2020-03-28 08:19:32 | PLAN REVIEW - BUILDING |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER ? BUILDING - PX3169 |
| PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| (SFHA). DESIGN SHALL COMPLY WITH FBC R322 - FLOOD |
| RESISTANT CONSTRUCTION. |
| R322.1.2STRUCTURAL SYSTEMS. |
| STRUCTURAL SYSTEMS OF BUILDINGS AND STRUCTURES SHALL BE |
| DESIGNED, CONNECTED AND ANCHORED TO RESIST FLOTATION, |
| COLLAPSE OR PERMANENT LATERAL MOVEMENT DUE TO |
| STRUCTURAL LOADS AND STRESSES FROM FLOODING EQUAL TO |
| THE DESIGN FLOOD ELEVATION. |
| R322.1.3FLOOD-RESISTANT CONSTRUCTION. |
| BUILDINGS AND STRUCTURES ERECTED IN AREAS PRONE TO |
| FLOODING SHALL BE CONSTRUCTED BY METHODS AND PRACTICES |
| THAT MINIMIZE FLOOD DAMAGE. |
| |
| 2. PROTECTION OF MECHANICAL EQUIPMENT REQUIRED. |
| R322.1.6PROTECTION OF MECHANICAL, PLUMBING AND |
| ELECTRICAL SYSTEMS. |
| ELECTRICAL SYSTEMS, EQUIPMENT AND COMPONENTS; HEATING, |
| VENTILATING, AIR CONDITIONING; PLUMBING APPLIANCES AND |
| PLUMBING FIXTURES; DUCT SYSTEMS; AND OTHER SERVICE |
| EQUIPMENT SHALL BE LOCATED AT OR ABOVE THE ELEVATION |
| REQUIRED IN SECTION R322.2 OR R322.3. |
| |
| 3. R322.2.2 ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION. |
| ENCLOSED AREAS, INCLUDING CRAWL SPACES, THAT ARE BELOW |
| THE DESIGN FLOOD ELEVATION SHALL: |
| 1. 1.BE USED SOLELY FOR PARKING OF VEHICLES, BUILDING |
| ACCESS OR STORAGE. |
| 2. 2.BE PROVIDED WITH FLOOD OPENINGS THAT MEET THE |
| FOLLOWING CRITERIA AND ARE INSTALLED IN ACCORDANCE WITH |
| SECTION R322.2.2.1: |
| 2.1.THE TOTAL NET AREA OF NON-ENGINEERED OPENINGS |
| SHALL BE NOT LESS THAN 1 SQUARE INCH (645 MM2) FOR EACH |
| SQUARE FOOT (0.093 M2) OF ENCLOSED AREA WHERE THE |
| ENCLOSED AREA IS MEASURED ON THE EXTERIOR OF THE |
| ENCLOSURE WALLS, OR THE OPENINGS SHALL BE DESIGNED AS |
| ENGINEERED OPENINGS AND THE CONSTRUCTION DOCUMENTS |
| SHALL INCLUDE A STATEMENT BY A REGISTERED DESIGN |
| PROFESSIONAL THAT THE DESIGN OF THE OPENINGS WILL |
| PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD FORCES ON |
| EXTERIOR WALLS BY ALLOWING FOR THE AUTOMATIC ENTRY AND |
| EXIT OF FLOODWATERS AS SPECIFIED IN SECTION 2.7.2.2 OF |
| ASCE 24. |
| 2.2.OPENINGS SHALL BE NOT LESS THAN 3 INCHES (76 MM) |
| IN ANY DIRECTION IN THE PLANE OF THE WALL. |
| 2.3.THE PRESENCE OF LOUVERS, BLADES, SCREENS AND |
| FACEPLATES OR OTHER COVERS AND DEVICES SHALL ALLOW THE |
| AUTOMATIC FLOW OF FLOODWATER INTO AND OUT OF THE |
| ENCLOSED AREAS AND SHALL BE ACCOUNTED FOR IN THE |
| DETERMINATION OF THE NET OPEN AREA. |
| |
| |
| 4. ELEVATION CERTIFICATE REQUIRED. - SEE NFIP REVIEW |
| FBC 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY) & |
| R322.2.1 ELEVATION REQUIREMENTS. BUILDINGS AND |
| STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS |
| COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED |
| TO OR ABOVE THE DESIGN FLOOD ELEVATION. PROVIDE FLOOD |
| DESIGN INFORMATION ON THE PROPOSED SURVEY AND PROVIDE |
| FLOOD ELEVATION CERTIFICATE. |
| |
| 5. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED. |
| PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE |
| PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE |
| RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS |
| APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD |
| MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
| |
| 6. PROVIDE ICYNENE INSULATION ICC - ES REPORT. SELECT |
| PRODUCT TO BE INSTALLED. REPORT TO BE ON SITE FOR CITY |
| INSPECTOR. |
| |
| 7. PROVIDE GENERATOR INSTALLATION INSTRUCTIONS. |
| SPECIFICALLY, PROVIDE ATTACHEMENT DETAIL. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 8. PROVIDE NOA'S FOR PRE-CAST LINTELS. |
| FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 9. PROVIDE STRUCTURAL DETAILS FOR NEW SITE WALLS. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 10. IDENTIFY THE TYPE OF FUEL SUPPLY TO PROPOSED BBQ |
| GRILL. IF NATURAL GAS PROVIDE SEPERATE GAS PERMIT WITH |
| GAS RISER DIAGRAHM. IF REMOVEABLE LP TANK PROVIDE |
| DETAIL OF CABINET SHOWING REQUIRED VENTS. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |