHORING, A THRESHOLD INSPECTOR WILL BE
 REQUIRED. THRESHOLD BUILDING / FL S. S. 553.71(7)
 "THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT.
 IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE CURRENT (OCTOBER
 2018) GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
 4) ADDITIONAL PERMITS WILL BE REQUIRED FOR ELECTRICAL,
 PLUMBING AND GAS. FBC 105.1
  
 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-06-10 Cont ID  
Sent By jpearson Date 2020-06-10 Time 12:57 Rev Time 0.00
Received By jpearson Date 2020-06-10 Time 12:26 Sent To  
Notes
2020-06-10 12:57:10APPROVED WITH PROVISO ON PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-07 Cont ID  
Sent By ppetty Date 2020-05-07 Time 12:43 Rev Time 0.00
Received By ppetty Date 2020-05-07 Time 12:43 Sent To  
Notes
2020-05-07 12:54:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5;
 WPB FBC 107.2.1
 2.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-24 Cont ID  
Sent By jpearson Date 2020-03-24 Time 15:04 Rev Time 0.00
Received By jpearson Date 2020-03-24 Time 15:04 Sent To I
Notes
2020-03-24 15:04:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-06-12 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-26 Time 08:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-11 Cont ID  
Sent By tklarge Date 2020-05-11 Time 09:53 Rev Time 0.00
Received By tklarge Date 2020-04-24 Time 14:31 Sent To  
Notes
2020-05-06 14:32:40TO PETER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-24 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-28 Time 15:38 Sent To  
Notes
2020-03-03 15:13:153/3 ROUTED TO POOL INBOX
2020-03-02 16:12:11ROUTED FROM ZONING TO PERMIT LIBRARIAN 3/3/20 EL
2020-02-28 15:38:10ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-06-12 Cont ID  
Sent By ccole Date 2020-06-12 Time 07:33 Rev Time 0.00
Received By ccole Date 2020-06-11 Time 11:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-05-11 Cont ID  
Sent By tklarge Date 2020-05-11 Time 09:53 Rev Time 0.00
Received By tklarge Date 2020-05-11 Time 06:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-16 Cont ID  
Sent By abelisle Date 2020-03-16 Time 11:17 Rev Time 0.00
Received By abelisle Date 2020-03-10 Time 20:57 Sent To  
Notes
2020-03-16 11:24:513/16/2020 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1-SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL OF THE SYSTEM COMPONENTS
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 2-SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE.
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9,
 4.4.9.1.
  
 3-SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN, PUMP, AND POOL HEATER. WPB AMENDMENTS TO FBC
 SEC. 107.2.1.
  
 4-A SEPARATE PERMIT IS REQUIRED FOR THE GAS/ PLUMBING
 INSTALLATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLANS EXAMINER
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-27 Cont ID  
Sent By rmcdouga Date 2020-05-27 Time 09:12 Rev Time 0.00
Received By rmcdouga Date 2020-05-27 Time 09:12 Sent To  
Notes
2020-05-27 09:14:56THE ELECTRONIC PLANS DO NOT HAVE THE ENGINEER'S DIGITAL
 SIGNATURE.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2020-05-27 Cont ID  
Sent By rmcdouga Date 2020-05-27 Time 09:15 Rev Time 0.00
Received By rmcdouga Date 2020-05-27 Time 09:15 Sent To  
Notes
2020-05-27 09:17:36THE CONTRACTOR'S AND OWNER'S NOTARIZED SIGNATURES ARE
 REQUIRED ON THE THRESHOLD INSPECTOR DOCUMENTS BEFORE
 THE PERMIT IS ISSUED.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-05-29 Cont ID  
Sent By elevesqu Date 2020-05-29 Time 14:52 Rev Time 0.00
Received By elevesqu Date 2020-05-29 Time 14:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-03-02 Cont ID  
Sent By elevesqu Date 2020-03-02 Time 16:11 Rev Time 0.00
Received By elevesqu Date 2020-03-02 Time 16:11 Sent To  
Notes
***NONE***