Plan Review Details - Permit 20021087
Plan Review Stops For Permit 20021087
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-04-01 Cont ID  
Sent By jgomez Date 2020-04-01 Time 12:40 Rev Time 0.00
Received By jgomez Date 2020-04-01 Time 12:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-16 Cont ID  
Sent By jgomez Date 2020-03-16 Time 10:37 Rev Time 0.00
Received By jgomez Date 2020-03-16 Time 10:31 Sent To  
Notes
2020-03-16 10:42:59PROVISO:
 SEPARATE FIRE SPRINKLER PERMIT REQUIRED.
  
  
 03/16/2020 TALKED TO JESSICA (ARCHITECT):
 1) USING 4" STUD FOR FIRE RATED HORIZONTAL SHAFT
 ASSEMBLY.
 2) FIRE RATED WALL ASSEMBLY COULD NOT GO ALL THE WAY UP
 BECAUSE OF ISSUES WITH THE DUCTWORK. THE HORIZONTAL
 SHAFT ASSEMBLY WAS USED ISOLATE THE ROOM FROM THE
 CORRIDOR.
 NOTE: ACCORDING TO TABLE 1020.1 CORRIDOR FIRE
 RESISTANCE IS NOT REQUIRED IF THE BUILDING IS FULLY
 SPRINKLERED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-13 Cont ID  
Sent By jgomez Date 2020-03-13 Time 20:01 Rev Time 0.00
Received By jgomez Date 2020-03-13 Time 10:43 Sent To  
Notes
2020-03-13 20:02:03REVISION BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- SPECIFY THE SIZE AND ORIENTATION OF THE I STUDS TO
 VERIFY COMPLIANCE WITH THE MAXIMUM HORIZONTAL SPAN FOR
 I-STUD ASSEMBLIES AS SHOWN ON THE TABLE OF USG ASSEMBLY
 SUBMITTED ON SHEET A2.1.1.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- CLARIFY WHY THE FIRE RATED PARTITION WAS REVISED AND
 DOESN'T GO ALL THE WAY UP TO THE BOTTOM OF THE CEILING.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-18 Cont ID  
Sent By jpearson Date 2020-03-18 Time 13:06 Rev Time 0.00
Received By jpearson Date 2020-03-18 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-09 Cont ID  
Sent By pleduc Date 2020-03-09 Time   Rev Time 0.00
Received By pleduc Date 2020-03-09 Time 16:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-01 Cont ID  
Sent By jgomez Date 2020-04-01 Time 12:40 Rev Time 0.00
Received By jgomez Date 2020-03-31 Time 13:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-31 Cont ID  
Sent By shill Date 2020-03-31 Time 10:03 Rev Time 0.00
Received By shill Date 2020-03-24 Time 09:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-24 Cont ID  
Sent By lmarchan Date 2020-03-24 Time 07:44 Rev Time 0.00
Received By lmarchan Date 2020-03-04 Time 09:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-04-01 Cont ID  
Sent By medwards Date 2020-04-01 Time 08:33 Rev Time 0.00
Received By medwards Date 2020-04-01 Time 07:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-03-30 Cont ID  
Sent By medwards Date 2020-03-27 Time 10:18 Rev Time 0.00
Received By medwards Date 2020-03-27 Time 09:47 Sent To  
Notes
2020-03-27 10:18:512ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20021087
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.1- PLEASE UPDATE THIS SHEET TO REFERENCE
 THE CORRECT FIRE RATED DIFFUSERS.
  
 2) PLEASE PROVIDE A DETAIL DRAWING OF THE SPECIFIED
 DIFFUSERS IN THE SPECIFIED UL CEILING ASSEMBLY. THE
 DIFFUSER MUST GO ALL THE WAY THROUGH THE ASSEMBLY. FBC
 FS107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By ccole Date 2020-03-23 Time 11:09 Rev Time 0.00
Received By medwards Date 2020-03-17 Time 16:28 Sent To  
Notes
2020-03-23 11:10:081ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20021087
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW HOW YOU ARE GOING TO PROTECT THE RATED
 CEILING IN THE NEW CONFERENCE ROOM. THIS IS A UL FIRE
 RATED ASSEMBLY. PROVIDE SPEC SHEETS FOR THE UL APPROVED
 DAMPERS APPROVED FOR THIS RATED ASSEMBLY. FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-01 Cont ID  
Sent By medwards Date 2020-04-01 Time 08:33 Rev Time 0.00
Received By medwards Date 2020-04-01 Time 08:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-03-23 Cont ID  
Sent By medwards Date 2020-03-23 Time 10:42 Rev Time 0.00
Received By medwards Date 2020-03-23 Time 10:42 Sent To  
Notes
2020-03-23 11:11:151ST REVIEW SIGNATURES ARE APPROVED. ANY CHANGES TO
 SHEETS MUST BE REVIEWED FOR SIGNATURES.
2020-03-18 13:06:45ELECTRICAL SHEETS OK.