Plan Review Stops For Permit 20021087 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2020-04-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-04-01 |
Time |
12:40 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-04-01 |
Time |
12:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2020-03-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-03-16 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-03-16 |
Time |
10:31 |
Sent To |
|
|
Notes |
2020-03-16 10:42:59 | PROVISO: | | SEPARATE FIRE SPRINKLER PERMIT REQUIRED. | | | | | | 03/16/2020 TALKED TO JESSICA (ARCHITECT): | | 1) USING 4" STUD FOR FIRE RATED HORIZONTAL SHAFT | | ASSEMBLY. | | 2) FIRE RATED WALL ASSEMBLY COULD NOT GO ALL THE WAY UP | | BECAUSE OF ISSUES WITH THE DUCTWORK. THE HORIZONTAL | | SHAFT ASSEMBLY WAS USED ISOLATE THE ROOM FROM THE | | CORRIDOR. | | NOTE: ACCORDING TO TABLE 1020.1 CORRIDOR FIRE | | RESISTANCE IS NOT REQUIRED IF THE BUILDING IS FULLY | | SPRINKLERED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-03-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-03-13 |
Time |
20:01 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-03-13 |
Time |
10:43 |
Sent To |
|
|
Notes |
2020-03-13 20:02:03 | REVISION BUILDING REVIEW CHECKLIST. | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- SPECIFY THE SIZE AND ORIENTATION OF THE I STUDS TO | | VERIFY COMPLIANCE WITH THE MAXIMUM HORIZONTAL SPAN FOR | | I-STUD ASSEMBLIES AS SHOWN ON THE TABLE OF USG ASSEMBLY | | SUBMITTED ON SHEET A2.1.1. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | 2- CLARIFY WHY THE FIRE RATED PARTITION WAS REVISED AND | | DOESN'T GO ALL THE WAY UP TO THE BOTTOM OF THE CEILING. | | SEC. 107.2.1 CITY AMENDMENTS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2020-03-18 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2020-03-18 |
Time |
13:06 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2020-03-18 |
Time |
13:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2020-03-09 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-03-09 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-03-09 |
Time |
16:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2020-04-01 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2020-04-01 |
Time |
12:40 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-03-31 |
Time |
13:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2020-03-31 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2020-03-31 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2020-03-24 |
Time |
09:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-03-24 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2020-03-24 |
Time |
07:44 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-03-04 |
Time |
09:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2020-04-01 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-04-01 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-04-01 |
Time |
07:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2020-03-30 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-03-27 |
Time |
10:18 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-03-27 |
Time |
09:47 |
Sent To |
|
|
Notes |
2020-03-27 10:18:51 | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT-20021087 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M0.1- PLEASE UPDATE THIS SHEET TO REFERENCE | | THE CORRECT FIRE RATED DIFFUSERS. | | | | 2) PLEASE PROVIDE A DETAIL DRAWING OF THE SPECIFIED | | DIFFUSERS IN THE SPECIFIED UL CEILING ASSEMBLY. THE | | DIFFUSER MUST GO ALL THE WAY THROUGH THE ASSEMBLY. FBC | | FS107.2.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-03-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2020-03-23 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-03-17 |
Time |
16:28 |
Sent To |
|
|
Notes |
2020-03-23 11:10:08 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT- 20021087 | | | | CODES IN EFFECT: | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE SHOW HOW YOU ARE GOING TO PROTECT THE RATED | | CEILING IN THE NEW CONFERENCE ROOM. THIS IS A UL FIRE | | RATED ASSEMBLY. PROVIDE SPEC SHEETS FOR THE UL APPROVED | | DAMPERS APPROVED FOR THIS RATED ASSEMBLY. FBC 107.2.1 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2020-04-01 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-04-01 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-04-01 |
Time |
08:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2020-03-23 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-03-23 |
Time |
10:42 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-03-23 |
Time |
10:42 |
Sent To |
|
|
Notes |
2020-03-23 11:11:15 | 1ST REVIEW SIGNATURES ARE APPROVED. ANY CHANGES TO | | SHEETS MUST BE REVIEWED FOR SIGNATURES. | 2020-03-18 13:06:45 | ELECTRICAL SHEETS OK. |
|
|