2020-03-05 08:21:04 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF |
| PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN |
| HEADING ?WALL PRESSURE?; PROVIDE THE ACTUAL [PSF] FROM |
| THE SUBMITTED ENGINEERS ASCE 7-10 DESIGN WIND LOADS; |
| FOLLOW INSTRUCTIONS FOR TABLE USE #3 THRU 3.3. PLEASE |
| CORRECT COLUMN HEADING ?ANCHOR SPACING?; PROVIDE |
| INFORMATION FROM PAGE 10 OF FL13757-R6. EXAMPLE: |
| MAXIMUM A.S.D. DESIGN PRESSURE RATING (P.S.F.) 62.0 OR |
| LESS, MAXIMUM SPAN 8?-8?; MOUNT TYPE C4; ANCHOR TYPE |
| ITW TAPCON; HOST STRUCTURE CONCRETE; 2.5? MINIMUM EDGE |
| DISTANCE MAXIMUM ANCHOR SPACING IS 7?. |
| |