Plan Review Details - Permit 20021104
Plan Review Stops For Permit 20021104
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-03-24 Cont ID  
Sent By jbrooks Date 2020-03-24 Time 14:31 Rev Time 0.00
Received By jbrooks Date 2020-03-24 Time 14:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-03-17 Cont ID  
Sent By jbrooks Date 2020-03-17 Time 09:03 Rev Time 0.00
Received By jbrooks Date 2020-03-17 Time 09:03 Sent To  
Notes
2020-03-17 09:03:30JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ?ANCHOR SPACING? PROVIDE INFORMATION FROM SHEET
 13 FL1850-R11. EXAMPLE SUBSTRATE POURED CONCRETE,
 MAXIMUM SPAN 8?-0?, A.S.D DESIGN NEGATIVE PRESSURE
 RATING (PSF) 120; CEILING MOUNT (G) USING TAPCONS WITH
 ADVANCED THREADFORM TECHNOLOGY ANCHOR SPACING IS 5.5?
 MAXIMUM. SECOND REQUEST.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-12 Cont ID  
Sent By jbrooks Date 2020-03-12 Time 08:40 Rev Time 0.00
Received By jbrooks Date 2020-03-12 Time 08:40 Sent To  
Notes
2020-03-12 08:42:07JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT THE
 FOLLOWING: COLUMN HEADING ?WALL PRESSURE?; PROVIDE THE
 ACTUAL [PSF] FROM THE SUBMITTED ENGINEERS ASCE 7-10
 DESIGN WIND LOADS. COLUMN HEADING ?ANCHOR SPACING?
 PROVIDE INFORMATION FROM SHEET 13 FL1850-R11. EXAMPLE
 SUBSTRATE POURED CONCRETE, MAXIMUM SPAN 8?-0? A.S.D
 DESIGN NEGATIVE LOAD (PSF) 120; CEILING MOUNTING (G)
 USING TAPCON WITH ADVANCED THREADFORM TECHNOLOGY ANCHOR
 SPACING IS 5.5? MAXIMUM.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-27 Cont ID  
Sent By jbrooks Date 2020-02-27 Time 09:03 Rev Time 0.00
Received By jbrooks Date 2020-02-27 Time 09:03 Sent To  
Notes
2020-02-27 09:03:41JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC B 1609. PROVIDE TWO SETS OF SIGNED AND SEALED
 DESIGN PRESSURE CALCULATIONS FOR HIGH RISE BUILDINGS BY
 A FLORIDA REGISTERED DESIGN PROFESSIONAL.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-03-24 Cont ID  
Sent By jbrooks Date 2020-03-24 Time 14:31 Rev Time 0.00
Received By jbrooks Date 2020-03-19 Time 09:55 Sent To  
Notes
2020-03-19 09:56:05RESUB ROUTED TO JBROOKS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-17 Cont ID  
Sent By jbrooks Date 2020-03-17 Time 09:03 Rev Time 0.00
Received By jbrooks Date 2020-03-13 Time 13:01 Sent To  
Notes
2020-03-16 13:01:29RESUB ROUTED TO JBROOKS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-12 Cont ID  
Sent By jbrooks Date 2020-03-12 Time 08:42 Rev Time 0.00
Received By jbrooks Date 2020-03-10 Time 13:18 Sent To  
Notes
2020-03-11 13:18:11RESUB ROUTED TO JBROOKS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-27 Cont ID  
Sent By jbrooks Date 2020-02-27 Time 09:04 Rev Time 0.00
Received By jbrooks Date 2020-02-25 Time 10:22 Sent To  
Notes
2020-02-26 10:23:09BLDG MISC 1